Nom et prénom: SIMATIC DP ET200SP Fail-Safe Electronic Module F-DI 8×24VDC HF
Modèle de remplacement direct: 6ES7136-6BA01-0CA0 (Factory upgraded version; the old model entered the phase-out stage starting Oct 1, 2024)
✅ Explication du code modèle
6ES7: SIMATIC S7 automation module électronique
136: ET200SP fail-safe F-I/O series
6BA00: F-DI 8-channel 24VDC high function (HF)
0CA0: ET200SP electronic module version
📌 Spécifications clés
Canaux: 8 fail-safe digital inputs + 8 built-in sensor supply VS
Tension nominale: DC24V, allowable range 19.2~28.8V, protection contre l'inversion de polarité
Cote de sécurité: SIL3 (CEI61508), PLe / Cat.4 (ISO13849-1)
Type d'entrée: Entrée coulante (Lecture P), supports 3-wire / 4-wire safety sensors (Arrêt d'urgence, barrière de sécurité, barrière immatérielle de sécurité, etc.)
Channel Delay: Independently configurable per channel from 0.4ms to 20ms
Largeur: 15 mm; Dimensions: 73(H) × 58(D) mm
Compatible BaseUnit: Type A0 BaseUnit, color marking CC01
Evaluation Modes: 1oo1 (single-channel), 1oo2 (dual-channel comparison detection)
Diagnostic: Channel-level short-circuit and wire-break diagnosis; configurable single-channel deactivation / module-wide deactivation
Micrologiciel: V3.0, firmware upgrade supported; je&M0~Je&M3 information supported
Environnement de programmation: TIA Portal V12+, SIMATIC Safety; STEP7 V5.5 SP3+
⚙️ Terminal Assignment (16-épingle)
1:DI0|2:DI1|3:DI2|4:DI3|5:DI4|6:DI5|7:DI6|8:DI7
9:VS0|10:VS1|11:VS2|12:VS3|13:VS4|14:VS5|15:VS6|16:VS7
VSn = Module-integrated short-circuit protected 24V sensor supply; external 24V supply is also acceptable
🧩 Typical Application Scenarios
ET200SP distributed safety station, connected to F-CPU (F-1511C / F-1512C / F-1516F, etc.):
Boutons-poussoirs d'arrêt d'urgence (ARRÊT D'URGENCE)
Interrupteurs pour barrières de sécurité, safety hinge switches
Barrières immatérielles de sécurité, safety laser scanner signal acquisition
Safety limit switches, safety foot switches
⚠️ Upgrade & Notes de compatibilité
- 6ES7136-6BA00-0CA0: PM400 obsolescence notice, phased supply reduction from Oct 1, 2024. New projects are recommended to select 6ES7136-6BA01-0CA0
- 6BA01 is pin-to-pin, Terminal, dimension and program compatible for direct replacement; firmware and diagnostic details optimized. BaseUnit and user program remain unchanged for drop-in replacement
- F-CPU + Safety program package is mandatory; standard non-safety CPUs cannot recognize F-modules
📎 Common Bill of Supporting Materials
BaseUnit: 6ES7193-6BP00-0BA0 (A0 BU, light-colored base unit)
Color marking label: CC01
Front connector: ET200SP 16-pin straight plug terminal
📋 Troubleshooting Guide
DIAG red light: Défaut module / F-communication fault / deactivation; DIAG green light: Module normal
Channel red light: Rupture de fil, court-circuit, mismatch error under 1oo2 mode
Deactivation reset: Acknowledge (F-Ack) inside safety program or adjust deactivation parameter strategy
Common pitfalls: Do not short two signal wires in 1oo2 wiring; do not overload VS supply
6ES7136-6BA00-0CA0|ET200SP F-DI 8×24VDC HF Application Scenarios
Positionnement: PROFIsafe distributed fail-safe digital module d'entrée, SIL3 / Cat.4 / PLe. Used with S7-1500F safety CPU. ET200SP remote station collects safety switch signals locally, replacing traditional safety relay circuits
- By Safety Signal Type (Le plus courant)
- E-Stop Pushbutton
Dual-channel 1oo2 wiring with normally closed dual contacts of E-stop. Rupture de fil, short-circuit and contact mismatch can be diagnosed. Safety rating reaches PLe/SIL3. Widely used in robot cells, presses and conveyor lines.
