Description du modèle: ACS355 machinery drive frequency convertisseur; 03E = 3-phase input, IP20 enclosure; 07A3 = rated output 7.3 UN; 4 = 380–480 V voltage class
Numéro de pièce: 3AUA0000058188
✅ Spécifications électriques de base
Puissance nominale: 3.0 kW (light overload / droit standard)
Rated Output Current I₂ₙ: 7.3 UN
Saisir: 3-phase 380–480 V ±10%, 48–63 Hz
Sortir: 0 ~ Uₙ, 0–599 Hz
Enclosure Protection: IP20 (without +B063 or other options)
Taille du cadre: R0
Refroidissement: Refroidissement par air
Moteur compatible: 3 kW 3-phase asynchronous motor
📦 Dimensions & Poids
Unité: W70 mm × H239 mm × D161 mm
Poids net: 1.8 kilos
Packaged Size: 350×220×130 mm, Poids brut 2.3 kilos
🧩 On-board I/O (Standard)
5 Entrées numériques (DEPUIS)
1 Sortie relais (RO)
2 Entrées analogiques (IA, 0–10 V / 4–20 mA)
1 Sortie analogique (AU, 4–20 mA)
Modbus RTU intégré (Terminal X1)
Optional plug-in communication adapters: Profibus-DP, CANopen, AppareilNet, EtherCAT, etc..
📌 Applications typiques
Machines générales: convoyeurs, les fans, pompes, mélangeurs, small processing machines. Supports standard V/F control and vector control, vitesses prédéfinies, ramps, multi-set parameter groups.
⚠️ Sélection & Notes de remplacement
- For IP66 version: add suffix +B063. Dimensions and weight differ completely, part number changes.
- Upgrade alternative within ABB portfolio: ACS380. Older ACS350 of the same power can be cross-referenced by current rating.
- Fusible / disjoncteur: sized per 7.3 A converter standard circuit. Output du/dt reactor is optional.
📎 Common Spare Parts & Accessoires
Control Panels: ACS-CP-A / ACS-CP-D
Input filter, output du/dt filter, résistance de freinage (braking chopper built-in)
Adaptateurs de communication, Modules d'extension d'E/S
ABB ACS355 (ACS355-03E-07A3-4)|Factory Default Parameters for ABB Standard Macro (9902=1)
Note: Parameters in Group 99 (données de la plaque signalétique du moteur) have no fixed default values. Enter data per 3 kW motor nameplate after power-up.
| Numéro de paramètre. | Nom du paramètre | Valeur par défaut | Remarques |
| 9902 | Application Macro Selection | 1 ABB Standard Macro | DI1 start, DI2 direction, AI1 reference; le plus largement utilisé |
| 9904 | Motor Control Mode | 3 Scalaire (V/F) | Facultatif: 1=Vector Speed, 2=Vector Torque |
| 9905 | Motor Rated Voltage | — | Follow nameplate; 380 V for standard 3 Moteur kW |
| 9906 | Courant nominal du moteur | — | Typical value for matched motor ≈6.2 A |
| 9907 | Motor Rated Frequency | — | 50 Hz for general asynchronous motors |
| 9908 | Motor Rated Speed | — | 1440 tr/min (4-pôle) |
| 9909 | Motor Rated Power | — | 3.0 kW |
| 1001 | Ext1 Start/Stop Command | 2 DI1 | DI1 closed = Run |
| 1002 | Ext Direction Command | 3 DI2 | DI2=0 Forward, DI2=1 Reverse |
| 1103 | Ext Reference 1 Sélection | 1 AI1 | AI1 0–10 V / 4–20 mA |
| 1105 | Ext Reference 1 Maximum | 50.0 Hz | Matches full-scale AI signal |
| 1201 | Constant Speed Selection | 0 Not Selected | Multi-speed via DI combination |
| 1301 | AI1 Minimum | 0.0 V | 0 V correspond à 0 Hz |
| 1302 | AI1 Maximum | 10.0 V | 10 V correspond à 50 Hz |
| 1304 | AI2 Minimum | 0.0 V | AI2 disabled by default |
| 1401 | Relay Output RO1 Source | 0 Ready | Output when drive is ready |
| 1501 | AO1 Signal Source | 102 Fréquence de sortie | AU: 4–20 mA mapped to 0–50 Hz |
| 1504 | AO1 Minimum Output | 4 mA | |
| 1505 | AO1 Maximum Output | 20 mA | |
