Marque: TENDU (Turquie)
Produit: 3-Phase Digital Adjustable Overvoltage / Sous-tension & Protection de séquence de phases Relais (Relais de surveillance de tension)
- Explication du code modèle
DGK: Series of 3-phase digital voltage control relays
04: Function code → Overvoltage + Sous-tension + Phase Sequence Monitoring
F: Version à affichage numérique (enhanced model)
Sibling model: DGK-04PF with extra phase loss protection
- Fonctions de protection
- 3-protection contre les surtensions de phase (U>)
- 3-protection contre les sous-tensions de phase (U<)
- Séquence de phases / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
- Real-time digital display of 3-phase line voltages + fault LED indication
- Spécifications techniques
Alimentation & mesures: 3-phase AC380V, no neutral required, L1/L2/L3 only
Fréquence: 50/60Hz auto-adaptive
Undervoltage setting range: 230~360V AC
Overvoltage setting range: 400~460V AC
Temps de retard de défaut: 0.1~10s adjustable
Output contact: 1NON+1NC (SPDT), 5UN / 250V AC resistive load
Montage: Montage sur rail DIN standard
Température de fonctionnement: -10℃ ~ +55℃
Précision de mesure: ±1V
- Définition du terminal
L1, L2, L3: 3-phase voltage input
1, 2, 3: Relay changeover contacts
Terminal 1: Caroline du Nord (Normalement fermé)
Terminal 2: COM (Commun)
Terminal 3: NON (Normalement ouvert)
Câblage standard (Moteur / Air Compressor / Pompe à eau)
Contactor coil circuit: Wire in series with 2-3 (NON)
Alarm lamp / Buzzer: Connectez-vous à 1-2 (Caroline du Nord)
Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.
- Câblage & Manuel de mise en service
Boutons du panneau & Indicateurs
U: Overvoltage setting key
U< : Undervoltage setting key
t : Time delay setting key
Affichage numérique: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages
DEHORS: Relay output indicator (ON under normal condition)
U: Overvoltage fault LED
U< : Undervoltage fault LED
PHASE: Phase sequence error LED
Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.
Pre-power Check (Obligatoire)
- Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
- Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
- Keep away from inverters and large contactors to avoid strong electromagnetic interference.
Step-by-step Commissioning
Étape 1: Allumer
Switch on 3-phase supply, digital display lights up:
OUT ON: Tension & phase sequence normal, relay energized, 2-3 fermé.
PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).
U/ U< SUR: Voltage exceeds threshold, protection activated.
Étape 2: Set Undervoltage U< (Recommandé: 340V for 380V systems)
- Short press the U< key to enter undervoltage setup.
- Press U< to increase value; press t to decrease value.
- Attendez 4 seconds without operation to auto-save and return to voltage monitoring screen.
Setting range: 230~360V
Étape 3: Set Overvoltage U(Recommandé: 420V for 380V systems)
- Short press the Ukey to enter overvoltage setup.
- Press Uto increase value; press t to decrease value.
- Auto-save after 4 seconds idle.
Setting range: 400~460V
Étape 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)
- Short press the t key to enter delay setup.
- U= increase time; U< = reduce time.
- Settings take effect after auto-save.
Gamme: 0.1~10s; same delay applies for fault trip AND automatic reset after voltage recovers.
Étape 5: Phase Sequence Function Note
DGK-04F: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 ouvre.
If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.
Étape 6: Functional Test
- Statut normal: OUT stays ON, 2-3 fermé, contactor can energize.
- Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 ouvre.
- Simulate undervoltage: Lower supply voltage or raise the U< seuil; U< LED lights up, le relais se désexcite.
- Swap two phases: PHASE fault triggers, relay drops out.
Hystérèse: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.
Paramètres recommandés (AC380V 3-phase Equipment)
Undervoltage U<: 340V
Overvoltage U>: 420V
Time delay t: 2s
Liste de dépannage
- PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
- OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
- Faux déclenchements fréquents: Increase time delay t; check for grid voltage flicker or loose terminal connections.
- Flashing reading on one phase: Abnormal voltage on that phase.
- Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.
Strict Prohibitions
❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).
❌ Do not feed single-phase 220V power into L1/L2/L3.
❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.
Temporisation (t) Setting for TENSE DGK-04F
Delay range: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.
Étapes de fonctionnement
- While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
- Press U= increase time value
- Press U< = decrease time value
- Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.
✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.
Compresseurs d'air & pompes à eau: 2s preferred
Fast cut-off protection requirement: set to 0.5s
Key Logic
En cas de surtension / sous-tension / reverse phase occurs: Le relais commence à chronométrer; contacts only open after the delay expires.
When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.
Phase sequence faults also follow this same time delay setting.
Problèmes courants
New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.
Unwanted frequent tripping: Increase the t value.
Slow recovery after fault: Reduce the t value appropriately.
Full Model List of TENSE (Turquie) DGK Digital Voltage Monitoring Relays
DGK series: Digital readout, adjustable over/undervoltage, Montage sur rail DIN, no neutral required (L1/L2/L3 line voltage detection).
Suffix definition: F = digital display; P = phase loss protection added
| Modèle | Phase | Fonctions principales | Remarques |
| DGK-01 | Monophasé | Adjustable overvoltage + sous-tension, affichage numérique | AC220V single-phase monitoring |
| DGK-03 | 3-phase | Sur/sous-tension réglable, no phase sequence check, affichage numérique | For loads with no rotation direction requirement |
| DGK-04 | 3-phase | Sur/sous-tension réglable, no phase sequence, analog knob (pas d'affichage) | Analog version without digital readout |
| DGK-04F | 3-phase | Surtension + Sous-tension + Phase Sequence, affichage numérique | Votre modèle actuel; no phase loss protection, phase sequence check cannot be disabled |
| DGK-04PF | 3-phase | Surtension + Sous-tension + Phase Sequence + Perte de phase, affichage numérique | Upgraded model of DGK-04F, widely used on air compressors & refroidisseurs |
Analog Knob Series (Série GK, No Digital Display)
| Modèle | Fonction |
| GK-03 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04F | 3-phase over/undervoltage + séquence de phases |
Phase Sequence / Perte de phase / Unbalance Protection Series (FK / FKV Series, without continuous voltage adjustment window)
These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.
FK-04: Perte de phase + séquence de phases, fixé 30% unbalance threshold
FK-05 / FK-05F: Perte de phase + séquence de phases, unbalance adjustable 5~25% (F = digital display)
FK-14 / FK-14P: Séquence de phases + perte de phase; P model with PTC motor thermal protection
FKM-05 / FKM-05F: Adjustable unbalance, séquence de phases, perte de phase
FKT-06 / FKT-06PF: 3-déséquilibre de phase + perte de phase + séquence de phases; PF with PTC input
FKV-03 / FKV-03F / FKV-03DF / FKV-03HF: Perte de phase, séquence de phases, déséquilibrer; some versions require neutral N
FKV-14 / FKV-14P: Economy phase sequence & phase loss relay; P with PTC protection
Suffix Quick Reference
F: Digital display type
P.: Phase loss protection function
T: Built-in PTC motor temperature protection
DF/HF: Adjustable unbalance ratio
N: Requires neutral wire (3P+N)
Guide de sélection rapide (Most Popular Engineering Models)
- Only over/undervoltage monitoring, no rotation check: DGK-03
- Sur/sous-tension + anti-reverse phase (motor rotation control): DGK-04F
- Sur/sous-tension + anti-reverse phase + protection contre la perte de phase: DGK-04PF (first choice for air compressors & refroidisseurs d'eau)
- Only phase loss & unbalance monitoring without voltage threshold adjustment: FK-05F / FKV-14
Common Specifications for All DGK 3-phase Models
Sortir: 1NO+1NC SPDT contact, 5A/250VAC
Time delay: 0.1~10s adjustable (shared trip & reset delay)
Plage de tension: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)
Pouvoir & measurement input: L1/L2/L3 only, no neutral wire needed
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur




















NH42-63-318x560.png)