- Barrière de sécurité / Safety Hinge Switch
Guard door interlock with dual-contact safety gate switch under 1oo2 evaluation. Door opening triggers safe stop. Supports zone safety interlock for welding cells, protective enclosures and equipment access doors.
- Barrière immatérielle de sécurité, Scanner laser de sécurité, Safety Photoelectric
Collect OSSD safety output signals from light curtains. The built-in VS sensor supply can power the light curtain directly. Single-channel or dual-channel mode optional. Applied in packaging machines, stamping equipment and robot access protection.
- Safety Mat, Safety Edge
Pressure-sensitive safety sensors to detect personnel entering hazardous zones, mainly for peripheral protection of robot workcells.
- Two-Hand Control Device
Synchronization signal acquisition for two-hand operation to prevent accidental triggering, used for high-risk equipment such as presses, injection molding machines and punch presses.
- Safety Limit Switch, Travel Safety Switch
Axis hard limit and guard limit, distinguishing safety limits from ordinary limits. For large machine tools and gantry equipment.
- Rope Pull Emergency Stop Switch (Conveyor Line Pull Switch)
Long-distance line-side E-stop for belt conveyors and stacker cranes. Channel-level wire-break diagnosis suits long cable field installation.
- Industrie & Machine Application
Automotive Automation: Welding stations, robot welding cells, lignes de convoyage d'assemblage final, fixture stations
Multiple distributed ET200SP remote stations. Each station installs this module locally to manage its own safety signals and implement zone shutdown without affecting the whole line.
Industrie des machines-outils: CNC machining centers, fraiseuses à portique, broyeurs
Spindle guard doors, slideway protective doors, safety hard limits. Supports long shielded cables (maximum. 1000m), fast response starting from 0.4ms input delay.
Conditionnement & Nourriture & Boisson: Machines de remplissage, palettiseurs, machines à étiqueter les manchons, monteurs de caisses
Hopper access doors, barrières immatérielles de sécurité, guard interlock. Meets CE Machinery Directive, suitable for hygienic machinery safety systems without separate safety relay cabinets.
Manutention des matériaux & Convoyage: Belt lines, lignes de tri, AS/RS stacker cranes
Line-side rope pull switches, portes d'accès, safety guard switches, safety deviation signals.
Équipement pharmaceutique: Remplissage, tableting and cleaning machines
SIL3-compliant safety signal acquisition, supports validation documentation and traceable safety diagnostics.
Caoutchouc & Plastiques, Moulage par injection, Die Casting: Presses à injecter, die casting cells
Barrières de sécurité, boutons à deux mains, safety light curtains for high-temperature molten material zone protection.
- Architecture & Usage Notes for Selection
1oo1 (Monocanal): Suitable for PLd / SIL2 applications with one signal per DI channel.
1oo2 (Dual-channel comparison): Cat.4 / PLe / SIL3. Fixed pairing: DI0&DI4, DI1&DI5, DI2&DI6, DI3&DI7 for cross-checking to detect short-circuits, wire breaks and contact discrepancies. This is the primary usage mode.
8 independent short-circuit protected VS sensor power supplies onboard. Can power safety sensors directly to reduce external 24V safety wiring; external power supply is also available.
Communication: PROFINET + PROFIsafe, mounted on ET200SP IM interface module. F-CPU + Safety package required; standard CPU cannot recognize F-modules.
Installation: Distributed near machine equipment to reduce heavy safety cable runs from control cabinets to field sensors, easier maintenance and zone diagnosis.
