Main contactor for 3-phase motor control, AC-3 115A, coil AC110V 50/60Hz, with built-in 1NO +1NC auxiliary contacts
✅ Model Breakdown
LC1: Standard 3-pole contactor (sans retour)
D: TeSys D (TeSys Déca) série
115: AC-3 rated operational current 115A (@440V)
F: Coil voltage code = AC110V
7: 50/60Hz universal AC coil
📌 Core Electrical Parameters
| Article | Paramètre |
| Contacts principaux | 3P Normalement ouvert (3NON) |
| AC-3 Operational Current Ie | 115UN (≤440V) |
| AC-1 Resistive Load Ith | 200UN (40℃ free air) |
| Coil Uc | AC110V, 50/60Hz |
| Contacts auxiliaires intégrés | 1NON + 1Caroline du Nord (Standard) |
| Tension d'isolement nominale Ui | 1000V |
| Tension de tenue aux impulsions nominale Uimp | 8kV |
| Utilisation Category | AC-1 / AC-3 / AC-3e / AC-4 |
Puissance nominale du moteur (AC-3)
380/400V: 55kW
220/230V: 30kW
415/440V: 59kW
660/690V: 80kW
📐 Mechanical & Installation
Montage: Rail DIN + base plate screw mounting
Terminaux: Screw terminals for copper bars / câbles
Température ambiante de fonctionnement: -40℃ ~ +60℃
Certifications: CCC, UL, ASC, CEI, RoHS
🧩 Extension Accessories (Common for TeSys D)
- Bloc de contacts auxiliaires: LA1DN (add extra NO/NC contacts)
- Timing unit: LA2DT on-delay / LA2DR off-delay
- Surge suppressor module: LA4DA (RC snubber for coil, suppress induced overvoltage)
- Relais de surcharge thermique: LRD485 (motor protection matched for 115A)
- Verrouillage mécanique: LA9D1150 (for forward/reversing circuit)
⚠️ Sélection & Informations de remplacement
- Other coil variants of the same series:
LC1D115M7: AC220V; LC1D115Q7: AC380V
- End-of-life notice: Old model LC1D1156F7 discontinued, LC1D115F7 is current TeSys Deca version; New generation upgrade replacement model: LC1D115A6KUE (wide voltage coil 100–250V AC/DC)
- Distinction: LC1D (TeSys Déca) ≠ LC1F (TeSys F large frame contactor, different outline dimension)
🛠 Typical Application Scenarios
Start/stop control for 3-phase motors: compresseurs d'air, pompes à eau, les fans, convoyeurs à bande
Chilled water units & HVAC control cabinets
Ensembles complets basse tension, PLC driven high-power motor circuits
Resistance furnaces and high-power resistive loads (200A rating under AC-1)
❗ Common Troubleshooting
- Bobine alimentée, no pull-in: Measure coil voltage for 110V; check coil open circuit and loose wiring
- Loud buzzing noise after pull-in: Faible tension d'alimentation, accumulated dust on iron core, broken short-circuit ring
- Frequent contact erosion: AC-4 heavy duty jogging application, upgrade current rating; check motor stall condition
- Signal de contact auxiliaire anormal: Aged auxiliary contacts or loose wiring, add LA1DN auxiliary block
Supporting Documents for LC1D115F7
- Dimensions du contour (mm)
Largeur: 120
Hauteur: 158
Profondeur: 136
Montage: 35mm rail DIN / M6 screw base mounting
Trous de montage: Vertical pitch 130mm; horizontal pitch 96~110mm (slotted hole)
Câblage du circuit principal: Max 120mm² solid cable; 50mm² flexible cable
Auxiliary control circuit: Max 2.5mm²
- Basic Wiring Schematic
Circuit principal
L1/L2/L3 → Contactor top terminals 1/L1, 3/L2, 5/L3; bottom terminals 2/T1, 4/T2, 6/T3 → Motor
Circuit de contrôle (AC110V Coil)
A1, A2: Bornes de bobine, powered by AC110V
Contacts auxiliaires standards: NON(Normalement ouvert) 13-14; Caroline du Nord(Normalement fermé) 21-22
Typical start-stop circuit: Start button parallel with 13-14 self-latching contact, series with stop button, connected to coil A1/A2.
For forward/reversing: Use LC1D115 + LA9D1150 mechanical interlock, electrical interlock is mandatory to prevent phase-to-phase short circuit.
