This is a 15 kW, 380–480 V three-phase high-performance general-purpose inverter drive from Schneider Electric’s Altivar 71 série. It features a built-in Category A EMC filter, no graphical terminal, and integrated CANopen & Modbus communication. The rated output current is 39 Un à 480 V / 48 Un à 380 V. It uses flux vector control technology, suitable for precise speed and torque control of fans, pompes, compresseurs, and complex industrial machinery. Classe de protection: IP20. Standard mounting: 35 mm rail DIN.
- Explication du modèle
| Pièce du modèle | Description |
| VTT | Série de produits: Schneider Altivar inverter drives |
| 71 | ID de série: Altivar 71 high-performance general-purpose drive (vs. ATV61 dedicated to fans & pompes) |
| HD | Notation & application: HD = Heavy Duty (15 kW and above), for heavy-duty loads |
| 15 | Puissance nominale: 15 kW (20 HP) |
| N4 | Classe de tension: three-phase 380–480 V (-15% à +10%), 50/60 Hz |
| Z | Option code: no graphical terminal, built-in Category A EMC filter, integrated CANopen & Modbus |
- Spécifications de base
Electrical Data
| Article | Valeur | Remarques |
| Puissance nominale | 15 kW (20 HP) | For three-phase asynchronous motors |
| Tension d'entrée | Triphasé 380-480 V | Range: -15% à +10% |
| Input frequency | 50/60 Hz | Range: ±5% |
| Courant de sortie nominal | 39 UN (480 V) / 48 UN (380 V) | Continuous operational current |
| Tension de sortie | 0 à la tension d'entrée | PWM, three-phase AC |
| Fréquence de sortie | 0.1–599 Hz | Adjustable range |
| Fréquence de commutation | 1–16 kHz | Nominal 4 kHz, adjustable for cooling/noise |
| Control method | Flux vector control (with/without sensor) | Open loop 1:100, closed loop 1:1000 |
| Capacité de surcharge | 150% rated current for 60 s | For starting and shock loads |
| Efficacité | Environ. 97% | Haute efficacité, energy-saving design |
Mécanique & Environmental Data
| Article | Valeur | Remarques |
| Degré de protection | IP20 | Finger‑safe, suitable for cabinet mounting |
| Montage | 35 mm DIN rail or screw mounting | Standard industrial mounting |
| Dimensions (L×H×P) | Environ. 150×380×210 mm | Compact, space‑saving |
| Poids | Environ. 22 kilos | Easy handling and installation |
| Température de fonctionnement | -10 °C ~ +40 °C | Derate above 40 °C |
| Storage temperature | -25 °C ~ +70 °C | High‑reliability design |
| Relative humidity | 5%–95% | Non‑condensing |
| Altitude | ≤ 1000 m | Derate above 1000 m |
Communication & Interface Data
| Article | Configuration | Remarques |
| Standard communication | CANopen, Modbus RTU | Intégré |
| Optional communication | Profibus-DP, AppareilNet, EtherNet/IP | Via communication cards |
| Digital inputs | 6 configurable | 24 À DC, PNP/NPN selectable |
| Analog inputs | 2 configurable | 0–10 V ou 4–20 mA |
| Digital outputs | 2 relais + 2 transistor | Relay rating: 250 V et / 5 UN |
| Analog outputs | 1 | 0–10 V ou 4–20 mA |
- Caractéristiques
- High-performance control: flux vector control provides precise speed and torque control. Speed accuracy: ±0.5% open loop, ±0.01% closed loop.
- Energy saving: Built-in ENA (Energy Adaptation) system automatically optimizes V/F pattern and adjusts output according to load; energy savings up to 30%.
- Filtre CEM intégré: Category A filter as standard, reduces electromagnetic interference, complies with EN 55011.
- Protection complète:
Motor protection: surintensité, surcharge, overheat, perte de phase, rotor bloqué, earth fault
Drive protection: surtension, sous-tension, overheat, court-circuit, parameter fault
Mains protection: surge suppression, voltage fluctuation tolerance
- Flexible control functions:
Multi-speed setting (jusqu'à 16 speeds)
PID closed-loop regulation (alimentation en eau à pression constante, constant tension control)
Flying Start: smooth start while motor is rotating
Brake unit management: built-in brake unit for fast stopping
- Communication integration: CANopen & Modbus RTU as standard, seamless connection to PLC, IHM, and automation devices.