- Applications inappropriées
Analog safety signals (select F-AI 6ES7136-6AAxx series)
Safety output (F-DQ, 6ES7136-6DB00 / 6DC00)
Intrinsically safe signals for explosion-proof zones
Ordinary non-safety digital input only (Standard ET200SP DI modules for lower cost)
6ES7136-6BA00-0CA0|Complete Installation & Instructions de câblage
Compatible BaseUnit: A0 light-colored base 6ES7193-6BP00-0BA0, color marking CC01. F-CPU + PROFIsafe mandatory; standard CPU not supported
Définition du terminal (16-pin BaseUnit)
1:DI0|2:DI1|3:DI2|4:DI3|5:DI4|6:DI5|7:DI6|8:DI7
9:VS0|10:VS1|11:VS2|12:VS3|13:VS4|14:VS5|15:VS6|16:VS7
VSn = Channel-wise short-circuit protected 24V sensor supply (integrated inside module)
✅ Fixed 1oo2 Pairing (Mandatory for SIL3/PLe/Cat.4)
Channel pairs: DI0&DI4; DI1&DI5; DI2&DI6; DI3&DI7
Only the first channel (DI0/DI1/DI2/DI3) is used for address assignment in configuration; the second channel is for cross-comparison check
- Étapes d'installation mécanique (Standard ET200SP Workflow)
- Rail: 35mm standard DIN rail with reliable earthing. Installation horizontale préférée: 0~60 ℃; installation verticale: 0~50℃
- Station sequence: ET200SP IM interface module at the far left, then BaseUnits in sequence. The first BaseUnit must be type A0 light-colored, dark B0 cannot start the station
- Mount BaseUnit: Snap onto DIN rail and lock rightward. BaseUnits connect end to end; internal spring contacts automatically connect the backplane bus. F-modules can only use A0 BU
- Wiring prep: Pull the 16-pin front connector out of the BaseUnit before crimping wires, avoid live plugging of terminals
- After crimping, reinsert the front connector into BaseUnit → Clip the F-DI electronic module from top until audible click
- Attach CC01 color label to prevent mixing with other BaseUnit types
- Mise à la terre: Shield of control cabinet and signal cables single-point grounded. Safety cables recommended shielded, routed separately from power cables
Classe de protection: IP20, installation en armoire uniquement, not for outdoor exposure
- Power Supply Options
Option A: Use built-in VS supply (Recommended for safety sensors, Arrêt d'urgence, barrières de sécurité)
Each VSn provides independent 24V+ with short-circuit diagnosis. One VS only supplies its matched sensor group
Exemple: VS0 powers the sensor group for DI0/DI4; VS1 powers DI1/DI5 group, and so on
Avantage: Short-circuit only triggers fault alarm for that individual channel without affecting other safety channels; wire break and short-circuit of supply circuit can be diagnosed
Option B: External 24V supply for sensors (Active OSSD light curtain, laser scanner)
VS terminals unused. Only two OSSD signal wires connect to DI channels. 0V of external 24V must be equipotential with PLC system M to avoid false alarms caused by potential difference
Module operating power: Supplied from L+/M bus of A0 BaseUnit, fed by power supply at IM side
- Three Typical Wiring Schemes
① 1oo2 Dual-channel Wiring (Dry-contact E-stop / Barrière de sécurité, SIL3/PLe)
Take DI0+DI4 pair as example (le plus largement utilisé)
- VS0 (Pin9) → Contact 1 of safety switch
- Output of safety switch contact1 → DI0 (Broche1)
- VS4 (Pin13) → Contact 2 of safety switch
- Output of safety switch contact2 → DI4 (Broche5)
- Common 0V of switch connected to system 24V M
Important: Never short the two contact signals! Module continuously compares DI0 and DI4 level; mismatch triggers deactivation and fault alarm. Normally closed dual contacts are standard for E-stop to meet safety requirements.
