A classic motor protection series from Schneider Electric, designed for low-power motors rated 0.1-32A. It provides protection against short circuit, overload and phase loss. Equipped with a rotary knob for manual closing and tripping, and built-in thermal-magnetic trip unit to deliver delayed overload protection and instantaneous short-circuit protection. The code 10 represents an adjustable setting current range of 4-6.3A, compatible with 1.5-2.2kW three-phase motors at 400V. Models suffixed with C are domestic versions, while those without C are imported versions. Both share identical performance parameters and comply with IEC and GB standards.
- Explication du code modèle
| Segment | GV2 | MP | 10 | C |
| Signification | Série de produits: TeSys Deca GV2 motor circuit breaker | Operation type: Panel Mount Rotary Knob with thermal-magnetic protection | Setting current range code: 4-6.3UN | Origin code: Manufactured in China |
- Principales spécifications techniques
| Catégorie | Données techniques | Remarques |
| General Information | ||
| Nom du produit | TeSys Deca GV2PM Motor Circuit Breaker | Specifically designed for motor control and protection |
| Code de commande | GV2PM10C | Standard commercial model |
| Statut du produit | Active | Standard product of Schneider Electric |
| Paramètres électriques | ||
| Poteaux | 3P. (Triphasé) | For three-phase asynchronous motors |
| Réglage de la plage de courant | 4-6.3UN | Adjustable via rotary knob, for 1.5-2.2kW motors (400V) |
| Courant opérationnel nominal (je) | 6.3UN | Maximum continuous operating current |
| Tension d'isolation nominale (Interface utilisateur) | 690V | Withstand voltage level of insulation system |
| Tension de fonctionnement nominale (Ue) | 400V et (50/60Hz) | Standard industrial voltage |
| Capacité de coupure ultime nominale en court-circuit (ICU) | 100kA @ 400V | Conforme à la CEI 60947-2 |
| Type de protection | Thermique-magnétique | Delayed overload protection + protection instantanée contre les courts-circuits |
| Paramètres mécaniques | ||
| Dimensions (L×H×P) | 89mm×85mm×91mm | Compact structure to save cabinet space |
| Poids | Environ. 280g | Easy for installation and maintenance |
| Montage | 35mm Montage sur rail DIN | Conforme à la norme EN 60715 |
| Terminaux | Bornes à vis, for 1.5-4mm² conductors | Suitable for solid and stranded wires |
| Mode de fonctionnement | Rotary knob (OFF-ON-RESET) | Manual reset required after tripping |
| Paramètres environnementaux | ||
| Température de fonctionnement | -20°C ~ +60°C | Adaptable to industrial environments |
| Protection contre la pénétration | IP20 | Prevents finger access to live parts |
| Certifications | CE, CCC, UL, ASC | Conforme aux normes de sécurité internationales |
- Full Range of GV2PM Rotary Knob Motor Circuit Breakers
| Modèle | Réglage de la plage de courant | Puissance moteur adaptée (400V) | Remarques |
| GV2PM01C | 0.1-0.16UN | 0.025-0.04kW | Minimum current rating |
| GV2PM02C | 0.16-0.25UN | 0.04-0.06kW | |
| GV2PM03C | 0.25-0.4UN | 0.06-0.1kW | |
| GV2PM04C | 0.4-0.63UN | 0.1-0.16kW | |
| GV2PM05C | 0.63-1UN | 0.16-0.25kW | |
| GV2PM06C | 1-1.6UN | 0.25-0.4kW | |
| GV2PM07C | 1.6-2.5UN | 0.4-0.63kW | |
| GV2PM08C | 2.5-4UN | 0.63-1.1kW | |
| GV2PM10C | 4-6.3UN | 1.1-2.2kW | Modèle actuel |
| GV2PM14C | 6.3-10UN | 2.2-3kW | |
| GV2PM16C | 9-14UN | 3-4kW | |
| GV2PM20C | 13-18UN | 4-5.5kW | |
| GV2PM21C | 17-23UN | 5.5-7.5kW | |
| GV2PM22C | 23-32UN | 7.5-11kW | Maximum current rating |
- Concurrent & Modèles équivalents
| Marque | Modèle | Réglage de la plage de courant | Mode de fonctionnement | Description du remplacement |
| Schneider Électrique | GV2ME10C | 4-6.3UN | Push-button | Alternative with different operation mode within the same series |
| Siemens | 3RV2011-0JA10 | 4-6.3UN | Rotary knob | Cross-brand functional replacement |
| ABB | MS116-6.3 | 4-6.3UN | Rotary knob | Cross-brand functional replacement |
| Eaton | DIL M9-10 | 4-6.3UN | Rotary knob | Cross-brand functional replacement |
| Chint | NDM1-63/3300 | 4-6.3UN | Rotary knob | Economical domestic alternative |
- Application Environments & Cas typiques
5.1 Applications recommandées
Automatisation industrielle: Protection for small pumps, fans and conveyor motors; compatible with PLC control circuits
Installations du bâtiment: Control and protection for air conditioning fans, pompes à eau, elevator door motors and fire linkage equipment
Nourriture & Industrie des boissons: Motor protection for packaging machines, filling machines and small mixers; meets hygiene requirements
Équipement médical: Safety protection for laboratory stirrers, centrifuges and small medical pumps
Machines agricoles: Protection for outdoor motors such as irrigation pumps, small harvesters and feed mixers
Centres de données: Protection for precision air conditioner fans, cooling water pumps and UPS cooling fans
5.2 Applications non recommandées
Démarrage fréquent: Not applicable for equipment starting more than 10 fois par heure. GV3 series or soft starters are recommended instead.