- LRD Thermal Overload Relay Matching List (Direct plug-in for LC1D115)
LRD43xx series, direct bottom plug-in without adapter; Class10A, surcharge du moteur + protection contre la perte de phase
| Article | Paramètre |
| Contacts principaux | 3P Normalement ouvert (3NON) |
| AC-3 Operational Current Ie | 115UN (≤440V) |
| AC-1 Resistive Load Ith | 200UN (40℃ free air) |
| Coil Uc | AC110V, 50/60Hz |
| Contacts auxiliaires intégrés | 1NON + 1Caroline du Nord (Standard) |
| Tension d'isolement nominale Ui | 1000V |
| Tension de tenue aux impulsions nominale Uimp | 8kV |
| Utilisation Category | AC-1 / AC-3 / AC-3e / AC-4 |
Alternative standalone mounting: LRD33 series, requires adapter LA7D3058 for separate base installation.
- Replacement Model List
✅ Original Schneider Remplacement de mise à niveau (LC1D115F7 planned phase-out)
- LC1D115AEHE: 3P 115A, coil 48~130V AC/DC (perfect replacement for original AC110V coil, recommandé)
- LC1D115AKUE: 3P 115A, wide voltage coil 100~250V AC/DC, best versatility
✅ Domestic equivalent replacement (compatible outline & terminal position for direct swap)
- Shanghai People: CJX2-D115 (bobine AC110V), silver contacts, fully matching dimension
- CHINT: NC2-115
- Délicieux: CJX2-115
Note: Domestic models differ slightly in auxiliary contact configuration and accessory base, verify mounting hole and auxiliary contacts before bulk replacement.
- Sélection & Notes de remplacement
- Tension de bobine: LC1D115F7 = AC110V; verify coil rating during replacement, do not directly use AC220V version.
- Compatibilité des accessoires: LA4DA coil surge suppressor, LA1DN auxiliary contact, LA9D1150 mechanical interlock are fully compatible.
- Load classification: AC-4 frequent jogging operation, avoid full-load operation, upgrade current rating.
Application Scenarios of LC1D115F7 (Bobine AC110V, AC-3 115A, 55kW motor @400V)
Positionnement de base: Mainly for start/stop control of 3-phase AC motors, also switching high-power resistive loads; AC110V control circuit widely used in panel build, imported equipment retrofitting, CVC & air compressor control cabinets
🏭 Industrial Equipment
- Compresseurs d'air: Start/stop of main motor for 55kW screw air compressors, protected by LRD thermal relay against overload and phase loss; PLC digital output drives contactor coil.
- Pompe à eau & Water Supply System: Pompes de circulation, pompes de surpression, sewage pumps as main circuit of constant pressure water supply cabinet; can be configured for 1-duty-1-standby pump interlock.
- Fan System: Dust removal fans, induced draft fans, large air handling unit supply fans; HVAC plant room and waste gas treatment cabinet.
- Machines de transport: Convoyeurs à bande, élévateurs à godets, lignes à rouleaux; heavy starting duty under standard AC-3 load.
- Machine & Caoutchouc & Plastic Equipment: Extrudeuses, large lathe main motors, injection molding machine hydraulic pump motors; retrofitting of old imported cabinets (many units adopt AC110V control circuit).
- Agitators: Chemical and water treatment mixing motors, add cabinet protection for corrosive environment.
🏢 Building HVAC & Infrastructure
- Central Chiller Plant: Pompes à eau de refroidissement, pompes à eau glacée, ventilateurs de tour de refroidissement, linked with building BA system; AC110V control circuit commonly adopted in foreign HVAC cabinets.
- Eau & Sewage Pumping Station: Underground pump house, municipal sewage lifting pump control cabinet.
- Heat Exchange Station: Circulation pumps for heating systems.
🔥 Resistive Load Switching (AC-1, 200UN)
For non-motor pure resistive load, maximum current rating increases to 200A
High-power electric heating tubes, fours à résistance, circuits de chauffage des étuves de séchage
Large 3-phase lighting loads
⚙️ Electrical Panel Industry
- PLC Control Cabinet: PLC digital output drives coil, motor status feedback signal from built-in 1NO+1NC auxiliary contacts of contactor.
- Soft Starter Bypass Contactor: Engage bypass after soft start completion for continuous operation.
- Forward/Reversing Reversing Circuit: Equipped with LA9D1150 mechanical interlock + electrical interlock for cranes and lifting equipment.
