Status: EOL Discontinued (since 2017); Direct replacement: G3PA-220B-VD-X
Type: Single-hase SSR, integrated heat sink, zero-cross triggering, opto-coupler isolation; the mainstream model for temperature control & heating loads
✅ Model Number Breakdown
G3PA: G3PA series power solid state relay
220: 20A rating, AC24~240V
B: Built-in heat sink
VD: DC control input (DC5~24V)
📌 Core Electrical Specifications
Input (Control Side)
Rated input voltage: DC 5~24V
Operating voltage range: DC 4~30V
Input current: ≤7mA @ 25℃
Must-operate voltage: ≤DC4V
Must-release voltage: ≥DC1V
Polarity: DC positive & negative, no reverse connection allowed
Isolation: Opto-triac isolation; dielectric strength AC4000V / 1min (input ↔ output)
Output (Load Side)
Load voltage: AC24~240V (50/60Hz)
Operating voltage range: AC19~264V
Rated load current: 0.1~20A @ 40℃ (derating required above 40℃ ambient temperature)
Non-repetitive surge current: 220A (60Hz, 1 cycle)
Repetitive peak off-state voltage VDRM: 600V
On-state voltage drop: ≤1.8V RMS
Leakage current: ≤5mA@AC100V; ≤10mA@AC200V
Trigger mode: Zero-cross turn-on
Operate / release time: ≤½ AC cycle +1ms
I²t rating: 260 A²·s
🧱 Environmental & Mechanical Data
Operating temperature: -30℃ ~ +80℃ (no condensation)
Storage temperature: -30℃ ~ +100℃ (no icing or condensation)
Humidity: 45~85% RH
Mounting: DIN rail mounting or M4 screw fixing
Weight: approx. 340g
Certifications: UL508, cUL, EN60950-1
🛠️ Typical Applications
- Temperature & Heating Control (Primary Use)
- Plastic machinery: Barrel heater bands for injection moulding machines, extruders, PET blow moulders with PID cycle control via temperature controllers
- Food processing equipment: Industrial ovens, drying lines, heat sealers, furnaces, constant-temperature water/oil baths
- Packaging machinery: Heat sealers, hot foil stamping machines, thermoforming equipment
Advantage: Zero-cross switching suppresses current surges and extends heater life; directly driven by PLC or temperature controller outputs
- HVAC & Environmental Equipment
Duct electric heaters, dehumidifier heating modules, auxiliary heating for thermostatic air conditioners, thermal cycling test chambers
Small fans & circulating water pumps (resistive / lightly inductive loads; NOT suitable for direct start-up of heavy-duty motors)
- Automation Production & Packaging Lines
AC solenoid valves, thermo-pneumatic actuators, small 220V transformers, indicator light banks
Conveyor auxiliary heating, labeler heating modules
Feature: Non-contact switching with no arcing; preferred for control cabinets with dust and low explosion risk
- Lighting & Building Automation (Resistive Lamp Loads)
Industrial lighting circuits, lamp ageing racks, infrared heating lamps (incandescent lamps only)
⚠️ Note: LED & fluorescent lamps suffer leakage current causing faint glow; install bleeder resistors in parallel.
- Burn-in & Test Equipment
Power ageing racks, load test benches, component high-temperature ageing boards with independent on/off control for multi-channel AC loads
Low-noise power switching for laboratory instruments without spark interference
✅ Application Limits & Selection Notes
Recommended loads: Resistive heating loads first; frequent switching (several times per second max); driven by DC24V PLC outputs; DIN rail cabinet installation
NOT suitable for: High-frequency PWM voltage regulation, direct starting of large motors, heavy inductive loads (large inductors, contactor coils), capacitive loads
Important note: This model is discontinued; new projects adopt G3PA-220B-VD-X, fully pin-to-pin and electrically compatible for direct replacement
⚠️ Troubleshooting Guide
- Output permanently ON: Thyristor breakdown caused by short-circuit load surge
- No switching action: Insufficient input voltage, insufficient PLC output current, reversed DC polarity
- Intermittent switching: Overheating due to poor heat dissipation, loose terminals, current exceeding derating curve
- Lamp faint glow from leakage current: Add parallel bleeder resistors for lamp loads
