Product Positioning:Stepper electric actuator (power head) for Danfoss ICM motorized valves in refrigeration systems, old A-series, obsolete
✅ Basic Information
Model:ICAD600A, Order code 027H9065
Brand:Danfoss (Refrigeration segment)
Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves
Construction:Stepper motor driven, with valve position feedback, local keypad & display, manual override function
Origin:Poland
📌 Core Electrical Specifications
Power supply:24V DC (+10% / -15%), DC power only
Max current:1.2 A
Control signals:
Analog input:0/4-20 mA, 0/2-10 V DC
Analog output:0/4-20 mA (valve position feedback)
3-channel NPN digital outputs (valve position status, fault, etc.)
Passive dry contact digital input
Protection class:IP67
Ambient temperature:-30 ℃ ~ +50 ℃
Housing:Aluminum body + PBT top cover, net weight approx. 1.2 kg
Connectors:M12 circular connector (4-pin power + 8-pin signal). Pre-assembled cables available as options: 027H0426 (1.5m), 027H0438 (3m), 027H0427 (10m), 027H0435 (15m)
🧩 Control Modes
- Analog modulation:Continuous regulation via EKC347 level controller or PLC with 4-20mA / 0-10V output
- Digital position control
- Local panel manual open, close and calibration
- Compatible with ICAD-UPS power-fail hold module for safe position protection upon power loss
🔁 Replacement Options (Key Section)
Factory successor:ICAD600B (Order No. 027H0485). Mechanically interchangeable, upgraded with OLED screen, Bluetooth APP and RS485 communication. However, wiring logic and parameter programming need verification and adaptation; direct blind replacement is not permitted.
Similar obsolete parts within the same series:027H9075 (ICAD600A, identical hardware to 027H9065, only version/config difference, also obsolete)
⚠️ Fault & Maintenance Notes
Common faults:Loss of communication, valve position non-following, motor stall, blank display, water ingress & oxidation at M12 connectors
Calibration:Full zero & full stroke auto-calibration must be performed after replacement or disassembly
Important:24V AC must NOT be applied directly. A dedicated isolated 24V DC power supply is required; voltage drop shall be calculated for long wiring runs
📎 Application Scope
Industrial ammonia refrigeration, CO₂ transcritical systems, large fluorinated refrigerant chiller packages, used for continuous regulation of liquid level, pressure and superheat (pump recirculation, evaporator, condenser, economizer circuits)
📋 Supporting Documentation
Manuals:AI000086409336 (General ICAD600/900 manual), AN000086415021 (Wiring & commissioning manual)
ICAD600A (027H9065) → ICAD600B (027H0485) Retrofit Checklist
Core conclusion:Mechanically compatible, fits directly on existing ICM20/25/32 valve bodies. But M12 pin assignment, parameter menu and fault logic differ; the old cable cannot be plugged in and powered up directly.
- Bill of Materials
| Category | Item | Remarks |
| Main unit | ICAD600B, Order No. 027H0485 | Replaces 027H9065, compatible with ICM20/25/32 |
| Optional pre-made cable | 027H0426 (1.5m) / 027H0438 (3m) / 027H0427 (10m) | B-series dedicated M12 power + M12 signal cable. Old A-series cables have different pinouts and reuse is not recommended |
| UPS power-fail hold | 027H0388 ICAD UPS module | Compatible with A & B; B has revised logic for UPS detection pin |
| Consumables | Molycote 55 grease, O-rings | For valve stem magnetic coupling seal; lubrication mandatory after disassembly to prevent water ingress failure |
| Tools | 2.5mm hex key, torque wrench, multimeter, insulating tape | Installation torque: 3N路m, tighten diagonally and evenly |
- Mechanical Retrofit (Low Risk)
✅ Compatibility:Valve seat, magnetic coupling and mounting screw positions match completely; no modification to valve body or bracket required
⚠️ Operating Procedure
- Manually set valve to mid-position first (to prevent valve stem detachment after actuator removal)
- Loosen the 3 fixing hex screws and lift the old ICAD600A vertically
- Inspect magnetic coupling and O-rings on valve body for damage, ice buildup or heavy contamination; remove old grease residue
- Apply Molycote 55 to O-ring groove and O-ring, align magnetic coupling and lower ICAD600B vertically
- Tighten the 3 screws diagonally at a controlled torque of 3N·m; avoid one-sided over-tightening
- Verify housing sealing surface is fully seated without warping
Risk points:Misaligned magnetic coupling or missing grease → water ingress, magnetic coupling slip and valve position drift later
- Electrical Retrofit (Critical! Pinout Incompatibility, Highest Risk Area)
ICAD600A:M12 power 3-pin; M12 signal 7-pin
ICAD600B:M12 power 4-pin; M12 signal 8-pin; independent 4-pin M12 RS485 port exclusive to B-series
4-pin M12 Power Connector (B)
Pin I Black:Fail-safe 19-24V DC (UPS backup power, optional)
Pin II White:Main 24V DC+
Pin III Brown:24V DC(GND)
Pin IV Blue:UPS status feedback signal (Not available on A-series)
8-pin M12 Signal Connector (B)
Pin A Black:Common terminal for fault output (NPN)
Pin B Brown:Fully open limit output
Pin C Red:Fully closed limit output
Pin D Orange:Signal GND
Pin E Yellow:Analog input (0/4-20mA /0/2-10V)
Pin F Pink:Analog feedback output (valve position 0/4-20mA)
Pin G Grey:Digital input DI (Enable / Safety close)
Pin H Violet:Reserved
Comparison with A: Wire color sequence for digital outputs and analog input differs. Direct plug-in of old cable will burn signal channels or trigger faults.