⚠️ AC-4 frequent jogging (frequent forward/reverse, démarrages et arrêts fréquents) accélère l'usure des contacts, current rating shall be increased.
⚡ New Energy & Stockage d'énergie
Cooling water pumps and fan control cabinets for PV & systèmes de stockage d'énergie
Fire exhaust fans for energy storage systems
📌 Selection & Remarques sur l'opération
- Tension de bobine: AC110V, widely used for imported equipment, foreign HVAC cabinets and legacy retrofit; AC220V version cannot be directly used for replacement.
- Load category: AC-3 preferred for normal motor start-stop; use caution for AC-4 frequent jogging.
- Protection matching: Must be fitted with LRD43 series thermal overload relay or upstream circuit breaker for short-circuit protection.
- End-of-life notice: LC1D115F7 scheduled for phase-out by end of 2026; new projects prefer wide voltage upgrade model LC1D115AKUE.
Schneider TeSys Deca (Original TeSys D) LC1D 3-Pole Contactor Full Model List
LC1D: 3-pole normally open main contacts, contacts auxiliaires standards 1NO+1NC; suffix code: F7=AC110V 50/60Hz; M7=AC220V; Q7=AC380V; B7=AC24V; E7=AC48V; 7=AC 50/60Hz
Exemple: LC1D09F7 = 9A, Bobine AC110V; LC1D115F7 is your target model
- LC1D Base Models (AC-3 @440V)
| Modèle de base | Courant nominal AC-3(UN) | Puissance moteur adaptée à 400 V(kW) |
| LC1D09 | 9 | 4 |
| LC1D12 | 12 | 5.5 |
| LC1D18 | 18 | 7.5 |
| LC1D25 | 25 | 11 |
| LC1D32 | 32 | 15 |
| LC1D38 | 38 | 18.5 |
| LC1D40 | 40 | 18.5 |
| LC1D50 | 50 | 22 |
| LC1D65 | 65 | 30 |
| LC1D80 | 80 | 37 |
| LC1D95 | 95 | 45 |
| LC1D115 | 115 | 55 |
| LC1D150 | 150 | 75 |
| LC1D170 | 170 | 90 |
| LC1D205 | 205 | 110 |
| LC1D245 | 245 | 132 |
| LC1D300 | 300 | 160 |
| LC1D410 | 410 | 220 |
| LC1D475 | 475 | 250 |
| LC1D620 | 620 | 315 |
Full Model = Base Model + Coil Suffix, par exemple. LC1D09F7, LC1D115M7, LC1D150Q7
- Common AC Coil Suffix Reference Table (50/60Hz)
| Code | Tension de bobine |
| B7 | AC24V |
| E7 | AC48V |
| F7 | AC110V (Votre modèle) |
| M7 | AC220V |
| P7 | AC230V |
| Q7 | AC380V |
| V7 | AC400V |
| R7 | AC440V |
Bobine CC: BD=DC24V, FD=DC110V, MD=DC220V; New wide voltage: KUE=100~250V AC/DC, EHE=48~130V AC/DC
- Derivative Series (Same TeSys D Platform)
- LC2D: Contacteur inverseur (integrated forward/reversing with built-in mechanical & electrical interlock)
LC2D09F7, LC2D12F7 … LC2D115F7
- LC1DT: 4-contacteur de pôle (DT20/DT25/DT32/DT40 etc., pour monophasé / dual-circuit resistive load)
- LC1DxxxS22: Safety mirror contact version, for safety circuit and emergency stop control
- LC1DxxA6KUE: New generation wide voltage coil upgrade model (replaces legacy F7/M7/Q7)
- Common Full Models of LC1D115
LC1D115F7: AC110V (your referenced model)
LC1D115M7: AC220V
LC1D115Q7: AC380V
LC1D115B7: AC24V
LC1D115E7: AC48V
LC1D115A6KUE: Wide voltage 100~250V AC/DC upgrade replacement
- Matched LRD Thermal Relay Series (Direct Plug-in for LC1D)
LRD01~LRD38 (matches 09~38A); LRD43 series (matches 40~170A, LRD4365, LRD4367, LRD4369 for LC1D115)
- Selection Remarks
- Suffix with C (par exemple. LC1D115F7C) = China local version, non-C = import version, identical electrical performance
- Coil can be replaced separately for large frame LC1D115 and above; coils of small size 09~95A are non-replaceable
- Old model LC1Dxxx6F7 being phased out; new projects prefer A6KUE wide voltage version