② 1oo2 Active OSSD (Barrière immatérielle de sécurité, Laser Scanner)
Two OSSD outputs from light curtain are active 24V signals, no VS supply required
- OSSD1 → DI0 (Broche1)
- OSSD2 → DI4 (Broche5)
- Light curtain powered by external 24V, 0V tied to PLC M
Configuration: 1oo2 evaluation mode to verify synchronous status of two OSSD signals
③ 1oo1 Single-channel (Only PLd / SIL2, NOT for E-stop or safety gates)
One DI channel for one sensor, powered by corresponding VSn
Exemple: VS0 → Sensor +, sensor signal → DI0; DI4 unused. Configure 1oo1 mode in hardware
Avertissement: 1oo1 cannot achieve PLe / Cat.4, forbidden for high-risk workstations
- TIA Portal Configuration Points After Wiring
- Select 6ES7136-6BA00-0CA0 in hardware configuration, assign PROFIsafe target address (F-address)
- Select channel evaluation mode: 1oo1 / 1oo2. 1oo2 must strictly follow pairing rule 0&4, 1&5, 2&6, 3&7
- Channel delay: 0.4~20ms configurable for chatter suppression; 0.4~2ms typical for E-stop
- Deactivation setting: Single-channel deactivation / full module deactivation; define deactivation reset method (F-Ack inside safety program)
- Download hardware configuration and safety program, complete F-signature validation, confirm PROFIsafe communication fault-free online
- Online test: Actuate safety sensor and observe channel LEDs. Mismatch in 1oo2 triggers DIAG red light and channel F red light
- Description du voyant LED
PWR green: Module power supply OK
DIAG: Green = Normal; Red = F comms fault / deactivation / module failure
CHx green: Channel logic ON (signal=1)
Fx red: Rupture de fil, court-circuit, dual-channel mismatch, supply fault on this channel
- Règles critiques & Field Pitfalls
- Do not short DI0 and DI4 under 1oo2 mode, this will trigger immediate fault
- VS cannot be cross-channel paralleled (par exemple. VS0 cannot power DI0 and DI1 sensors together, independent short-circuit diagnosis will be lost)
- Separate routing for safety cables and power cables to avoid interference and unintended deactivation
- Equipotential bonding: All safety sensor 0V must share the same M potential with PLC. Floating ground causes random false alarms
- Never hot-swap module or front connector. Cut off safety circuit power before wiring
- The module diagnoses wire break and short-circuit, but the field cables must be safety-certified cables
- Commissioning Sequence
Éteindre & wire → Check continuity and no short-circuit → Power on → Download hardware + safety program in TIA → Establish PROFIsafe communication → Test each safety sensor → Trigger deactivation and test reset function → Safety acceptance
SIMATIC S7 6ES7 Automation Electronic Module List (Grouped by Series, including ET200SP F-modules you queried)
Prefix rule: 6ES7 = SIMATIC S7 electronic module
Suffix grade identifier: BA=Basic / ST=Standard / HF=High Function / HS=High Speed / F=Fail-safe (PROFIsafe)
- ET200SP Distributed I/O Modules (6ES713x, your primary series)
Entrée numérique DI
| Numéro de commande. | Description |
