A classic motor protection series from Schneider Electric, designed for low-power motors rated 0.1-32A. It provides protection against short circuit, overload and phase loss. Equipped with a rotary knob for manual closing and tripping, and built-in thermal-magnetic trip unit to deliver delayed overload protection and instantaneous short-circuit protection. O código 10 represents an adjustable setting current range of 4-6.3A, compatible with 1.5-2.2kW three-phase motors at 400V. Models suffixed with C are domestic versions, while those without C are imported versions. Both share identical performance parameters and comply with IEC and GB standards.
- Explicação do código do modelo
| Segmento | GV2 | PM | 10 | C |
| Significado | Série de produtos: TeSys Deca GV2 disjuntor do motor | Operation type: Panel Mount Rotary Knob with thermal-magnetic protection | Setting current range code: 4-6.3UM | Origin code: Manufactured in China |
- Principais Especificações Técnicas
| Categoria | Dados Técnicos | Observações |
| Informações gerais | ||
| Nome do produto | TeSys Deca GV2PM Motor Circuit Breaker | Specifically designed for motor control and protection |
| Código do pedido | GV2PM10C | Standard commercial model |
| Status do produto | Ativo | Standard product of Schneider Electric |
| Parâmetros Elétricos | ||
| Poloneses | 3P (Trifásico) | For three-phase asynchronous motors |
| Configurando o intervalo atual | 4-6.3UM | Adjustable via rotary knob, for 1.5-2.2kW motors (400V) |
| Corrente Operacional Nominal (É) | 6.3UM | Corrente máxima de operação contínua |
| Tensão nominal de isolamento (interface do usuário) | 690V | Withstand voltage level of insulation system |
| Tensão operacional nominal (Ué) | 400V e (50/60Hz) | Standard industrial voltage |
| Capacidade nominal máxima de interrupção de curto-circuito (UTI) | 100kA @ 400V | Compatível com IEC 60947-2 |
| Tipo de proteção | Termomagnético | Delayed overload protection + proteção instantânea contra curto-circuito |
| Parâmetros Mecânicos | ||
| Dimensões (L×A×P) | 89mm×85mm×91mm | Compact structure to save cabinet space |
| Peso | Aprox.. 280g | Easy for installation and maintenance |
| Montagem | 35mm montagem em trilho DIN | Compatível com EN 60715 |
| Terminais | Terminais de parafuso, for 1.5-4mm² conductors | Suitable for solid and stranded wires |
| Modo de operação | Botão giratório (OFF-ON-RESET) | Manual reset required after tripping |
| Parâmetros Ambientais | ||
| Temperatura operacional | -20°C ~ +60°C | Adaptable to industrial environments |
| Proteção de entrada | IP20 | Prevents finger access to live parts |
| Certificações | CE, CCC, UL, CSA | Em conformidade com os padrões internacionais de segurança |
- Full Range of GV2PM Rotary Knob Motor Circuit Breakers
| Modelo | Configurando o intervalo atual | Potência do motor correspondente (400V) | Observações |
| GV2PM01C | 0.1-0.16UM | 0.025-0.04kW | Minimum current rating |
| GV2PM02C | 0.16-0.25UM | 0.04-0.06kW | |
| GV2PM03C | 0.25-0.4UM | 0.06-0.1kW | |
| GV2PM04C | 0.4-0.63UM | 0.1-0.16kW | |
| GV2PM05C | 0.63-1UM | 0.16-0.25kW | |
| GV2PM06C | 1-1.6UM | 0.25-0.4kW | |
| GV2PM07C | 1.6-2.5UM | 0.4-0.63kW | |
| GV2PM08C | 2.5-4UM | 0.63-1.1kW | |
| GV2PM10C | 4-6.3UM | 1.1-2.2kW | Current model |
| GV2PM14C | 6.3-10UM | 2.2-3kW | |
| GV2PM16C | 9-14UM | 3-4kW | |
| GV2PM20C | 13-18UM | 4-5.5kW | |
| GV2PM21C | 17-23UM | 5.5-7.5kW | |
| GV2PM22C | 23-32UM | 7.5-11kW | Maximum current rating |
- Concorrente & Modelos Equivalentes
| Marca | Modelo | Configurando o intervalo atual | Modo de operação | Descrição da substituição |
| Schneider Elétrica | GV2ME10C | 4-6.3UM | Push-button | Alternative with different operation mode within the same series |
| Siemens | 3RV2011-0JA10 | 4-6.3UM | Botão giratório | Cross-brand functional replacement |
| ABB | MS116-6.3 | 4-6.3UM | Botão giratório | Cross-brand functional replacement |
| Eaton | DIL M9-10 | 4-6.3UM | Botão giratório | Cross-brand functional replacement |
| Chint | NDM1-63/3300 | 4-6.3UM | Botão giratório | Economical domestic alternative |
- Ambientes de aplicativos & Casos Típicos
5.1 Aplicativos recomendados
Automação Industrial: Protection for small pumps, fans and conveyor motors; compatible with PLC control circuits
Building Facilities: Control and protection for air conditioning fans, bombas de água, elevator door motors and fire linkage equipment
Comida & Indústria de Bebidas: Motor protection for packaging machines, filling machines and small mixers; meets hygiene requirements
Equipamento Médico: Safety protection for laboratory stirrers, centrifuges and small medical pumps
Agricultural Machinery: Protection for outdoor motors such as irrigation pumps, small harvesters and feed mixers
Centros de dados: Protection for precision air conditioner fans, cooling water pumps and UPS cooling fans
5.2 Non-recommended Applications
Partida frequente: Not applicable for equipment starting more than 10 vezes por hora. GV3 series or soft starters are recommended instead.
