Nom et prénom: Frequency/Voltage/Current (10 kHz Version)
KFU8 series DIN rail signal conditioning module, designed for frequency/speed acquisition from encoders and pulse capteurs, converting pulse signals into standard analog signals, with an optional frequency-divided pulse output.
Distinction:
KFU8-FSSP-1.D-Y = 10 kHz maximum input frequency
KFU8-FSSP-1.D-Y322444 = 40 kHz high-speed version
Many suppliers mix these two models; confirm the frequency limit during selection.
✅ Fonctions principales
- Two measurement modes: Fréquence (Hz) / Vitesse de rotation (tr/min)
Gamme de fréquence: 0.001 Hz ~ 9999 Hz
Speed range: 0.02 rpm ~ 9999 tr/min
- Configurable analog output (selectable via menu):
0…10 V / 2…10 V
0…20 mA / 4…20 mA
- Frequency-divided pulse output: division ratio 1~9999, isolated pulse signal for PLC or secondary instruments
- Intégré 24 V DC auxiliary sensor power supply; compatible with 2/3/4-wire proximity switches and NPN/PNP incremental encoders
- 4-digit red LED display; shows input Hz/rpm or output V/mA. 4-button local programming with one-touch Teach-In calibration
- Period measurement method, optimized for low-speed pulse signals
📌 Electrical Specifications
Alimentation: 24 À DC
Consommation d'énergie: <5 W
Max input frequency: 10 kHz (ce modèle); minimum pulse width ≥40 μs
Précision: ≤0.2% FS
Processing response: 5 ms internal update; display refresh adjustable from 0.01~2.5 s (no impact on signal conversion)
Isolement: Galvanic isolation between input and analog output
Classe de protection: IP20 (montage en armoire uniquement)
Montage: Snap-on 35 mm rail DIN
Terminaux: Removable coded terminals, wire cross-section 0.2~2.5 mm²
Température de fonctionnement: -25 ℃ ~ +40 ℃ (sans condensation)
Température de stockage: -40 ℃~+85 ℃
📋 Terminal Assignment
| Terminal | Signal |
| 1 | Sensor GND |
| 2 | Sortie d'impulsion |
| 5 | Sortie analogique + |
| 6 | Sortie analogique – (Tension) |
| 4 | Sortie analogique – (Actuel) |
| 7 | Capteur 24 V+ |
| 11 | Power Supply L+ 24 À DC |
| 12 | Power Supply L- 0 V |
| 14 | NPN/PNP Input – (Cathode) |
| 15 | NPN/PNP Input + (Anode) |
| 13 | Sensor GND |
| Remaining terminals | Caroline du Nord (Not Connected) |
⚙️ Factory Default Parameters
Mode: tr/min (Vitesse de rotation)
Pulse per revolution (PPR): 1
Full Scale Range: 9999
Sortie analogique: 0…10 V
Display Refresh Time: 0.33 s
Division Ratio: 1
Enregistrer les paramètres: Long-press Enter + + to store into EEPROM (power-down retention)
🛠 Typical Applications
Speed measurement for conveyors, les fans, pumps and roller tables
Converting pulse signals from flowmeters into 4–20 mA analog signals for DCS/PLC
Encoder signal division, local speed display + analog transmission
Stable measurement of low-frequency pulse signals (period measurement outperforms frequency counting at low speeds)
⚠️ Guide de dépannage
| Faute | Causes possibles & Remèdes |
| Pas de puissance, pas d'affichage | 1. Vérifier 24 V DC at terminals 11/12; 2. Bornes lâches; 3. Reverse polarity protection activated |
| Signal present but reading always zero | 1. NPN/PNP wiring reversed; 2. Pulse width ≥40 μs; 3. Non 24 V on sensor supply terminal 7; 4. Wrong measurement mode (rpm/Hz) |
| Des lectures fluctuantes | 1. Increase display refresh time; 2. Use shielded cable with single-end grounding; 3. Check voltage drop on encoder supply; 4. Ensure high level ≥16 V DC, low level ≤6 V DC |
| Analog output stuck | 1. Match current/voltage output type with AI card; 2. Max load resistance ≤600 Ω for current output; 3. Re-run Teach-In calibration |
| Display overflow | 1. Actual speed exceeds set RANGE; 2. Incorrect PPR setting (value too large) |
