Nom complet du produit: Modicon Premium AS‑Interface V2 Master Module (AS-i Master)
It is a rack-mounted module for Premium (TSX57) API. End-of-life (EOL: 2021‑01‑23), end of service: 2026‑12‑31. Non recommandé pour les nouveaux projets; only available for spare parts and retrofit of legacy equipment.
- Définition du code modèle
TSX: Prefix for Modicon Premium series
SAY: AS-i bus master module
1000: Version V2, supports standard and extended addressing
- Spécifications de base
| Article | Paramètre |
| Protocole de bus | AS‑Interface V2, M2E profile |
| Addressing Mode | Standard addressing + extended addressing |
| Slave Capacity | Jusqu'à 31 slaves in standard mode; analog slaves available with extended addressing |
| Supported Slave Types | Discrete I/O (4I/3O, 4I/4O), AS-i analog slaves, AS-i safety interface slaves |
| Alimentation | Powered by Premium rack backplane |
| Backplane Current Draw | 450mA @5VDC |
| Interface | 3-pin male SUB-D, AS-i bus terminal |
| Poids | 0.34kilos |
| Max Modules per Rack | TSX570/TSX57C: 1 ordinateur; TSX571: 2 pièces; TSX572: 4 pièces; TSX573~TSX576: jusqu'à 8 pièces |
| Panneau avant | LED d'état (PWR/OK/FAULT, A/B group), 32-point slave diagnostic LEDs, 2 operation buttons |
| Logiciel de programmation | Unité Pro |
| Code SH | 85389099 |
- Description de la fonction
- Acts as the AS-i bus master for Premium PLC to connect field AS-i sensors and actuators (détecteurs de proximité, électrovannes, modular I/O, etc.), greatly simplifying field wiring.
- Front panel integrated diagnostic LEDs for quick troubleshooting of AS-i bus faults, slave disconnection and address conflicts.
- Supports acquisition from AS-i analog slaves, not limited to discrete signals only.
- Compatible with AS-i safety slaves (safety input / safety output).
- Modèle de remplacement
Official Recommended Replacement: BMXEIA0100 (M340 PLC AS-i Master Module)
Note: Platform migration from Premium TSX57 to M340 requires rack, CPU and software replacement. It is not a direct plug-and-play replacement. For legacy systems, only used / surplus TSXSAY1000 can be sourced as spare parts.
- Installation & Directives d'entretien
- Installation: DIN rail mounting in Premium rack, X-Bus backplane communication; Indice de protection IP20, pour installation en armoire uniquement.
- AS-i Bus: Use dedicated AS-i yellow flat cable; AS-i power supply must be installed at both ends of the bus. SUB-D connector spare: Contact Phénix 1841909, Schneider internal part number W815891970101A.
- Dépannage
FAULT red LED: Bus short circuit, panne de courant, duplicate slave address
A/B LED: Indicate AS-i A/B dual group slaves
32 LEDs: Corresponding slave online status; OFF = slave lost
- Liste de contrôle d'inspection d'occasion
Power on and verify PWR/OK LED without faults
All front panel LEDs light normally, no damage
SUB-D connector free of oxidation and intact pins
Rack gold-plated contacts without burn marks
Perform bus scan test with AS-i power supply and AS-i slave
- Clarification des idées fausses courantes
❌ Not an analog output module. Some vendors incorrectly label it as AO module. It is an AS-i fieldbus communication master module.
TSXSAY1000 (Premium AS-i V2 Master Module) Cas de candidature
Core feature: TSXSAY1000 is the AS-i bus master mounted on Premium PLC rack. Suitable for scattered field I/O, large quantity of sensors, solenoid valves and safety signal acquisition. One AS-i yellow flat cable transmits data and power simultaneously, drastically reducing hardwiring work. All cases are legacy projects (Premium platform, Unity Pro programming), mainly for retrofit and maintenance of existing equipment. Premium platform is not recommended for new projects.