✅ Two implementation options:
Option 1: Purchase factory pre-assembled B-series cables, re-terminate wiring at cabinet terminals one-to-one (Recommended for reliable site performance)
Option 2: Rewire existing cable, re-crimp M12 contacts according to above definition and apply clear marking
Power requirement remains 24VDC SELV isolated power supply, max 1.2A, same as A-series; 24V AC is not supported.
- Host / Controller Program Modification (EKC347 / PLC)
- Analog control loop (4-20mA control)
Control signal range: 0/4-20mA, 0-10V definition unchanged. B internal input resistance differs; range setting on PLC/EKC side can stay, but valve position feedback reading calibration is recommended.
A: Valve feedback 4-20mA; B also 4-20mA with improved load capacity up to 500Ω
- Digital position signals (Full open, Full close, Fault)
All three are NPN open-collector outputs with identical function definition. Common terminal pin has changed; PLC input common point wiring must be adjusted accordingly.
- Existing EKC347 parameters:
Superheat, liquid level setpoints and PID gains can be retained
Valve body model must be reselected inside B actuator (parameter i26). B will automatically calibrate stroke
- RS485 (New for B): Not required if original system has no bus. If bus communication is planned later, Modbus mapping and terminating resistor need to be added.
- Commissioning & Calibration Procedure (Mandatory, Skipping Causes Position Error)
- Double-check wiring, power on without load first, check OLED screen (B uses OLED, A uses segment LCD)
- Enter parameter menu, set valve body type: ICM20/25/32 (i26) → trigger automatic stroke calibration
- Calibration sequence: Auto full close → full open → full close, zero and full stroke recorded
- Manual mode test: Open / close via local panel, confirm smooth movement without sticking
- Auto mode: Apply 4mA / 20mA reference signal, verify linear tracking of valve position feedback
- Fault simulation: Signal loss, power loss, check fault output and UPS safe position logic
- Save parameters and back up configuration (B supports Bluetooth APP commissioning via Danfoss BT tool)
Important:A-series fault code list cannot be used for B; B alarm system is revised and some alarm definitions are different.
- Risk Checklist & Pitfall Avoidance
- ❌ Plug old A cable directly into B: Pin misalignment → burnt analog channels, power short circuit, A1/A2 alarms
- ❌ Skip calibration before commissioning: Zero drift, incomplete closure or incomplete opening
- ❌ Omit Molycote 55 application: Magnetic coupling water ingress, slip and position loss at low temperature
- ❌ Ignore blue UPS pin: Continuous UPS fault alarm on B if blue wire is not connected when UPS module is fitted
- ❌ Torque over 3N·m: Housing deformation and seal failure
- Acceptance Test Items
Static: Valve position 0%, 50%, 100%, feedback error ≤±2%
Dynamic: Step response test, no oscillation or sticking
Fault conditions: Wire break, power loss, stall; controller receives fault signal correctly
Environmental protection: IP67, proper connector sealing, no condensation ingress in humid conditions
Recurring Faults after ICAD600A (027H9065) → ICAD600B (027H0485) Replacement, Causes & Troubleshooting
Premise: Most issues originate from incorrect pin wiring, missing calibration, UPS logic difference, impedance / load mismatch. Mechanical seizure of valve body is a pre-existing condition, not a new fault introduced by replacement.
