SIRIUS 3RT series 3-contacteur de puissance AC pôle, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts
- Décodage du modèle
3RT1056-6AP36
3RT: SIRIUS power contactor series
10: Contacteur standard (non-safety, non-reversing type)
56: Frame size S6, AC-3 400V 185A
6: Coil voltage 220…240V AC/DC
UN: Connexion du jeu de barres du circuit principal
P.: Screw terminals for auxiliary contacts
36: Contacts auxiliaires 2 Normalement ouvert + 2 Normalement fermé (2NON+2NC)
- Spécifications électriques de base
| Article | Paramètre |
| Nombre de pôles principaux | 3 poteaux (3NON) |
| AC-3 (Motor load @400V) | 185UN, 90kW |
| AC-1 (Resistive load @40℃) | 215UN |
| Tension assignée d'emploi Ue | Max.. 1000V et |
| Coil control voltage Uc | 220~240 V CA/CC (Wide-range AC/DC coil) |
| Contacts auxiliaires | 2NON + 2Caroline du Nord, bornes à vis |
| Connexion du circuit principal | Jeu de barres |
| Taille du cadre | S6 |
| Degré de protection | Front IP00; IP20 with cover installed |
| Tension de tenue aux chocs | 8kV main circuit / 6kV auxiliary circuit |
| Température ambiante | -25℃ ~ +60℃ (Derating required above 40℃) |
- Champ d'application
On/off control of 3-phase motors such as fans, pompes à eau et compresseurs
Control cabinets, climatisation centrale, industrial production lines and power cabinets
Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression
- Modèles alternatifs
- Domestique SIEMENS remplacement: 3RT5056-6AP36
Fonction identique, current rating and coil specification. Fabriqué en Chine, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model
- Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
- Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)
Note: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.
- Installation & Directives d'entretien
- Installation: Montage vertical, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
- Circuit principal: Connexion par jeu de barres, tighten to specified torque per datasheet to prevent overheating and contact burning.
- Bobine: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
- Contact life: Under AC-3 motor duty, mechanical life approx. 10 millions d'opérations; electrical life depends on breaking current.
- Dépannage
Coil energized but no pull-in: Mesurer la tension de la bobine, check coil open circuit or mechanical jamming
Pull-in but no continuity on main circuit: Loose busbar or burned main contacts
Bavarder / bruit anormal: Faible tension de bobine, accumulated dust on iron core, fatigue printanière
- Code SH des douanes
85364900 (Electromagnetic contactor)
- Optional Spare Parts & Accessoires
Relais de surcharge thermique: 3RU2156 series (for 90kW motor)
Suppresseur de surtension: 3RT1955-1CD00 (Circuit RC), 3RT1955-1DG00 (Varistance)
Bloc de contacts auxiliaires: 3RH1951 (for extra auxiliary contacts)
Arc shield & main contact repair kit: 3RT1956 contact assembly
Tableau de comparaison: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36
Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.
| Article de comparaison | 3RT1056-6AP36 (Imported Version) | 3RT5056-6AP36 (Version domestique) |
| Gamme de produits | SIRIUS 3RT1, version importée de la norme mondiale | SIRIUS 3RT5, local domestic version |
| Origine | Amberg Factory, Allemagne | SIEMENS low voltage plant in China (SEAL) |
| AC-3 @400V | 185UN / 90kW | 185UN / 90kW |
| Charge résistive AC-1 | 215UN | 215UN |
| Spécification de la bobine | 220~240 V CA/CC | 220~240 V CA/CC |
| Contacts auxiliaires | 2NON+2NC, bornes à vis | 2NON+2NC, bornes à vis |
| Connexion du circuit principal | Jeu de barres | Jeu de barres |
| Taille du cadre | S6 | S6 |
| Dimension globale / Trous de montage | Identique, interchangeable directement | Identique, interchangeable directement |
| Durée de vie mécanique | 10 millions d'opérations | 10 millions d'opérations |
| Durée de vie électrique AC-3 | Même (depends on breaking current) | Même (depends on breaking current) |
| Ambient Temperature Range | -25℃ ~ +60℃ | -25℃ ~ +60℃ |
| Accessoires compatibles | Compatibilité totale: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, bloc de contacts auxiliaires | 100% compatible with accessories of 3RT1056 |
| Certifications | CCC, CE, UL, ASC, suitable for overseas projects | CCC, CE; UL optional for certain batches, standard for domestic projects |
| Nameplate | Allemand + English marking, Fabriqué en Allemagne | Chinois + English marking, made in China |
| Delivery Lead Time | Long, mostly forward order with unstable lead time | Court, domestic stock available with fast delivery |
| Prix | Plus haut | Lower with cost advantage |
| Scénarios d'application | Équipement d'exportation, overseas projects, high-end foreign-invested projects, cases requiring imported components | Domestic control cabinets, pompes à eau & les fans, CVC, general industrial automation |
| Performances électriques | Identique, no derating difference | Identique, no derating difference |
| Code SH | 85364900 | 85364900 |
| Model Naming Definition | 3RT10: Global original series | 3RT50: Domestic localized series |
Notes clés
- Interchangeabilité: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, jeu de barres, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
- Guide de sélection
✅ Choose 3RT5056: Projets nationaux, budget control, livraison rapide; preferred for most domestic panel building projects.
✅ Choose 3RT1056: Export machinery, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.
- Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.
Supplémentaire: Shared Spare Parts List
Relais de surcharge thermique: 3RU2156 series
Suppresseur de surtension: 3RT1955-1CD00 / 3RT1955-1DG00
Main contact repair kit: 3RT1956
Additional auxiliary contact block: 3RH1951
Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36
Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185UN). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.
- Common Applications (Both Models Applicable)
(1) Direct-on-line Motor Starting (Main AC-3 Duty)
Pompes à eau, pompes à eaux usées, pompes de circulation (traitement de l'eau, CVC, bâtiment, industrie chimique)
Compresseurs d'air, grands ventilateurs, ventilateurs d'extraction de fumée
Convoyeurs, mélangeurs, extrudeuses, concasseurs (nourriture, building material, exploitation minière)
Chillers and large refrigeration compressors for central air conditioning
MCC motor control centre drawer units for 90kW motor circuits
(2) Charge résistive AC-1
High-power heating elements, fours à résistance
Main circuit switching of high-power circuits inside distribution cabinets
(3) AC-6B Capacitor Switching
Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)
Correspondance: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.
- Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
- Domestic panel projects, domestic factories, CVC, approvisionnement en eau & drainage, general factory automation
Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.
- Domestic municipal projects: Stations d'épuration des eaux usées, municipal pump stations, building HVAC cabinets
- Domestic machinery OEM: Ventilateurs, compresseurs d'air, chiller units sold in domestic market
- Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
- Retrofit replacement for old contactors, tight budget and fast delivery required
✅ Convient pour: Domestic projects without mandatory UL/CSA certification or German origin requirement
- Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
- Export machinery & equipment (export to Southeast Asia, Moyen-Orient, Europe and other overseas sites)
Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.
- New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
- Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
- High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
- Spare part replacement for legacy equipment: Original unit fitted with 3RT1056 and client requires identical OEM spare parts
✅ Convient pour: Export machinery, overseas projects, client specified imported components, mandatory UL/CSA certification
- Éviter les pièges de la sélection
- Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
- For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
- For export to Europe / Amérique du Nord, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
- Heavy vibration & dusty heavy industry environments (exploitation minière, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
- Scénarios non applicables
Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.
Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)
Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur


















NH42-63-318x560.png)