| No pulse output on terminal 2 | 1. Division ratio ≠ 1; 2. Open-collector output requires external pull-up resistor on PLC side; 3. Input frequency below lower limit |
| Self-test error Err on power-up | EEPROM checksum failure; power cycle first; repeated error means hardware failure, replace the module |
| Poor low-speed accuracy | This module uses period measurement; ensure pulse width ≥40 μs; avoid ultra-narrow pulses |
📎 Cross-model & Options de remplacement
Même série: KFU8-FSSP-1.D-Y322444 (40 kHz, for high-speed encoders)

Alternatives nationales: CZJ, UBE frequency/speed isolators (must support period measurement + frequency-divided pulse output)
- Instructions de câblage (KFU8-FSSP-1.D-Y)
Full Terminal List
| Terminal | Définition du signal | Note |
| 1 | Sensor GND | Spare sensor ground |
| 2 | Frequency-divided Pulse Output | Isolated pulse for PLC high-speed counter |
| 4 | Current Output I- | Negative terminal for 4…20 mA |
| 5 | Analog U+/I+ | Common positive for voltage & current output |
| 6 | Voltage Output U- | Negative terminal for 0…10 V |
| 7 | Capteur 24 V+ | Encoder/proximity sensor supply, maximum. 30 mA |
| 8 | Entrée NAMUR – | NAMUR sensor channel |
| 9 | Entrée NAMUR + | NAMUR sensor channel |
| 11 | Module Power L+ 24 À DC | Main power positive |
| 12 | Module Power L- 0 V | Main power negative |
| 13 | Sensor GND | Sensor power ground |
| 14 | NPN/PNP Input – (Cathode) | Pulse negative |
| 15 | NPN/PNP Input + (Anode) | Pulse positive |
| Autres | Caroline du Nord | Do not connect |
Standard Wiring Schemes
- 3-wire PNP Encoder (Le plus courant)
Brown wire → Terminal 7 (24 V+)
Blue wire → Terminal 13 (GND)
Black signal wire → Terminal 15; Terminal 14 shorted to 13 (GND)
- 3-wire NPN Encoder
Marron → 7; Bleu → 13
Black signal → 14; Terminal 15 shorted to 7 (24 V+)
- 4–20 mA analog to DCS AI card
Terminal 5 → AI+; Terminal 4 → AI-
- 0…10 V voltage output
Terminal 5 → AI+; Terminal 6 → AI-
- Frequency-divided pulse output
Terminal 2 to PLC high-speed counter; fit external pull-up resistor on PLC side
Avis important: Max sensor supply current = 30 mA; do not drive multiple encoders. Use shielded cable for long-distance pulse wiring, ground the shield only at one end.
- Button Operation & Parameter Setup
4 front-panel keys: Mode (Menu), ◀, +, Entrer
- Allumer; wait for self-test then enter measurement display (Hz/rpm)
- Short press Mode to switch menu items; ◀ = shift digit; + = change value
- Enregistrer les paramètres: Long press Enter + + together to write into EEPROM (conservé après une coupure de courant)
- Exit menu: Long press Mode to return to measurement screen
Menu Items (English Original)
- MODE: Measurement Mode
rpm = Rotational Speed (Encoder application recommended)
Hz = Frequency (Pulse flowmeter)
- PULSE: Pulses Per Revolution (PPR)
Exemple: 1000-line encoder → set PULSE=1000
- RANGE: Full Scale Value
Exemple: 0~1500 rpm → set RANGE=1500
- DEHORS: Type de sortie
0-10V / 2-10V / 0-20mA / 4-20mA
- DIV: Division Ratio (1~9999)
Output pulse = Input pulse ÷ DIV; set DIV=1 if no division required
- DISP: Display Refresh Time (0.01~2.5 s)
Increase to 0.5~1 s to stabilize low-speed readings; ensemble 0.1 s for high speed
- TEACH: One-touch Calibration (Teach-In)
Run equipment to full-scale speed, enter TEACH and press Enter; auto-set upper range (zero point fixed at 0)
Valeur par défaut d'usine: MODE=rpm, PULSE=1, RANGE=9999, OUT=0…10V, DIV=1, DISP=0.33 s
Factory Reset Procedure
Allumer, hold Mode + Enter for 5 seconds until FACT appears; confirm to restore all factory settings. All custom parameters will be erased.