| 2007 | Minimum Frequency | 0.0 Hz | |
| 2008 | Maximum Frequency | 50.0 Hz | |
| 2202 | Temps d'accélération 1 | 5.0 s | |
| 2203 | Temps de décélération 1 | 5.0 s | |
| 2102 | Stop Mode | 1 Coast Stop | 2=Ramp Stop |
| 2601 | U/F Ratio | 1 Linéaire | Squared for fan/pump duty |
| 3017 | Overcurrent Trip Limit | 4×I₂n | |
| 3025 | STO Function | 0 Alarm Only | Régler sur 1 triggers fault 0044 |
| 5302 | EFB Station Address | 1 | Modbus RTU Slave Address |
| 5303 | Débit en bauds | 9600 | |
| 5304 | Parité | 0 No Parity, 1 Stop Bit |
ACS355 Fault Code List (English with Troubleshooting Guidance)
| Code d'erreur | Nom du défaut | Description | Dépannage courant |
| 1 | SURINTENSITÉ | Output current exceeds trip threshold | Court-circuit moteur, dommages au câble, locked load, temps de rampe trop court, incorrect motor data |
| 2 | DC OVERVOLT | DC bus voltage too high | Décélération rapide, regenerative load, high supply voltage, manque de résistance de freinage |
| 3 | DEV OVERTEMP | IGBT module overtemperature | Blocked airflow, ventilateur en panne, température ambiante élevée, surcharge, mauvaise ventilation de l'armoire |
| 4 | SHORT CIRC | Motor-side short circuit | Motor winding short, phase-to-phase short on power cable, shorted output terminals |
| 6 | DC UNDERVOLT | DC bus voltage insufficient | Phase d'entrée manquante, open fuse/contact, voltage dip, undersized supply |
| 9 | MOT OVERTEMP | Estimated motor temperature exceeded | Surcharge du moteur, mauvais refroidissement, incorrect motor thermal protection settings |
| 16 | EARTH FAULT | Earth leakage on motor/power cable | Damaged cable insulation, motor insulation failure, moisture ingress |
| 22 | SUPPLY PHASE | Perte de phase d'entrée / 3-déséquilibre de phase | Fusible d'entrée grillé, poor contactor contacts, unbalanced 3-phase supply |
| 44 | SAFE TORQUE OFF (STO) | STO safety circuit activated | STO terminals not jumpered, safety loop open, parameter 3025=1 triggers fault |
| 28 | COMM ERROR | Built-in EFB bus communication break | Modbus wiring, résistance de terminaison, address conflict, master offline |
| 35 | AI1 LOSS | AI1 signal below fault threshold | Transmitter wire break, faulty sensor, threshold setting in 3021 |
| 36 | AI2 LOSS | AI2 signal loss | Broken AI2 wiring, faulty transmitter |
| 41 | ID RUN FAIL | Motor identification run failed | Wrong motor wiring, mismatched power rating, rotor bloqué |
| 51 | USER PARAM FAULT | Parameter set corrupted | Restore factory defaults and re-enter motor parameters |
| 71 | FAN FAULT | Cooling fan failure | Fan jammed, fan supply fault |
✅ Reset Methods: Panel RESET, DI reset, communication reset, cycle d'alimentation. Fault history stored in Group 04 paramètres.
Quick Operation
Réinitialisation d'usine: Paramètre 9606, enter RESET. The drive restarts and loads ABB Standard Macro defaults.
Installation Notes for ABB ACS355-03E-07A3-4 (Frame R0, IP20)
This unit is for cabinet installation only. Indice IP20, not suitable for direct outdoor exposure.
- Montage mécanique & Dissipation thermique
- Orientation de montage: Vertical upright installation is mandatory. Do not invert. Side mounting is permitted for R0 frame but vertical is preferred. Cooling air flows bottom-in, top-out; inverted mounting causes overheating fault 0003.
- Minimum Clearances
Top ≥75 mm, Bottom ≥75 mm; no mandatory side clearance, reserve space for maintenance.