- Power-on Faults (Alarm at power-up, no display, cyclic reboot)
- Blank OLED, no illumination
Cause: Wrong M12 power pin assignment, reversed 24VDC polarity, insufficient power capacity, excessive voltage drop, water ingress & oxidation at M12 plug
Troubleshooting: Measure Pin II(+) & III(-) with multimeter; confirm DC24V not AC24V; measure voltage at actuator end for long cable runs
- Cyclic reboot & flashing screen after power-up
Cause: Blue UPS Pin IV left floating without connection; old A-type UPS module mismatched; high ripple power supply
Remedy: Disable UPS detection in menu if UPS module is not used; do not leave pin floating and tolerate constant alarm
- Power fault alarm immediately after energization (B exclusive alarm)
Cause: Forced reuse of old cable, cross connection between power and signal lines, internal short in connector
- Calibration Related Faults (Most frequent after swap)
- Auto-calibration aborted, stops mid-cycle, stroke error alarm
Triggers:
Misaligned magnetic coupling, coupling slip, O-ring binding; valve stem offset during assembly
Contamination, ice plug or spool seizure in valve body (A may tolerate marginal friction while B has tighter detection)
Incorrect mounting torque (over-tightened coupling or insufficient torque leading to slip)
Wrong valve body selection at parameter i26 (selected larger ICM size)
Symptom: Calibration halts halfway and cannot complete full close → full open travel
- Calibration successful, but valve fails to close tight / over-travel / cannot reach full open
Cause: Spool was not set to mid-position before calibration; worn seat, foreign debris, abnormal magnetic coupling gap
Feature: 4mA command does not correspond to 0% feedback, 20mA cannot reach 100%
- Control Signal Loop Faults (4-20mA / 0-10V)
- Control signal applied, valve stationary, position reading fixed
Cause: Wrong connection at analog input Pin E; signal GND not common with controller GND; signal type mismatch (menu set for voltage while current signal is applied, or vice versa)
Key note: B input impedance differs from A; verify drive capability of EKC347 or PLC analog output
- Inaccurate / drifting feedback, feedback inconsistent with actual valve position
Cause: Wrong wiring at feedback Pin F; feedback loop overloaded resistance, loose GND connection, incomplete calibration
Symptom: Controller reading differs from local actuator display
- Valve oscillation, small continuous hunting
Cause: PID parameters inherited from A; B stepper response speed differs; poor shielding earthing causing interference; signal cable routed together with power cable
Note: PID tuned for A often oscillates directly on B and requires fine adjustment
- Digital Output Faults (Full Open / Full Close / Fault NPN)
- PLC fails to receive full-open / full-close signal or signal stays permanently ON
Cause: A & B have different common terminal definition for digital outputs. Reused old cable leads to wrong common connection; reversed external supply for NPN loop
Critical point: B’s three DO channels share Pin A (fault common), which is completely different from A
- Persistent fault output with normal valve operation
High incidence: UPS detection enabled without UPS module fitted, B interprets status as UPS fault; UPS function not disabled in menu
- UPS Power-Fail Hold Specific Faults (with 027H0388 fitted)
- Fails to move to safe position on power loss or constant UPS alarm at startup
Cause: B blue Pin IV on power plug is UPS status feedback, which does not exist on A; legacy UPS wiring incompatible; aged UPS battery
Pitfall: A UPS only required power feed; B requires both power and status feedback wire otherwise permanent alarm
- Communication Faults (RS485 Modbus, New for B)
- No Modbus data read, intermittent communication
Cause: Wrong wiring on 4-pin M12 communication port; missing terminating resistor; duplicate address; mismatched baud rate; poor shield earthing
Tip: Bus port can be left unconnected if unused for analog control; avoid accidental signal connection to this port
- Low Temperature / Site Environmental Faults (Common for NH₃ & CO₂ transcritical systems)
- Random position loss and slip at low temperature without fixed alarm
Cause: Molycote 55 grease not applied during assembly; missing or damaged O-ring, moisture entering magnetic coupling and freezing
Feature: Calibration passes at ambient temperature, random drift when cooled, temporary recovery after reboot
- Condensation inside connector, intermittent sporadic faults
Cause: Aged old M12 connector seal; poor crimp sealing after reworking cable, IP67 rating compromised
- Misleading Apparent Faults (Logic Difference, Not Actual Failure)
- Different valve movement at identical 4mA setpoint compared with A
Not a fault: B stroke algorithm, dead band and stepper speed parameters are independent; loop matching is required
- Alarm codes not found in A manual
B alarm table rewritten; many A alarm IDs do not exist on B
- Different local keypad operation logic
Menu navigation and manual mode entry sequence changed; commissioning personnel may mistake for actuator malfunction
- Fast Troubleshooting Sequence (On-site Priority)
- Verify every M12 pin assignment (power, signal, UPS) first to rule out miswiring
- Confirm power supply: Stable 24V DC, ≥22V at actuator terminals under load
- Check menu settings: Signal type (current / voltage), valve body model i26, UPS enable / disable
- Run a complete auto-calibration again
- Check common ground and shield bonding, eliminate interference
- Test in manual mode alone to isolate whether fault lies in actuator hardware or upstream controller signal
Danfoss ICAD Stepper Electric Actuator Full Model & Order Code List (For ICM Refrigeration Valves)
Description: ICAD = Stepper motor actuator for ICM / ICMTS regulating valves and CVE pilot valves. Divided into A-series (old, obsolete), B-series (new, active), TS transcritical dedicated variant. All models run on 24V DC.
