Order No.: 2903154
Phoenix Contact TRIO POWER 2nd-generation three-phase DIN rail switching power supply with Push-in spring terminals. Designed for powering PLCs, sensors and actuators inside electrical control cabinets. Widely used in machine manufacturing, automated production lines, HVAC and hoisting equipment.
The code 2901354 often appears in industry documents as shorthand; the complete official part number is 2903154.
✅ Model Definition
TRIO: TRIO POWER series industrial power supply
PS: Power Supply
2G: 2nd Generation
3AC: 3-phase AC input
24DC: 24V DC output
10: Rated output current 10A
📌 Key Technical Specifications
Input
Rated: 3×400~500V AC; capable of emergency operation with 2×400~500V AC two-phase supply
Operating range: 3×320~575V AC
Frequency: 50/60Hz
Input current: 3×0.6A @400VAC
Output
Rated: 24V DC /10A (240W)
Adjustable output: 24~28V DC
Dynamic Boost: 15A for 5 seconds (to handle inrush loads of motors and capacitors)
Ripple & noise: ≤50mVpp
OVP overvoltage protection: Output clamped ≤30V DC
Mechanical & Environmental
Mounting: DIN 35mm rail
Dimensions (W × H × D): 42 ×130 ×160 mm
Wiring: Push-in screwless spring terminals
Operating temperature: -25℃ ~ +70℃; derating 2.5%/K above 60℃
Efficiency: >92%
Parallel operation: Supports parallel connection for capacity expansion and redundancy; series connection for voltage boosting
Protections: Overcurrent, short-circuit, overtemperature, output overvoltage
Signal: Relay alarm contact (DC-OK signal)
📋 Certifications & Applications
Standards: EN61010, UL, CE, PELV protective extra-low voltage
Typical applications: Automated production lines, packaging machinery, conveyor systems, 24V power supply for control cabinets feeding PLC, DI/DO modules, sensors and solenoid valves
High MTBF, suitable for 24/7 continuous industrial operation
⚠️ Selection & Replacement Notes
- Model distinction: 2903154 is 3-phase 3AC; single-phase 1AC version is 2903149, do not mix them up
- Domestic alternative: Mean Well SDR-240-24, Delta DRP-240-24 (note: no dynamic boost capability for inrush current)
- Redundancy solution: When paralleling two 2903154 units, use redundancy module such as QUINT-DIODE
- Installation: Maintain ≥50mm vertical clearance at top and bottom for heat dissipation; units can be mounted side-by-side with zero horizontal clearance
🛠️ Troubleshooting Guide
POWER LED off: Check 3-phase L1/L2/L3 mains supply; loss of any phase may prevent startup; verify PE earth connection
Output voltage drop / insufficient load capacity: Prioritize checking loose terminals, low input voltage and high-temperature derating
OK contact open: Output overcurrent / short circuit or internal overtemperature protection. Disconnect load and retest
Tripping on power-up due to inrush: Utilize boost feature and evaluate switching surge current
📦 HS Code for Export
8504401400 (Static converters, industrial switching power supply, for customs reference only, subject to local customs determination)
TRIO-PS-2G/3AC/24DC/10 (Order No. 2903154)
Efficiency: >92%
Test condition: 400V AC input, full rated load
Additional Power Consumption Parameters
No-load power consumption: <1.1 W
Power loss at rated load: <22 W
Note: This value is the nominal figure from Phoenix Contact official datasheet. Actual efficiency under light load (20%~50% load) will be slightly lower than the 92% full-load rating.