Stacked multiple drives: hot exhaust from lower unit must not blow directly onto upper unit. Use baffles, staggered layout or independent air ducts.
- Mounting Options: Screw fixing or 35 Rail DIN standard de mm. Mounting base must be rigid and flame-retardant. Prevent conductive dust from entering the unit during drilling (risk of short circuit).
- Conditions ambiantes
Température ambiante: -10 ~ +50 °C; déclasser au-dessus 40 °C. Pas de condensation, pas de glaçage.
Altitude: Full rating ≤1000 m; derate with increasing altitude above 1000 m.
Prohibited environment: conductive dust, gaz corrosif, strong magnetic fields (near contactors / large single-core cables), heavy vibration or shock.
- Sécurité & Power-off Procedures (Critique)
After disconnection, attendez 5 minutes for DC bus capacitors to fully discharge before opening covers, wiring or measuring. Do not touch power terminals or internal PCB when powered.
For permanent magnet motors: motor may generate back EMF when rotating even with supply disconnected. Mechanically lock the shaft before working on motor cables.
Before power-up: Disconnect U2/V2/W2 at the converter, test motor insulation to earth with 1000 V megger. Do not energise if insulation is poor (≥100 MΩ @25°C for ABB motors).
Strictly forbidden: Connect mains supply to U2/V2/W2 output terminals, this will destroy the unit.
- Sélection des câbles, Routing & CEM
- Cable Recommendations
Motor cable: Symmetric shielded VFD cable preferred, reduces bearing currents and EMI. Unshielded standard cables often interfere with sensors and instruments.
Signaux analogiques (IA/Monde): Double-shielded twisted pair. DI/DO relay signals: shielded twisted pair. Separate power cables and control cables in different trunking, minimum gap ≥20 cm. Cross only at 90° where unavoidable.
Do not mix 24 V low-voltage and 220 V high-voltage circuits inside one cable.
- Shield Grounding Rules
360° shield termination with earthing clamp; avoid pigtail earthing (poor high-frequency EMC performance). Shield of motor cable grounded at both converter and motor ends.
PE conductor must be short, thick and connected reliably to cabinet earth bar.
- IL / Ungrounded Delta System: Remove internal EMC filter earth screw, otherwise earth fault 0016 may occur. Keep screw fitted for standard TN-S systems.
- Output-side Restrictions: Do not connect capacitors or surge suppressors to U2/V2/W2. For long motor cables (>50 m), fit output du/dt reactor to protect motor insulation.
- Couple aux bornes & STO Safety Circuit
Control terminal tightening torque: 0.4 N·m. Power terminals follow datasheet torque specification.
STO (Coupure sûre du couple): Factory fitted with jumper. If STO function is unused, STO terminals must be permanently jumpered. Open STO triggers fault 0044. For safety applications, wire to safety relay contacts.
Résistance de freinage (BRK+, BRK-): Utiliser un câble blindé, mount close to drive to minimise lead inductance.
- Input Protection, Mise à la terre & Auxiliary Devices
Fit circuit breaker or fuses on input side, sized for 7.3 Une note. Input AC reactor is recommended to reduce harmonic distortion.
Mise à la terre: PE conductors must be home-run separately to earth bar, do not daisy-chain. Never use neutral N as protective earth PE.
Cabinet ventilation: Install cabinet fans to keep internal temperature below 40 °C. Clean filters regularly to prevent blocked cooling paths.
- Pre-power-up Checklist
- Bornes de puissance: U1/V1/W1 supply, U2/V2/W2 motor, BRK+/braking resistor – verify connections.
- Circuits de contrôle: DI/AI/AO, STO jumper, mise à la terre du blindage.
- Insulation test passed, no short circuit or earth leakage.
- Air path unobstructed.
- Motor nameplate data ready; perform motor identification after first power-up.