Cas 1: Ligne d'assemblage de composants automobiles (Application typique)
Aperçu du projet
Contrôleur principal: TSXP573623M Premium CPU + TSXSAY1000 AS-i master module for one assembly station bus
AS-i slaves: Capteurs de proximité, capteurs photoélectriques, station pushbutton boxes, solenoid valve islands, AS-i safety slaves (safety gates, arrêt d'urgence)
I/O count: A/B dual group, around 42 AS-i slaves; includes discrete I/O and a small number of analog slaves (pressure sensor AS-i modules)
Architecture du système
Premium Rack (TSXP57+TSXSAY1000) → SUB-D Connector → AS-i Yellow Flat Cable → Field AS-i Slaves
Reason for TSXSAY1000 Selection
- Assembly stations are distributed. Traditional hardwiring requires separate cables from each sensor back to control cabinet, with high cost of cables, trunking and wiring labor. AS-i single cable connects all points in series.
- AS-i Safety support: Safety gate and E-stop signals transmitted via AS-i safety channel, natively supported by TSXSAY1000.
- Front panel 32-channel diagnostic LEDs allow maintenance personnel to identify offline slaves at a glance for fast fault location.
Logique de contrôle
Material presence detection at station, cylinder solenoid valve actuation, safety gate interlock, protection d'arrêt d'urgence
Analog pressure acquisition (press-fit pressure) uploaded to PLC for press-fit judgment
Pain Points & Entretien
Défauts: AS-i flat cable insulation damage, poor contact from piercing terminals. TSXSAY1000 FAULT LED alarm, read bus diagnostic word in Unity Pro.
Limitation: Max bus length ≤100m; AS-i repeater required for longer distance.
Retrofit Alternative
Full Premium platform replacement: M340 + BMXEIA0100 AS-i master
Cas 2: Food Packaging Line (Emballage à flux horizontal / Case Packer)
Aperçu du projet
Premium TSXP57254M + TSXSAY1000; case conveying line with multi-section belt conveyors, material stop cylinders and detection photoelectric sensors
AS-i slaves: Capteurs photoélectriques, material presence switches, électrovannes, AS-i modular I/O
Process Requirement
Multi-section conveyor sorting, material detection, material stop and reject. Field I/O points scattered along long conveying line.
Avantages
- Humid environment in packaging workshop. AS-i flat cable with piercing connection, fast wiring, M12 waterproof slaves.
- Simple configuration in Unity Pro for TSXSAY1000, automatic slave scan and I/O mapping.
- Add new slaves directly on AS-i bus when expanding stations, no massive recabling.
Typical Fault
Insufficient AS-i power capacity. Voltage drop occurs when multiple solenoid valves energize simultaneously, causing temporary slave dropout reported by TSXSAY1000.
Cas 3: Automated Warehouse Conveyance & Pallet Detection
Aperçu du projet
Pallet inbound conveyor section in automated warehouse, Premium PLC + TSXSAY1000 to manage scattered detection points on conveyor line
AS-i slaves: Pallet presence photoelectric sensors, position proximity switches, stop cylinder solenoid valves, pallet oversize detection
Processus
Pallet inbound, position identification, stop and release. I/O points spread along long conveyor, control cabinet installed at one end of warehouse.
Justification de la sélection
Traditional point-to-point wiring incurs extremely high cable cost. AS-i cable routed along conveyor cable tray with single drop branches. TSXSAY1000 supports up to 62 discrete AS-i slaves, sufficient for one inbound conveyor line.
Note: For multi-bus warehouse projects, multiple TSXSAY1000 modules can be installed on Premium rack (jusqu'à 8 modules for TSX573 and above) to expand multiple independent AS-i buses.
Cas 4: Valve Island & Level Switch Acquisition in Wastewater Treatment Plant (Industrie de transformation)
Aperçu du projet
Wastewater pre-treatment, mechanical bar screens and sludge discharge valve banks; Premium PLC, TSXSAY1000, field AS-i valve islands + interrupteurs de niveau
AS-i slaves: Pneumatic valve AS-i valve islands, interrupteurs de niveau, flow switches, 4-20mA AS-i analog modules
Processus
Bar screen start/stop, on/off control of sludge discharge valves, liquid level monitoring. Valve groups distributed around tanks under humid and corrosive environment.
Caractéristiques
TSXSAY1000 supports AS-i analog slaves for direct acquisition of liquid level and pressure analog signals, eliminating large quantity of additional analog input modules.
Consideration
AS-i bus is not suitable for ultra-long distance wiring across tanks; AS-i repeater required if length exceeds 100m.