- Guide de sélection
Applications typiques
Industrial machinery: compresseurs, convoyeurs, mélangeurs, centrifugeuses
Building services: grands ventilateurs, pompes, Systèmes CVC
Material handling: grues, ascenseurs, convoyeurs
Applications requiring precise speed control and high dynamic response
Environments with strict EMC requirements
Principes de sélection
- Correspondance de charge:
Continuous loads (les fans, pompes): select 1:1 rated power
Intermittent loads (compresseurs, grues): 1.1–1.2 times power margin
Shock loads (concasseurs, presses): select HD series for 150% surcharge
- Voltage and power:
Supply: three-phase 380–480 V
Motor power ≤ 15 kW, current ≤ 39 UN (480 V) / 48 UN (380 V)
For higher power: ATV71HD 22 kW, 30 kW, etc..
- Control & communication:
Standard configuration for general use
Advanced communication (Profinet, EtherCAT) via option cards
Graphical terminal: models ending in N4 (par ex., ATV71HD15N4)
- Environnement:
Déclasser 1% par °C ci-dessus 40 °C
Déclasser 1% per 100 m above 1000 m
Additional protection for humid or corrosive environments
- Notes d'installation
- Pre-installation:
Verify model and inspect physical condition
Confirm input voltage matches mains supply
Prepare 35 mm DIN rail or mounting plate
Ensure sufficient cooling space in cabinet
- Installation procedure:
Mount vertically on 35 mm rail DIN
Keep at least 100 mm clearance for cooling
Circuit principal: L1/L2/L3 = input, U/V/W = motor
Circuit de commande: wire DI/DO/AIO and communication per diagram
Couple de la borne principale: M6 approx. 8 N·m, cable 16–35 mm²
- Sécurité:
Isolate and verify voltage-free before work
Separate power and control wiring
Use shielded motor cable (maximum. 50 m shielded, 100 m unshielded)
Earth resistance ≤ 4 Oh
Check motor and protection parameters before power-up
- Mise en service & maintenance:
Perform motor auto-tuning at first power-up
Test start/stop, speed adjustment, and protection
Inspect fan and capacitors annually
Keep unit clean and dust‑free
- Modèles alternatifs
Same‑series Alternatives
| Modèle | Différence | Application |
| ATV71HD15N4 | With graphical terminal | Local setting and monitoring |
| ATV71HU15N4Z | Standard duty (ci-dessous 15 kW) | Light loads, no heavy‑duty performance |
| ATV71HD22N4Z | 22 kW | Higher power requirements |
| ATV71HD15Y4Z | 525–690 V | High‑voltage mains |
Upgrade Alternatives
| Modèle | Mise à niveau | Application |
| ATV930D15N4 | ATV900 series, performances supérieures | Complex motion control, high precision |
| ATV630D15N4 | Ventilateur/pompe dédié | HVAC optimized for energy saving |
| ATV71HD15N4F | Enhanced filter | Stricter EMC requirements |
Budget Alternatives
| Modèle | Différence | Application |
| ATV71HU15N4Z | Standard duty, no HD performance | Stable loads, low dynamic response |
| ATV61HD15N4Z | Fan/pump series | Basic fan/pump control, rentable |
The Schneider Electric ATV71HD15N4Z is a high-performance, high-reliability general-purpose inverter drive. With flux vector control, filtre CEM intégré, complete protection, and flexible communication, it is an ideal choice for 15 kW applications in industrial automation. Proper selection, installation, and maintenance ensure long‑term reliable operation and deliver precise, efficient, energy‑saving speed control for various machinery.