TRIO-PS-2G/3AC/24DC/10 (Order No. 2903154)
Overall dimensions (W × H × D): 42 mm × 130 mm × 160 mm
📌 Installation Clearance (Critical for cabinet layout)
Horizontal sides: Zero gap side-by-side mounting allowed at ambient ≤40℃; reserve 10mm side clearance when temperature approaches 70℃
Vertical: ≥50mm clearance at top and bottom (mandatory)
Mounting rail: Standard NS35 DIN rail (EN60715)
Weight
Approx. 1.1kg
Phoenix Contact TRIO-PS-2G Series Full Model List (TRIO POWER 2nd Generation, Push-in terminals)
Series common features: DIN35 rail mounting, dynamic Boost (1.5×rated current for 5s), DC-OK relay alarm, parallel redundancy support, -25~+70℃, derating 2.5%/K above 60℃
1-phase Input 1AC (100~240VAC)|24VDC Output
| Model | Order No. | Output Rating | Dimension W×H×D(mm) |
| TRIO-PS-2G/1AC/24DC/3/C2LPS | 2903147 | 24V 3A /72W | 30 ×130 ×115 |
| TRIO-PS-2G/1AC/24DC/5 | 2903148 | 24V 5A /120W | 36 ×130 ×115 |
| TRIO-PS-2G/1AC/24DC/10 | 2903149 | 24V 10A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/1AC/24DC/20 | 2903151 | 24V 20A /480W | 65 ×130 ×160 |
3-phase Input 3AC (3×320~575VAC, rated at 3×400VAC)|24VDC Output (Your target model group)
| Model | Order No. | Output Rating | Dimension W×H×D(mm) |
| TRIO-PS-2G/3AC/24DC/5 | 2903153 | 24V 5A /120W | 36 ×130 ×115 |
| TRIO-PS-2G/3AC/24DC/10 | 2903154 | 24V 10A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/3AC/24DC/20 | 2903155 | 24V 20A /480W | 65 ×130 ×160 |
| TRIO-PS-2G/3AC/24DC/40 | 2903156 | 24V 40A /960W | 120 ×130 ×160 |
1-phase Input 1AC|48VDC Output
| Model | Order No. | Output Rating | Dimension W×H×D(mm) |
| TRIO-PS-2G/1AC/48DC/5 | 2903159 | 48V 5A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/1AC/48DC/10 | 2903160 | 48V 10A /480W | 65 ×130 ×160 |
- Common Matching Accessories (For cabinet integration)
- QUINT-DIODE/12-24DC/20 Redundancy diode module for dual power supply redundancy
- CBM E4 24DC/0.5-10A NO-R 4-channel 24V electronic circuit breaker (2905743)
- CBM E8 24DC/0.5-10A NO-R 8-channel electronic circuit breaker (2905744)
✅ Key Selection Guidelines
- Suffix C2LPS: Only available for the 3A single-phase variant with SIL capability; not required for standard automation projects
- 3AC three-phase models can run on two phases (L1/L2 only)
- Width reference: 3A=30mm; 5A=36mm; 10A=42mm; 20A=65mm; 40A=120mm, cabinet layout mainly depends on width
Phoenix Contact TRIO-PS-2G Series Certification List (Including TRIO-PS-2G/3AC/24DC/10, Order No.2903154)
All models in this series share the same certification package. Only the C2LPS suffix model has extra SIL0 capability; standard models are SIL=0
✅ Global Certifications
- CE (EU)
Low Voltage Directive LVD 2014/35/EU
EMC Directive 2014/30/EU
- UL / cULus (UL Listed)
UL508 (Industrial control equipment)
UL60950-1 (Information technology safety)
ANSI/ISA-12.12.01, Class I Division II Groups A/B/C/D (suitable for North American hazardous areas)
- IECEE CB Certificate (CB scheme, foundation for multi-country certification conversion)
- EAC Customs Union Certification (Russia, Belarus, Kazakhstan and other EAEU markets)
- DNV GL Marine Certificate (Suitable for ship and offshore control cabinets)
- BIS (BIS license for India market)
✅ Environmental Compliance
RoHS (EU)
REACH
WEEE compliant with waste electrical and electronic equipment directive
✅ Safety & Functional Standards (Standards ≠ Certificates; product compliance specifications)
IEC 60950-1: SELV Safety Extra-Low Voltage
EN 50178: PELV Protective Extra-Low Voltage
EN 60204-1: Safety of machinery electrical equipment (widely used for machinery)
EN 50121-4: Railway EMC standard
IEC 61508: SIL 0 (Standard models of this series; TRIO-PS-2G/1AC/24DC/3/C2LPS is specifically marked SIL0 functional safety)
Housing flammability: UL94 V0
✅ EMC Electromagnetic Compatibility Standards
EN 61000-6-1 / 6-2: Immunity (residential / industrial environments)
EN 61000-6-3 / 6-4: Radiated & conducted emissions
EN 61000-3-2: Harmonic current limits
📌 Selection Remarks
- Domestic projects: No CCC certificate, not within mandatory 3C scope. CE for EU export, UL for North America, EAC for Russia/Central Asia, DNV for marine projects.
- SIL level: Standard TRIO-PS-2G cannot be used for SIL1 and above safety loops. If SIL higher level is required, select QUINT series SIL-rated power supplies.
Contactor,circuit breaker,sensor,Encoder,PLC,Converter
















NH42-63-318x560.png)