- A-series (Old generation, 027H9xxxx, Obsolete)
| Model | Order Code | Compatible Valve | Remarks |
| ICAD600A | 027H9065 | ICM20/25/32 | Your current model, segment LCD, no RS485, no Bluetooth |
| ICAD600A | 027H9075 | ICM20/25/32 | Same ICAD600A, version variation |
| ICAD600A | 027H9120 | ICM20/25/32 | Same specification |
| ICAD600A-TS | 027H9078 | ICMTS20~ICMTS80 | CO₂ transcritical dedicated |
| ICAD900A | 027H9101 | Large bore ICMTS | CO₂ transcritical dedicated |
| ICAD1200A | 027H9077 | ICM40/50/65/100/125/150 | High torque A version |
| ICAD1200A | 027H9122 | ICM40/50/65/100/125/150 | Same ICAD1200A |
- B-series (Current active, 027H04xx, OLED + Bluetooth, optional RS485 / Ethernet)
ICAD600B (For ICM20 / ICM25 / ICM32)
| Model | Order Code | Configuration |
| ICAD600B | 027H0485 | Display, Bluetooth, RS485 (Most common, direct replacement for A) |
| ICAD600B | 027H0486 | Display, Bluetooth, Ethernet |
| ICAD600B | 027H0488 | No display, Bluetooth, RS485 |
| ICAD600B | 027H0489 | No display, Bluetooth, Ethernet |
ICAD1200B (For ICM40~ICM150)
| Model | Order Code | Configuration |
| ICAD1200B | 027H0490 | Display, Bluetooth, RS485 |
| ICAD1200B | 027H0491 | Display, Bluetooth, Ethernet |
| ICAD1200B | 027H0492 | No display, Bluetooth, Ethernet |
| ICAD1200B | 027H0493 | No display, Bluetooth, RS485 |
ICAD600B-TS:CO₂ transcritical dedicated, separate order family for ICMTS valve bodies
- Accessories & Cable Order Codes (ICAD compatible)
| Description | Order Code | Note |
| ICAD UPS power-fail hold module | 027H0388 | Works with A & B (B has UPS status detection pin) |
| Pre-assembled cable 1.5m | 027H0426 | M12 power + M12 signal, B-series only |
| Pre-assembled cable 3m | 027H0438 | M12 power + M12 signal |
| Pre-assembled cable 10m | 027H0427 | M12 power + M12 signal |
| Pre-assembled cable 15m | 027H0435 | M12 power + M12 signal |
| M12 connector spare kit | 027H0430 | Signal plug spare part |
| Protective dust cap | 027H0431 | Top cover protection for actuator |
- Quick Selection Reference
ICM20 / ICM25 / ICM32 → ICAD600A (Obsolete) / ICAD600B (Replacement)
ICM40~ICM150 → ICAD1200A (Obsolete) / ICAD1200B (Replacement)
ICMTS (CO₂ transcritical) → ICAD600A-TS / ICAD900A / ICAD600B-TS
- Critical Notes
- All A-series (027H9xxx) are discontinued. B-series is preferred for replacement. Mechanically interchangeable, pin assignment incompatible; old cable must not be plugged directly.
- B-series: RS485 variant widely used for site retrofit; Ethernet variant for building automation and remote SCADA
- TS variants have special internal seals and firmware tuned for CO₂ transcritical operation; standard ICAD600B cannot substitute directly
- All ICAD actuators run on 24V DC. 24V AC supply is strictly prohibited
Contactor,circuit breaker,sensor,Encoder,PLC,Converter
















NH42-63-318x560.png)