Standard Selection Procedure for Schneider Inverter Drives
(Industrial general‑purpose, for sales / quotation / conception)
- Define Application & Série
General industrial machinery: compresseurs, convoyeurs, mixers → ATV71 series (haute performance, high dynamics)
Ventilateurs / Pumps / CVC: climatisation, water supply, ventilation → ATV61 series (dedicated algorithm, économie d'énergie)
Complex motion control: grues, ascenseurs, precision machinery → ATV900 series (high‑end, multi‑axis synchronization)
- Determine Load Category
Continuous load (AC‑1): radiateurs, lighting → 1:1 power selection
Motor load (AC‑3): squirrel‑cage motor DOL → motor current ≤ drive rated current
Shock load (AC‑4): concasseurs, presses → select HD series for 150% surcharge
- Calculate Current & Notation
- Read motor nameplate: pouvoir / voltage → rated current
- Apply 1.1–1.25 safety margin (inrush, continuous duty)
- Select rated power / current from Schneider catalog
Exemple: 380 V three‑phase 15 kW motor ≈ 30 A → ATV71HD15N4Z (48 UN) is suitable.
- Select Voltage Class
200–240 V single/three‑phase: small equipment
380–480 V three‑phase: norme industrielle
525–690 V three‑phase: high‑voltage systems
- Define Control & Communication
- Control method:
General: standard flux vector control
High precision: closed‑loop vector with encoder
- Communication:
Standard: Modbus RTU
Facultatif: CANopen, Profibus-DP, EtherNet/IP
- IHM:
No terminal: model ends with Z
Graphical terminal: model ends with N4
- Special Functios
Filtre CEM: Category A (built‑in) or B (facultatif)
Unité de freinage: built‑in (standard) or external (high power)
Sécurité: STO (Coupure sûre du couple) available
Extended I/O via option cards
- Environnement & Montage
Température > 40 °C, altitude > 1000 m → derate or upsize
Protection: IP20 for cabinet, IP54+ for outdoor
Montage: 35 mm DIN rail or screws, vertical for cooling
- Final Check: Modèle + Certificates
- Confirm full model: series–power–voltage–option
Exemple: ATV71HD15N4Z
- Verify certificates: CE, UL, CCC, RoHS
- Confirm options: communication card, braking resistor, filtre, etc..
Complete Guide to International Brand Alternatives
for Schneider ATV71HD15N4Z
Executive Summary: For 15 kW 380–480 V three‑phase high‑performance applications, the following international brand alternatives offer flux vector control, built‑in EMC filter, ≥150% overload, and standard communication. They can directly replace the ATV71HD15N4Z in industrial machinery, les fans, pompes, and material handling.
- ABB Alternative
Modèle recommandé: ACS580-01-033A-4
Spécifications de base
| Article | Valeur | Comparison to ATV71HD15N4Z |
| Puissance nominale | 15 kW (20 HP) | Même |
| Tension d'entrée | Three‑phase 380–480 V (-15% à +10%) | Même |
| Courant de sortie nominal | 33 UN (HD) | Slightly lower than 39 A/48 A |
| Surcharge | 150% pour 60 s | Même |
| Control | DTC Direct Torque Control | Better dynamics than flux vector |
| Communication | Modbus RTU standard; Profibus-DP, EtherNet/IP optional | Même |
| Filtre CEM | Built‑in Category A | Même |
| Protection | IP20 | Même |
| Montage | Wall / cabinet | Même |
Key advantages: ABB patented DTC; open loop speed range 1:1000, torque response < 10 MS.
Applications: Compresseurs, convoyeurs, mixers requiring high dynamics and precise torque control.
Backup Model: ACS550-01-033A-4
Cost‑effective alternative, fonctions simplifiées, suitable for stable loads like fans and pumps.
- Siemens Alternative
Modèle recommandé: SINAMICS G120C 6SL3210-1KE23-2UF1 (Compact)
Spécifications de base
| Article | Valeur | Comparison to ATV71HD15N4Z |
| Puissance nominale | 15 kW (HD) / 18.5 kW (LO) | Même / plus haut |
| Tension d'entrée | Three‑phase 380–480 V (+10% à -20%) | Gamme plus large |
| Courant de sortie nominal | 38 UN (HD) | Almost identical to 39 UN |
| Surcharge | 200% pour 3 s + 150% pour 57 s | Mieux |
| Control | Sensorless vector control | Même |
| Communication | Profibus DP standard; PROFINET, EtherNet/IP optional | Même |
| Filtre CEM | Built‑in C3 filter | Better than Category A |
| Protection | IP20 | Même |
| Montage | 35 mm rail DIN / screws | Même |
Key advantages: Siemens SINAMICS platform, seamless TIA Portal integration, STO built‑in.