Summary of TSXSAY1000 Application Profile
✅ Suitable Scenarios
- Scattered field sensors and actuators, large volume of discrete I/O (photo-électrique, proximité, électrovannes)
- Systems requiring AS-i safety bus (safety gates, arrêt d'urgence)
- Small volume analog acquisition (pression, liquid level via AS-i slaves)
- Retrofit and spare part replacement of legacy Premium systems
❌ Scénarios inappropriés
- High-speed process and heavy analog volume applications (Profibus / Modbus TCP preferred)
- Long bus distance (>100m without repeater)
- Nouveaux projets (Premium platform EOL, M340+BMXEIA0100 recommended)
Configuration Guidelines (Unité Pro)
- Insert TSXSAY1000 into hardware tree of Premium rack
- Configure AS-i V2, standard / extended addressing
- Bus scan to identify group A / B slaves
- Automatically map AS-i input and output to PLC internal variables
- Read module diagnostic word for SCADA alarm (bus fault, slave dropout)
Schneider Modicon Premium AS-i V2 Master Module TSXSAY1000 Full Technical Specifications
Positionnement du produit: AS‑Interface V2 fieldbus master module for Premium PLC rack. EOL, configured by Unity Pro software.
- Informations de base
| Article | Paramètre |
| Modèle | TSXSAY1000 |
| Famille de produits | Modicon Premium (TSX57) |
| Type de module | AS‑Interface V2 Bus Master |
| AS-i Profile | M2E |
| Logiciel | Unité Pro |
| Code SH | 85389099 |
| Poids net | 0.34 kilos |
- Bus Communication Parameters
| Article | Paramètre |
| AS-i Version | AS‑Interface V2 |
| Addressing Mode | Standard addressing + extended addressing (A/B dual group) |
| Max Slave Quantity | Standard addressing: 31 unités; extended addressing: 31 unités; maximum total 62 discrete slaves |
| Supported Slave Types | Discrete I/O slaves (standard 4I/4O, extended 4I/3O), AS-i analog slaves, AS-i safety interface slaves (barrière de sécurité, arrêt d'urgence) |
| Bus Medium | AS-i dedicated yellow flat cable |
| Max Bus Length | 100m (without repeater) |
| Bus Power | External independent AS-i power supply (backplane only supplies module itself, not AS-i bus power) |
- Paramètres électriques
| Article | Paramètre |
| Alimentation du module | Premium rack X-Bus backplane 5VDC |
| Backplane Current Consumption | 450mA @5VDC |
| Interface de bus | 3-pin male SUB-D (AS-i+, AS-i-) |
- Rack Configuration (Max TSXSAY1000 Quantity per Premium CPU)
| Modèle de processeur | Max TSXSAY1000 Quantity |
| TSX570 / TSX57C | 1 ordinateur |
| TSX571 | 2 pièces |
| TSX572 | 4 pièces |
| TSX573 / TSX574 / TSX575 / TSX576 | 8 pièces |
- LED du panneau avant & Operation Buttons
Indicateurs d'état LED
- PWR OK (Vert): Backplane power supply of module normal
- FAUTE (Rouge): AS-i bus fault, court-circuit, slave loss, address conflict
- A/B (Vert): A-group / B-group slave group indicator
- 32 Diagnostic LEDs: Non.0~31, slave online status; OFF = slave offline
Buttons
- A/B: Toggle display between A-group and B-group slave status
- MODE: Hors ligne / online switch, slave initialization, infrared address setting support
- Environnemental & Spécifications mécaniques
| Article | Paramètre |
| Classe de protection | IP20 (cabinet use only) |
| Température ambiante de fonctionnement | 0 ℃ ~ +60 ℃ |
| Température de stockage | -25 ℃ ~ +70 ℃ |
| Vibration Test | IEC 60068‑2‑6 Fc |
| Shock Test | IEC 60068‑2‑27 Ea |
| Méthode de montage | Slot installation on Premium rack backplane |
- Points forts fonctionnels
- Supports AS-i Safety safety bus, safety slave connection for safety gate and emergency stop signal acquisition.
- Supports AS-i analog slaves for pressure, liquid level analog signal acquisition.
- Built-in bus diagnostics; diagnostic word readable in PLC program for SCADA alarm.
- Supports automatic bus scan, slave address detection and conflict detection.
- Limitation Notes
- ❗ Not an I/O module. It is a fieldbus communication master module without local I/O points.
- EOL spare part only, not recommended for new projects. Official hardware migration: M340 + BMXEIA0100.
- AS-i bus is not suitable for high-speed mass analog transmission; AS-i repeater required when bus length exceeds 100m.