Heavy-duty start: Not suitable for motors with starting current over 8 vezes a corrente nominal. Additional overload protection is required.
Explosive hazardous areas: No explosion-proof certification. Do not use directly in Zone IIC explosive areas.
DC motors: The GV2 series is designed exclusively for AC motors. Use dedicated protective devices for DC motors.
5.3 Casos de aplicação típicos
Caso 1: Mixing System in Pharmaceutical Factory
Aplicativo: Sobrecarga, short-circuit and phase loss protection for 1.5kW reactor stirring motors
Configuração: GV2PM10C + LC1D12 Contactor + Control Buttons
Benefícios: Prevents motor burnout caused by agitator jamming; complies with GMP standards and trips rapidly for equipment protection during faults.
Caso 2: Air Conditioning System in Commercial Buildings
Aplicativo: Protection and control for 2.2kW fresh air handling units and water pump motors
Configuração: GV2PM10C + Building Automation System (BASE) + Temperature Sensors
Benefícios: Enables automatic start/stop of fans and pumps, protects motors against overload, reduces maintenance costs and improves energy efficiency by 12%.
Caso 3: Conveyors on Automated Production Lines
Aplicativo: Protection and control for 1.1kW small conveyor motors
Configuração: GV2PM10C + CLP + Emergency Stop Buttons
Benefícios: Avoids motor damage from conveyor jamming, works with emergency stop system for safe shutdown, and shortens Mean Time To Repair (MTTR) to within 3 minutos.
Caso 4: Aeration System in Wastewater Treatment Plant
Aplicativo: Protection and control for 2.2kW small aeration fans
Configuração: GV2PM10C + Liquid Level Sensors + Automatic Control Cabinet
Benefícios: Performs reliably in humid environments, prevents fan burnout from overload, realizes unattended automatic operation and cuts operational costs by 30%.
- Dicas de seleção & Regras de referência rápida
Selection Rhythm
Choose GV2PM10C,
Intervalo atual 4 to 6.3A,
Matches motors 1.5 to 2.2kW,
Operação do botão rotativo, IP20 rating,
35mm trilho DIN, 89mm largura,
High breaking capacity with thermal-magnetic protection,
Safeguards motors from overload and short circuit,
Reliable for industrial and building applications.
Regras de referência rápida
- Correspondência atual: 10 = 4-6.3A; 08 = 2.5-4A; 14 = 6.3-10A. Larger figure means wider current range.
- Modo de operação: PM = Rotary knob; ME = Push-button; LP = Magnetic-only type (short-circuit protection only).
- Combinação de poder: 4-6.3A corresponds to 1.5-2.2kW @ 400V. Approximate formula: Current × 0.5 ≈ Matched motor power (kW).
- Installation Features: 89mm largura, 35mm montagem em trilho DIN, Classificação de proteção IP20, ideal for installation inside control cabinets.