- Installation-related Fault Quick Reference
0003 Overtemp: Blocked airflow, insufficient top/bottom clearance, montage inversé, high cabinet temperature
0016 Défaut de terre: Mise à la terre incorrecte du blindage, EMC screw not removed for IT system, damaged/wet motor cable
0044 STO Fault: STO terminals not jumpered, safety loop open
Fluctuating AI signals: Mixed power/control wiring, poor shield grounding, non-twisted analog cable
ABB ACS355 Model & Part Number List|03E 3-phase 380–480 V, IP20, Filtre CEM intégré, Version standard
Description du modèle:
03 = entrée triphasée; E = EMC filter enabled (50 Hz); trailing 4 = 380~480 V; +B063 = IP66 high protection variant (commande séparée)
Part Number format: 3AUA00000XXXXX (ABB part number, used for purchasing, quotation and customs declaration)
Tailles de cadre: R0/R1/R3/R4; built-in braking chopper and STO.
| Modèle | Puissance nominale kW | Output Current I₂N(UN) | Cadre | ABB Part Number (3AUA) |
| ACS355-03E-01A2-4 | 0.37 | 1.2 | R0 | 3AUA0000058186 |
| ACS355-03E-01A9-4 | 0.55 | 1.9 | R0 | 3AUA0000058243 |
| ACS355-03E-02A4-4 | 0.75 | 2.4 | R0 | 3AUA0000058187 |
| ACS355-03E-03A3-4 | 1.1 | 3.3 | R1 | 3AUA0000058184 |
| ACS355-03E-04A1-4 | 1.5 | 4.1 | R1 | 3AUA0000058185 |
| ACS355-03E-05A6-4 | 2.2 | 5.6 | R1 | 3AUA0000058189 |
| ACS355-03E-07A3-4 | 3 | 7.3 | R0 | 3AUA0000058188 |
| ACS355-03E-08A8-4 | 4 | 8.8 | R1 | 3AUA0000058190 |
| ACS355-03E-12A5-4 | 5.5 | 12.5 | R3 | 3AUA0000058191 |
| ACS355-03E-15A6-4 | 7.5 | 15.6 | R3 | 3AUA0000058192 |
| ACS355-03E-23A1-4 | 11 | 23.1 | R3 | 3AUA0000058193 |
| ACS355-03E-31A0-4 | 15 | 31 | R4 | 3AUA0000058195 |
| ACS355-03E-38A0-4 | 18.5 | 38 | R4 | 3AUA0000058194 |
| ACS355-03E-44A0-4 | 22 | 44 | R4 | 3AUA0000058196 |
Supplementary Range: 01E Single-phase 200–240 V, IP20, CEM intégrée
| Modèle | Power kW | Current A | Cadre | Numéro de pièce |
| ACS355-01E-02A4-2 | 0.37 | 2.4 | R0 | 3AUA0000058174 |
| ACS355-01E-04A7-2 | 0.75 | 4.7 | R1 | 3AUA0000058175 |
| ACS355-01E-06A7-2 | 1.1 | 6.7 | R1 | 3AUA0000058176 |
| ACS355-01E-07A5-2 | 1.5 | 7.5 | R2 | 3AUA0000058177 |
| ACS355-01E-09A8-2 | 2.2 | 9.8 | R2 | 3AUA0000058178 |
Accessoires communs & Part Numbers for ACS355
| Nom de l'accessoire | Modèle | Numéro de pièce |
| Basic Control Panel | ACS-CP-A | 3AUA0000040901 |
| Panneau de configuration adjoint (Chinois) | ACS-CP-D | 3AUA0000040902 |
| Profibus DP Adapter | FPBA-01 | 3AUA0000040888 |
| CANopen Adapter | FCAN-01 | 3AUA0000040889 |
| DeviceNet Adapter | FDNA-01 | 3AUA0000040890 |
| EtherCAT Adapter | FECA-01 | 3AUA0000040891 |
Suffix Options (added after model +xxxx)
+B063: IP66 high protection version (pour humide, dusty environments)
+N830: Non-coated PCB (standard cabinet version)
+J400: Potentiometer kit
Exemple: ACS355-03E-07A3-4+B063 (IP66 variant, numéro de pièce différent)
Model Code Guide for Export Selection
03E: 3-phase, EMC filter enabled (mainstream for China market) ✅
03U: 3-phase, EMC filter disabled (60 Hz overseas version)
03X: Export special version, not common locally
01E / 01U: Monophasé 220 V models
Replacement series: ACS380 (nouvelle génération, successor to ACS355)