- Fault Troubleshooting Table
| Symptôme | Étapes de dépannage |
| No display after power-up | 1. Mesure 24 V DC between terminals 11 & 12; 2. Check loose terminals; 3. Reverse polarity protection triggered |
| No reading, display stays zero | 1. Verify NPN/PNP wiring polarity; 2. Ensure pulse width ≥40 μs; 3. Vérifier 24 V output on terminal 7; 4. Confirm correct MODE (rpm/Hz) |
| Instable, flickering readings | 1. Increase DISP refresh time; 2. Shield cable single-end grounded; 3. Check voltage drop on encoder supply; 4. High level ≥16 V DC, low level ≤6 V DC |
| Analog output locked and unchanged | 1. Match OUT type with AI card (current/voltage cannot be mixed); 2. Current output load resistance ≤600 Ω; 3. Re-run TEACH calibration |
| Display over-range overflow | 1. Actual speed exceeds RANGE setting; 2. PPR value set too high |
| No pulse output on terminal 2 | 1. DIV ratio not equal to 1; 2. Open-collector output requires external power/pull-up resistor on PLC; 3. Input frequency below lower limit |
| Err code on power-up self-test | EEPROM data error; restart first; repeated error = hardware damage, remplacer le module |
| Inaccurate low-speed measurement | This module uses period measurement (good for low speed); ensure pulse width ≥40 μs, avoid ultra-narrow pulses |
- Parameter Table (Chinese ↔ English, Exportable)
| Chinese Parameter | English Tag | Gamme | Remarques |
| 测量模式 | MODE | tr/min / Hz | Vitesse / Fréquence |
| 每转脉冲数 | PULSE | 1~9999 | Encoder PPR value |
| 满量程 | RANGE | 1~9999 | Corresponds to full-scale analog output |
| 输出类型 | DEHORS | 0-10V,2-10V,0-20mA,4-20mA | Analog signal selection |
| 分频系数 | DIV | 1~9999 | Pulse output division |
| 显示刷新时间 | DISP | 0.01~2.5 s | Only affects display, no impact on conversion speed |
| 一键标定 | TEACH | — | Dynamic full-scale calibration |
| 精度 | Précision | ≤0.2%FS | Full-scale accuracy |
| 最大输入频率 | Fmax | 10 kHz | For model Y only (not Y322444) |
- Procédure de mise en service (On-site Sequence)
- Wire with power disconnected; double-check power, encoder and analog terminals
- Allumer; verify 24 V DC on sensor supply terminal 7
- Set MODE, PPR, RANGE and OUT type
- Rotate the encoder and confirm reading follows actual speed
- Measure analog output with multimeter, verify zero and full-scale values
- If pulse division is needed: connect PLC high-speed counter and test terminal 2 pulse signal
- Save parameters and record settings; commissioning complete
Pepperl+Fuchs KFU8 Series DIN Rail Signal Converter Order List
Description: KFU8 = K-System local-display programmable signal conditioners; divided into standard type and Ex intrinsically safe barrier type.