Applications: Lines, material handling integrated with Siemens PLC.
Backup Model: SINAMICS G120 6SL3224-0BE31-1UA0 (Modulaire)
Conception modulaire, expandable I/O, communication, and safety for complex systems.
- Danfoss Alternative
Modèle recommandé: VLT AutomationDrive FC302P15KT5E20H2BGXXXXSXXXXAXBXCXXXXDX (131F9966)
Spécifications de base
| Article | Valeur | Comparison to ATV71HD15N4Z |
| Puissance nominale | 15 kW (HD) / 18.5 kW (LO) | Même / plus haut |
| Tension d'entrée | Three‑phase 380–500 V | Gamme plus large |
| Courant de sortie nominal | 32 UN (HD) / 37.5 UN (LO) | Slightly lower |
| Surcharge | 160% pour 60 s (every 10 min) | Mieux |
| Control | Sensorless vector control | Même |
| Communication | Modbus RTU / CANopen standard; Profibus-DP, EtherNet/IP optional | Même |
| Filtre CEM | Built‑in C3 filter | Better than Category A |
| Protection | IP20 | Même |
| Montage | Wall mounting, back‑channel cooling | 30% space saving |
Key advantages: Patented back‑channel cooling, compact, low noise ≤ 65 dB.
Applications: HVAC fans, pompes, and noise‑sensitive industrial machines.
- Rockwell Automatisation (Allen‑Bradley) Alternative
Modèle recommandé: PowerFlex 755 20G1ANC302JA0NNNNN
Spécifications de base
| Article | Valeur | Comparison to ATV71HD15N4Z |
| Puissance nominale | 15 kW (20 HP) | Même |
| Tension d'entrée | Three‑phase 380–480 V (±10%) | Même |
| Courant de sortie nominal | 32 UN (HD) | Slightly lower |
| Surcharge | 150% pour 60 s | Même |
| Control | TotalForce sensorless vector | Même |
| Communication | EtherNet/IP standard; Profibus-DP, DeviceNet optional | Advanced Ethernet |
| Filtre CEM | Built‑in | Même |
| Protection | IP20 | Même |
| Montage | Wall / cabinet | Même |
Key advantages: TotalForce platform, seamless Logix integration, advanced diagnostics.
Applications: North American equipment, automotive lines, machines d'emballage.
Backup Model: PowerFlex 525 25B-D030N114
Compact, cost‑effective for space‑limited general applications.
- Other International Brands
Eaton: SVX9000-4T0032
Specs: 15 kW, 380–480 V, 32 UN, 150%/60 s, built‑in EMC, IP20, Modbus/CANopen.
Use: High‑reliability applications: grues, compresseurs.
Vacon: NXC0320T4H0SSSA1A2
Specs: 15 kW, 380–480 V, 32 UN, 150%/60 s, vecteur sans capteur, built‑in EMC, IP20.
Use: General industrial machinery, multi‑PLC systems.
- Replacement Selection Guide
| Requirement | Modèle recommandé | Reason |
| High dynamics / precise torque | ABB ACS580-01-033A-4 | DTC, réponse rapide |
| Siemens system integration | Siemens G120C / G120 | TIA Portal, STO built‑in |
| Low noise / space saving | DanfossFC302 | Back‑channel cooling, compact |
| Rockwell system integration | PowerFlex 755 | TotalForce, Logix compatible |
| Cost‑effective general use | ABBACS550 / PowerFlex 525 | Simplified, economical |
| Wide voltage fluctuation | Siemens G120C | +10% à -20% tolérance |
All international alternatives meet the performance requirements for 15 kW three‑phase applications. Each brand offers strengths in control, intégration, cooling, and features. Selection should prioritize system compatibility, type de charge, environment, and budget to ensure plug‑and‑play replacement.
All recommended models include a built‑in EMC filter, standard communication, and full protection, allowing direct replacement of the ATV71HD15N4Z without extra basic components.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires





















NH42-63-318x560.png)