🔁 Replacement Options
- Original direct replacement: G3PA-220B-VD-X (same pinout & specs, current production)
- Higher current within the same series: G3PA-240B-VD (40A), G3PA-260B-VD (60A)
- Domestic alternative: Zero-cross SSR 20A/AC240V from Ximaden / Yangming
📎 Terminal Definition (4 terminals total)
+,-: DC control input (polarized)
L, OUT : AC load circuit (phase sequence does not matter for zero-cross type)
Complete Model List of OMRON Solid State Relays (SSR)
Suffix explanation: VD = DC control; VA = AC control; -X = new version replacing discontinued old models; B = integrated heat sink; G3PA is your target series
- G3PA Series-Integrated Heat Sink Single-Phase SSR (Heating, DIN Rail Mount)
Old EOL models: G3PA-210B-VD / G3PA-220B-VD / G3PA-240B-VD / G3PA-260B-VD / G3PA-420B-VD
New pin-compatible replacements with suffix -X
G3PA-210B-VD-X|AC24~240V, 10A, DC5~24V control
G3PA-220B-VD-X|AC24~240V, 20A, DC5~24V control (direct replacement for G3PA-220B-VD)
G3PA-240B-VD|AC24~240V, 40A, DC5~24V control
G3PA-260B-VD|AC24~240V, 60A, DC5~24V control
G3PA-420B-VD / -2|AC200~480V, 20A, DC12~24V
G3PA-430B-VD / -2|AC200~480V, 30A, DC12~24V
G3PA-450B-VD-2|AC200~480V, 50A, DC12~24V
Interchangeable power cartridges: G32A-A10/-A20/-A40/-A60/-A420
- G3PE Series-Compact Slim Heat Sink SSR (Single & Three-Phase Heaters)
Single-phase:
G3PE-215B / 225B / 235B / 245B (15/25/35/45A, AC240V, zero-cross / random options)
Three-phase solid-state contactors:
G3PE-515B / 525B / 535B / 545B (3-phase 380V heating loads)
- G3PJ Series-Low Heat SSR for Dense Cabinet Installation
G3PJ-225B-VD, G3PJ-225B-VD-PU (Push-in spring terminals), 25A single-phase
- G3PF Series-Intelligent SSR with Built-in CT (Heater Burnout & SSR Short-Circuit Detection)
Single-phase: G3PF-225B / 235B / 245B
Three-phase: G3PF-525B / 535B / 545B
- G3PC Series-Fault Detection SSR with Alarm Output
For safety monitoring in temperature control loops with fault signal output
- G3PH Series-High-Current High-Power SSR
G3PH-275B: AC240V, 75A
G3PH-475B / 4150B: AC480V, 75A / 150A
- G3NA Series-Puck-Style SSR (No Built-in Heat Sink; External Heat Sink Required)
5~90A bare power core, cost-effective with separate heat sink
G3NA-205B, 210B, 220B, 240B, 260B, 420B, 440B, 460B, 490B
- G3NE Series-Low-Cost Compact SSR (Built-in Equipment, 5~20A)
G3NE-210T, 220T, 210SL, 220SL; small size for cabinet internal mounting
- G3F / G3FD Series-Plug-in Socket SSR (MY Relay Footprint)
G3F-203SN, G3FD-102SN; DIN socket pluggable, small-power IO & solenoid valves
- G3H / G3HD Series-High-Current Plug-in SSR (LY Relay Footprint)
G3H-205B, G3H-210B; socket installation
- G3R-I/O Series-Isolated Interface SSR (High Insulation for PLC Signal Isolation)
Ultra-thin IO isolation SSR for PLC signal separation
- G3RV Series-6mm Ultra-Slim DIN Rail SSR (G2RV Relay Form Factor)
G3RV-SR, G3RV-ST; high-density control cabinets
- PCB-Mount Miniature SSR (Low Current)
G3MC: Ultra-small PCB SSR, 1A / 2A
G3TB: PCB-mounted SSR with status indicator
- G3PW Series-Single-Phase Power Controller (Not Standard SSR; Phase-Angle Regulation)
Thyristor power regulator for continuous voltage adjustment, not simple on/off zero-cross switching
Suffix Code Legend (Quick Selection Guide)
VD: DC5~24V DC input
VA: AC100~240V AC input
B: Integrated heat sink
-X: New production version replacing discontinued old models
-2: 480V high-voltage variant
PU: Push-in spring terminals
SL/SN: Input circuit variations
Prefix 2: AC240V single-phase; Prefix 4/5: AC400/480V (single / three-phase)
Quick Selection Cheat Sheet
Standard heating, DIN rail, 20A → G3PA-220B-VD-X (replaces old G3PA-220B-VD)
Heater burnout monitoring required → G3PF
Three-phase heating → G3PE three-phase / G3PF three-phase
Current above 75A → G3PH
Cost-saving with external heat sink → G3NA
Plug-and-play replacement for mechanical relays → G3F / G3H
Contactor,circuit breaker,sensor,Encoder,PLC,Converter



















NH42-63-318x560.png)