- Solução de problemas
| Fenômeno de falha | Possíveis causas | Soluções |
| Tropeços frequentes | Setting current too low | Turn the rotary knob clockwise to increase current within 4-6.3A |
| Sobrecarga do motor / locked rotor | Check for overloading and eliminate jamming | |
| Phase loss operation | Inspect three-phase power supply and repair broken wires or poor contacts | |
| Falha ao fechar | Knob not reset | Turn the knob to OFF position then back to ON after tripping |
| Bloqueio mecânico | Clear foreign objects or replace damaged components | |
| Fiação errada | Recheck three-phase wiring and eliminate short circuits | |
| Overheated contacts | Terminais de fiação soltos | Retighten terminals for good contact |
| Carga excessiva | Reduce load or replace with higher-rated circuit breaker if needed | |
| Temperatura ambiente excessivamente alta | Improve ventilation and keep temperature below 60°C |
- Key Features Summary
- Proteção Abrangente: Thermal-magnetic trip unit provides delayed overload, instantaneous short-circuit and phase loss protection, compatível com IEC 60947-4-1.
- Wide Compatibility: 4-6.3A adjustable current range for 1.5-2.2kW three-phase motors; easy operation via rotary knob.
- Estrutura Compacta: Dimension 89mm×85mm×91mm with 35mm DIN rail mounting to save cabinet space.
- Alta confiabilidade: Ampla faixa de temperatura operacional (-20°C ~ +60°C) and IP20 rating for harsh industrial conditions.
- Fácil instalação & Manutenção: Standard interface for seamless matching with contactors; simple knob reset after faults.
Application Scenarios of Schneider GV2PM10C (4~6,3A)
This is a 3-pole rotary-knob motor circuit breaker with thermal-magnetic protection. It is suitable for 1.1~2.2kW three-phase asynchronous motors at 400V. Adopting DIN rail mounting, it integrates overload, short-circuit and phase loss protection, and is widely used in industrial, prédio, light industry and municipal fields.
- Main Application Scenarios
1.1 Industrial Automated Production Lines
Small belt conveyors and roller motors
Workshop auxiliary fans and dust extraction fans
Auxiliary power motors for manipulators and small positioners
Machine tool cooling pumps and lubrication pumps
Combined with PLC and relay circuits for local and remote control & proteção
1.2 AVAC & Building Electromechanical Systems
Terminal fans, fresh air fans and exhaust fans of central air conditioning
Small circulating water pumps and make-up water pumps for building water supply & drenagem
Cooling fans for computer room precision air conditioners
Auxiliary fans and door drive motors in elevator rooms
Fire exhaust fans and damper linkage motors (meeting fire power distribution standards)
1.3 Indústria Leve, Comida & Indústria de embalagens
Small mixers, blenders and feeding machines
Máquinas de embalagem, labelers and conveyor drive motors
Filling equipment and small roller conveyors
Ventilation fans and washing pumps for food workshops
(Compact body and qualified protection level, suitable for dusty and humid workshop conditions)
1.4 Tratamento de Água & Municipal Engineering
Small aeration fans, dosing pumps and reflux pumps in sewage treatment plants
Booster pumps for landscape pools and residential water supply
Small power motors inside on-site control boxes of pumping stations
Fans and water pumps supporting river and pipeline monitoring equipment
1.5 Laboratory & Medical Supporting Equipment
Laboratory stirrers, centrifuges and circulating water pumps
Exhaust and fresh air system motors for medical clean rooms
Medical water purifiers and small delivery pumps
(Sensitive protection effectively prevents equipment stalling and motor burnout)
1.6 Armazenagem, Logística & Supermarkets
Warehouse ventilation fans and dust removal equipment
Condenser fans and fresh air systems for supermarket refrigeration units
Motors for light sorting lines and small roller conveyors
1.7 Agricultural Machinery & Outdoor Light-duty Equipment
Small irrigation pumps and spray devices for farmland
Feed mixers and small agricultural ventilation equipment
(Wide temperature adaptability for outdoor simple electrical control boxes)
- Cenários não recomendados
- High-frequency starting equipment: Mais do que 10 starts per hour may cause false tripping. Dedicated starting solutions are recommended.
- Heavy-load motors with high starting current: Starting current far exceeds normal level; match with thermal relays and contactors additionally.
- Explosive hazardous areas: Without explosion-proof certification, not allowed for direct use in explosive zones.
- DC motors and high-power single-phase motors: Designed for three-phase AC motors only.
- Environments with long-term temperature above +60°C or strong corrosive gas: Protection accuracy and service life will be reduced.
- Common Matching Solutions for On-site Use
- Standard motor circuit: GV2PM10C + LC1D Contactor + Botões de pressão (Local start & parar)
- Automatic control circuit: GV2PM10C + Contator + CLP (Remote automatic control)
- Fire linkage circuit: GV2PM10C + Fire Module + Contator (Fire forced start / forced trip)
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares


















NH42-63-318x560.png)