Heavy-duty start: Not suitable for motors with starting current over 8 fois le courant nominal. Additional overload protection is required.
Explosive hazardous areas: No explosion-proof certification. Do not use directly in Zone IIC explosive areas.
DC motors: The GV2 series is designed exclusively for AC motors. Use dedicated protective devices for DC motors.
5.3 Cas d'application typiques
Cas 1: Mixing System in Pharmaceutical Factory
Application: Surcharge, short-circuit and phase loss protection for 1.5kW reactor stirring motors
Configuration: GV2PM10C + LC1D12 Contactor + Control Buttons
Avantages: Prevents motor burnout caused by agitator jamming; complies with GMP standards and trips rapidly for equipment protection during faults.
Cas 2: Air Conditioning System in Commercial Buildings
Application: Protection and control for 2.2kW fresh air handling units and water pump motors
Configuration: GV2PM10C + Building Automation System (BAS) + Temperature Sensors
Avantages: Enables automatic start/stop of fans and pumps, protects motors against overload, reduces maintenance costs and improves energy efficiency by 12%.
Cas 3: Conveyors on Automated Production Lines
Application: Protection and control for 1.1kW small conveyor motors
Configuration: GV2PM10C + API + Emergency Stop Buttons
Avantages: Avoids motor damage from conveyor jamming, works with emergency stop system for safe shutdown, and shortens Mean Time To Repair (MTTR) to within 3 minutes.
Cas 4: Aeration System in Wastewater Treatment Plant
Application: Protection and control for 2.2kW small aeration fans
Configuration: GV2PM10C + Liquid Level Sensors + Automatic Control Cabinet
Avantages: Performs reliably in humid environments, prevents fan burnout from overload, realizes unattended automatic operation and cuts operational costs by 30%.
- Conseils de sélection & Quick Reference Rules
Selection Rhythm
Choose GV2PM10C,
Plage actuelle 4 to 6.3A,
Matches motors 1.5 to 2.2kW,
Rotary knob operation, IP20 rating,
35mm rail DIN, 89mm largeur,
High breaking capacity with thermal-magnetic protection,
Safeguards motors from overload and short circuit,
Reliable for industrial and building applications.
Quick Reference Rules
- Correspondance actuelle: 10 = 4-6.3A; 08 = 2.5-4A; 14 = 6.3-10A. Larger figure means wider current range.
- Mode de fonctionnement: PM = Rotary knob; ME = Push-button; LP = Magnetic-only type (short-circuit protection only).
- Correspondance de puissance: 4-6.3A corresponds to 1.5-2.2kW @ 400V. Approximate formula: Current × 0.5 ≈ Matched motor power (kW).
- Installation Features: 89mm largeur, 35mm Montage sur rail DIN, Indice de protection IP20, ideal for installation inside control cabinets.