Suffix rules:
1.D = 1-channel; 2.D = 2-channel
Y = 10 kHz input; Y322444 = 40 kHz (only for FSSP models)
Ex = Intrinsically safe for hazardous area Zone 0/1/2
| Order Part Number | Nom du produit | Brief Function | Explosion Proof |
| KFU8-FSSP-1.D-Y | Frequency/Speed Converter (10 kHz) | Encoder pulse → analog 0-10V/4-20mA, with frequency-divided pulse output & affichage local | Non |
| KFU8-FSSP-1.D-Y322444 | Frequency/Speed Converter (40 kHz) | Same as FSSP, maximum 40 kHz for high-speed encoders | Non |
| KFU8-DW-1.D | Speed Monitor | Overspeed/underspeed monitoring with relay alarm output; maximum 40 kHz, period measurement | Non |
| KFU8-UFC-1.D | Frequency Converter with Limit Alarms | 1 mHz~10 kHz; NAMUR/dry contact input; 4-20mA + relais + sortie transistorisée; SIL2 | Non |
| KFU8-UFC-1.D.FA | Convertisseur de fréquence (Ancienne version) | Modèle hérité; phase-out, replace with UFC-1.D | Non |
| KFU8-UFC-Ex1.D | Intrinsically Safe Frequency Barrier | A partir de maintenant, Zone 0/1/2, NAMUR input, SIL2 | Oui (A partir de maintenant) |
| KFU8-UFT-2.D | Dual-channel Frequency/Slip/Speed Direction Monitor | Dual NAMUR/dry contact input; detect rotation direction, slip and synchronous deviation; analogique + sortie relais | Non |
| KFU8-UFT-Ex2.D | Barrière directionnelle/glissante à double canal antidéflagrante | Surveillance de rotation à double canal pour zones dangereuses | Oui (A partir de maintenant) |
| KFU8-USC-1.D | Convertisseur de signal universel tension/courant | Isolement & mise à l'échelle pour 0/4-20mA & 0-10V signaux analogiques; avec alarme relais limite | Non |
| KFU8-GUT-Ex1.D | Transmetteur de température universel à sécurité intrinsèque | Entrée RTD/Thermocouple, alarme à double relais, SIL2 | Oui (A partir de maintenant) |
Règle de codage du modèle
KFU8 [Code de fonction] [Canal].[Version] [-Suffixe]
FSSP: Fréquence Vitesse → Transmission de vitesse avec sortie d'impulsion divisée
DW: Surveillance de vitesse → Surveillance de la vitesse & alarme
UFC: Convertisseur de fréquence universel → Conversion de fréquence + alarme de limite
UFT: Fréquence universelle Twin → Fréquence double canal, direction & surveillance des glissades
USC: Convertisseur de signal universel → Isolation du signal analogique standard
INTESTIN: Température universelle → Transmission du signal de température
Ex: Barrière antidéflagrante à sécurité intrinsèque
1.D = canal unique; 2.D = Double canal
Y = 10 kHz; Y322444 = 40 kHz (Suffixe exclusif FSSP)
Accessoires communs série KFU8
K-CJC-EX: Cold-junction compensation terminal (for GUT temperature modules)
KF-ST-5BU / KF-ST-5GN: Removable coded terminals (blue/grey)
Power Rail: K-series power bus for multi-module parallel power supply
Guide de sélection rapide
- Speed transmission + divided pulse output → FSSP (Oui / Y322444)
- Overspeed/underspeed alarm (no divided pulse) → DW-1.D
- NAMUR proximity switch frequency input + alarm → UFC / UFC-Ex
- Dual encoders, slip & rotation direction detection → UFT-2.D / UFT-Ex2.D
- Analog 4-20mA/0-10V isolation, mise à l'échelle & alarm → USC-1.D
- RTD/TC temperature measurement in hazardous area → GUT-Ex1.D
Notes complémentaires
All KFU8 modules: 40 mm largeur, 35 Montage sur rail DIN mm, 4-affichage des chiffres + 4-button programming; different from non-display KFD0 / KFA5 barriers.
Alimentation: Most models support 20~90 V DC / 48~253 V AC; FSSP model only supports 24 À DC.
End-of-life notice: UFC-1.D.FA is obsolete; select UFC-1.D for new projects.