CJ40-125-380V is a mainstream industrial AC contactor in China, complying with standards GB/T 14048.4 e CEI 60947-4-1. It is widely used for switching control in three-phase motor control and power distribution circuits. Model Explanation CJ: Code for AC Contactor 40: Design series number 125: Rated operational current of main circuit: 125A at 380V under utilization ...

  • Detalhes do produto

CJ40-125-380V is a mainstream industrial Contator CA in China, complying with standards GB/T 14048.4 e CEI 60947-4-1. It is widely used for switching control in three-phase motor control and power distribution circuits.

  1. Explicação do modelo

CJ: Code for AC Contactor

40: Design series number

125: Rated operational current of main circuit: 125A at 380V under utilization category AC-3

380V: Rated control voltage of electromagnetic coil (CA 50 Hz), also suitable for main circuit rated voltage 380V

  1. Principais parâmetros técnicos

2.1 Parâmetros do Circuito Principal

ItemEspecificação
Tensão nominal de isolamento Ui690V (1140V for some brands)
Conventional thermal current Ith125UM
Máx.. potência do motor (AC-3)380V:75kW; 660V:55kW; 1140V:55kW
Number of main poles3-pólo (padrão)
Rated operating frequency (AC-3)1200 operações/hora
Short-circuit protection device (SCPD)Recomendado: RT16-250 fuse

2.2 Bobina & Características operacionais

Rated control voltage: AC 380V/50Hz; options: 220V, 110V, 36V, etc..

Pull-in voltage: (85%~110%) of rated coil voltage Us

Tensão de saída: (20%~75%) of rated coil voltage Us

Coil consumption: Starting 492VA, Holding 61VA/20W

2.3 Auxiliary Contact Parameters (standard for 63A and above)

Corrente térmica convencional: 10UM

Rated control capacity: AC 300VA, DC 60W

Configuração padrão: 4 NÃO + 2 NC; opcional: 3 NÃO + 3 NC, 2 NÃO + 2 NC

Utilization categories: AC-15 (AC control), DC-13 (Controle CC)

  1. Construção & Dimensões de montagem
  2. Características: Direct-operated double-break structure, silver-alloy main contacts, arc-resistant plastic + steel grid arc chute, strong arc extinguishing performance, high durability.
  3. Vida mecânica: 10 milhões de operações; Vida elétrica: 1.2 milhões de operações (AC-3)
  4. Dimensões de montagem (common for CJ40-63~125):

Dimensões gerais: 116milímetros (C) × 143mm (H) × 154mm (D)

Espaçamento dos furos de montagem: Horizontal 100±0.435mm, Vertical 90±0.435mm

Diâmetro do furo de montagem: φ5.8mm

Montagem: Fixação por parafuso, suitable for TH75 mounting rail

  1. Aplicativo & Condições Operacionais

4.1 Principais aplicações

Used in AC 50/60Hz power systems up to 1140V for frequent starting/stopping and remote control of three-phase squirrel-cage induction motors.

Can be combined with thermal relays / motor protectors to form magnetic starters for overload protection.

Also used for switching resistive loads, bancos de capacitores, and other distribution loads.

4.2 Standard Operating Conditions

Temperatura ambiente: -5℃ ~ +40 ℃, average ≤ +35℃ in 24h

Altitude: ≤ 2.000m

Grau de poluição: 3; Categoria de instalação: Ⅲ

Montagem: Inclination ≤ ±5° from vertical; no significant shock or vibration

  1. Seleção & Notas de uso
  2. Controle motor: Sob serviço AC-3, verify contactor current ≥ 1.25 × corrente nominal do motor. For heavy-duty / frequent inching, select one size larger.
  3. Fiação: Use copper cables with adequate current rating; tighten terminals to avoid overheating. Observe coil terminals A1/A2 polarity; do not exceed rated voltage.
  4. Manutenção: Regularly inspect arc chute and contacts for damage. Maintenance only when power is disconnected.
  5. Pedido: Specify model, tensão da bobina, and auxiliary contact configuration. Padrão: 4 NÃO + 2 NC if not specified.

Summary of Cross‑Brand Replacements for CJ40-125-380V

Matching Criteria:

AC-3 at 380V, rated operational current ≥125A, 3-pólo, coil AC380V 50Hz, plus mounting compatibility, contatos auxiliares, and duty compatibility.

Priorities: Direct Drop‑in Replacements → Domestic Equivalents → Imported Equivalents.

Prioridade 1: 100% Direct Drop‑in Replacements

Same CJ40 series from major Chinese brands, montagem idêntica, contatos, características elétricas.

  1. CHNT: CJ40-125 AC380V
  2. DELIXI: CJ40-125 AC380V
  3. TENGEN: CJ40-125 AC380V
  4. Shanghai People Electric: CJ40-125 AC380V
  5. HUANYU, GREATWALL: CJ40-125 AC380V
  6. Tianshui 213: CJ40-125 AC380V

Prioridade 2: Domestic Equivalent Series

MarcaModelo de substituiçãoPrincipais recursos
CHNTNXC-125 AC380VNew economical heavy‑duty, rail/screw mount, expandable aux contacts
CHNTCJ20-125 AC380VClassic national standard, fully compatible with CJ40 duty
CHNTNC1-125 AC380VCompactar, partida frequente, rail mount
DELIXICJX2s-F125 AC380VHigh-current dedicated, excelente extinção de arco
DELIXICDC1-125 AC380VLong mechanical life, high-frequency operation
TENGENCJX4-125 AC380VCompatible with LC1‑D mounting, for imported equipment replacement
Tianshui 213GSC2-125F AC380VServiço Pesado, high shock & resistência à vibração

Prioridade 3: Importado / Joint‑Venture Premium Models

MarcaModelo de substituiçãoPrincipais recursos
SchneiderLC1D125Q7CClassic D series, 125E AC-3, widely used
SchneiderLC1F125Q7CHeavy‑duty F series, long life for continuous operation
ABBA125-30-11 AC380VReliable general‑purpose
ABBAF125-30-11 AC380VWide voltage coil, CA/CC, strong voltage fluctuation resistance
Siemens3RT5055-1AP36SIRIUS premium, for PLC systems
Siemens3RT6055-1AP36Economy version, same ratings
MitsubishiS-N125 AC380VJapanese standard, 120–125A range
LS (LG)GMC-125 AC380VKorean standard, custo-benefício

Core Replacement Rules

  1. No compromise on ratings: Must meet AC-3, ≥125A at 380V, 3-pólo, coil AC380V. Do NOT downsize.
  2. Aux contact matching: Original = 4 NÃO + 2 NC. Use auxiliary contact modules if needed.
  3. Mounting check: Direct replacement for same CJ40 series; verify hole spacing for cross‑series / imported models.
  4. Duty upgrade: For frequent inching, invertendo, heavy loads: use longer‑life models or step up to 160A. For light loads: economical models are acceptable.

 