- Dépannage
| Phénomène de défaut | Causes possibles | Solutions |
| Déclenchements fréquents | Setting current too low | Turn the rotary knob clockwise to increase current within 4-6.3A |
| Surcharge du moteur / rotor bloqué | Check for overloading and eliminate jamming | |
| Opération de perte de phase | Inspect three-phase power supply and repair broken wires or poor contacts | |
| Défaut de fermeture | Knob not reset | Turn the knob to OFF position then back to ON after tripping |
| Bourrage mécanique | Clear foreign objects or replace damaged components | |
| Mauvais câblage | Recheck three-phase wiring and eliminate short circuits | |
| Overheated contacts | Loose wiring terminals | Retighten terminals for good contact |
| Charge excessive | Reduce load or replace with higher-rated circuit breaker if needed | |
| Température ambiante trop élevée | Improve ventilation and keep temperature below 60°C |
- Key Features Summary
- Protection complète: Thermal-magnetic trip unit provides delayed overload, instantaneous short-circuit and phase loss protection, conforme à la CEI 60947-4-1.
- Wide Compatibility: 4-6.3A adjustable current range for 1.5-2.2kW three-phase motors; easy operation via rotary knob.
- Structure compacte: Dimension 89mm×85mm×91mm with 35mm DIN rail mounting to save cabinet space.
- Haute fiabilité: Wide operating temperature range (-20°C ~ +60°C) and IP20 rating for harsh industrial conditions.
- Installation facile & Entretien: Standard interface for seamless matching with contactors; simple knob reset after faults.
Application Scenarios of Schneider GV2PM10C (4~6,3A)
This is a 3-pole rotary-knob motor circuit breaker with thermal-magnetic protection. It is suitable for 1.1~2.2kW three-phase asynchronous motors at 400V. Adopting DIN rail mounting, it integrates overload, short-circuit and phase loss protection, and is widely used in industrial, building, light industry and municipal fields.
- Main Application Scenarios
1.1 Industrial Automated Production Lines
Small belt conveyors and roller motors
Workshop auxiliary fans and dust extraction fans
Auxiliary power motors for manipulators and small positioners
Machine tool cooling pumps and lubrication pumps
Combined with PLC and relay circuits for local and remote control & protection
1.2 CVC & Building Electromechanical Systems
Terminal fans, fresh air fans and exhaust fans of central air conditioning
Small circulating water pumps and make-up water pumps for building water supply & drainage
Cooling fans for computer room precision air conditioners
Auxiliary fans and door drive motors in elevator rooms
Fire exhaust fans and damper linkage motors (meeting fire power distribution standards)
1.3 Industrie légère, Nourriture & Industrie de l'emballage
Small mixers, blenders and feeding machines
Machines d'emballage, labelers and conveyor drive motors
Filling equipment and small roller conveyors
Ventilation fans and washing pumps for food workshops
(Compact body and qualified protection level, suitable for dusty and humid workshop conditions)
1.4 Traitement de l'eau & Municipal Engineering
Small aeration fans, dosing pumps and reflux pumps in sewage treatment plants
Booster pumps for landscape pools and residential water supply
Small power motors inside on-site control boxes of pumping stations
Fans and water pumps supporting river and pipeline monitoring equipment
1.5 Laboratory & Medical Supporting Equipment
Laboratory stirrers, centrifuges and circulating water pumps
Exhaust and fresh air system motors for medical clean rooms
Medical water purifiers and small delivery pumps
(Sensitive protection effectively prevents equipment stalling and motor burnout)
1.6 Entreposage, Logistique & Supermarchés
Warehouse ventilation fans and dust removal equipment
Condenser fans and fresh air systems for supermarket refrigeration units
Motors for light sorting lines and small roller conveyors
1.7 Machines agricoles & Outdoor Light-duty Equipment
Small irrigation pumps and spray devices for farmland
Feed mixers and small agricultural ventilation equipment
(Wide temperature adaptability for outdoor simple electrical control boxes)
- Scénarios non recommandés
- High-frequency starting equipment: Plus que 10 starts per hour may cause false tripping. Dedicated starting solutions are recommended.
- Heavy-load motors with high starting current: Starting current far exceeds normal level; match with thermal relays and contactors additionally.
- Explosive hazardous areas: Without explosion-proof certification, not allowed for direct use in explosive zones.
- DC motors and high-power single-phase motors: Designed for three-phase AC motors only.
- Environments with long-term temperature above +60°C or strong corrosive gas: Protection accuracy and service life will be reduced.
- Common Matching Solutions for On-site Use
- Standard motor circuit: GV2PM10C + LC1D Contactor + Boutons poussoirs (Local start & arrêt)
- Automatic control circuit: GV2PM10C + Contacteur + API (Remote automatic control)
- Fire linkage circuit: GV2PM10C + Fire Module + Contacteur (Fire forced start / forced trip)