| 6ES7131-6BH01-0BA0 | DI 16×24VDC ST |
| 6ES7131-6BF00-0BA0 | DI 8×24VDC ST |
| 6ES7131-6BH00-0BA0 | EN 16×24VDC HF |
| 6ES7131-6FD00-0BB1 | DI 4×120..230VAC ST |
Digital Output DQ
| Numéro de commande. | Description |
| 6ES7132-6BH01-0BA0 | DQ 16×24VDC 0.5A ST |
| 6ES7132-6BF00-0BA0 | DQ 8×24VDC 0.5A ST |
| 6ES7132-6BD20-0BA0 | DQ 4×24VDC 2A HF |
| 6ES7132-6HD00-0BB1 | DQ 4×120..230VAC 2A ST |
Entrée analogique AI
| Numéro de commande. | Description |
| 6ES7134-6HD01-0BA1 | AI 4×U/I ST |
| 6ES7134-6GF00-0AA1 | AI 8×U/I HF |
| 6ES7134-6JD00-0DA1 | AI 4×TC Thermocouple HS |
| 6ES7134-6PA00-0CU0 | AI Energy Measurement Module |
| 6ES7134-6JF00-0CA1 | AI 4×RTD Resistance Temperature Detector |
Analog Output AQ
| Numéro de commande. | Description |
| 6ES7135-6HD00-0BA1 | AQ 4×U/I ST |
| 6ES7135-6FB00-0BA1 | AQ 2×U/I HF |
✅ Fail-Safe F-Modules (PROFIsafe, votre modèle cible)
| Numéro de commande. | Description |
| 6ES7136-6BA00-0CA0 | F-DI 8×24 VCC HF (Ancienne version, replaced by 6BA01) |
| 6ES7136-6BA01-0CA0 | F-DI 8×24 VCC HF (Upgraded direct replacement) |
| 6ES7136-6DB00-0CA0 | F-DQ 4×24VDC 2A PPM |
| 6ES7136-6DC00-0CA0 | F-DQ 8×24VDC 0.5A |
| 6ES7136-6AA00-0CA0 | F-AI 4×I 0/4-20mA |
ET200SP BaseUnit BU
| Numéro de commande. | Description |
| 6ES7193-6BP00-0BA0 | A0 Light-colored BU (For F-modules, CC01 marking) |
| 6ES7193-6BP00-0DA0 | B0 Dark-colored BU |
- S7-1500 / ET200MP Signal Modules (6ES753x)
Numérique
6ES7521-1BL00-0AB0: DI 32×24VDC HF
6ES7521-1BH00-0AB0: EN 16×24VDC HF
6ES7522-1BL01-0AB0: DQ 32×24VDC 0.5A HF
6ES7522-1BH01-0AB0: DQ 16×24VDC 0.5A HF
Analogique
6ES7531-7NF00-0AB0: AI 8×U/I HF
6ES7531-7KF00-0AB0: AI 8×U/I/RTD/TC ST
6ES7532-5HD00-0AB0: AQ 4×U/I ST
6ES7532-5NB00-0AB0: AQ 2×U/I ST
6ES7536-1MF00-0AB0: F-AI 8×I 4-20mA Safety Analog Input
- S7-1200 Signal Modules SM (6ES722x / 6ES723x)
Numérique
6ES7221-1BF32-0XB0: SM1221 DI 8×24VDC
6ES7221-1BH32-0XB0: SM1221 DI 16×24VDC
6ES7222-1BF32-0XB0: SM1222 DQ 8×24VDC Transistor
6ES7222-1BH32-0XB0: SM1222 DQ 16×24VDC Transistor
6ES7223-1BL32-0XB0: SM1223 16DI/16DQ
Analogique
6ES7231-4HD32-0XB0: SM1231 AI 4×U/I
6ES7231-5ND32-0XB0: SM1231 AI 8×U/I
6ES7232-4HD32-0XB0: SM1232 AQ 4×U/I
6ES7234-4HE32-0XB0: SM1234 AI4/AQ2
- S7-200 SMART EM Expansion Modules (6ES7288)
6ES7288-2DE16-0AA1: EM DE16 16DI
6ES7288-2QT16-0AA1: EM QT16 16DQ Transistor
6ES7288-3AE04-0AA1: EM AE04 4AI
6ES7288-3AR04-0AA1: EM AR04 4RTD
6ES7288-3AT08-0AA1: EM AT08 8TC
- IM Interface Modules (ET200SP / MP Communication Base)
6ES7155-6AA01-0BN0: IM155-6 PN ST ET200SP PROFINET Interface
6ES7155-6BA00-0CN0: IM155-6 DP ST ET200SP PROFIBUS Interface
6ES7545-5DA00-0AB0: IM155-5 PN ET200MP
- Model Encoding Decoding Guide
6ES7 136 6BA00 0CA0
- 6ES7: SIMATIC S7 electronic module
- 136: ET200SP fail-safe F-I/O
- 6BA00: F-DI 8×24 VCC HF
- 0CA0: Version and compatible BaseUnit type
Series segment identification:
13x = ET200SP I/O
52x/53x = S7-1500 / ET200MP I/O
22x/23x = S7-1200 SM signal module
288 = S7-200 SMART EM module