Disjuntor do motor Schneider GV2P32

The GV2P32 is a 3-pole thermal-magnetic motor circuit breaker (MPCB) da série Schneider TeSys GV2. Possui uma configuração de corrente ajustável de 24-32A, compatible with 15kW @ 400V three-phase motors. Providing dual protection against overload and short circuit, with IP20 protection degree, it is widely applied in industrial motor control circuits. Model Code Explanation Code ...

  • Detalhes do produto

The GV2P32 is a 3-pole thermal-magnetic motor circuit breaker (MPCB) da série Schneider TeSys GV2. Possui uma configuração de corrente ajustável de 24-32A, compatible with 15kW @ 400V three-phase motors. Providing dual protection against overload and short circuit, with IP20 protection degree, it is widely applied in industrial motor control circuits.

  1. Explicação do código do modelo
Segmento de códigoSignificadoDescrição
GV2Série de produtosTeSys GV2 series motor circuit breakers for motor overload and short-circuit protection
PTipo de operaçãoRotary knob manual control, imported version (equivalente nacional: GV2PM series)
32Classificação atualAdjustable setting range: 24-32UM, for motor circuits with rated current up to 32A

Definição completa do modelo: GV2P32 = Schneider GV2 series, tipo de botão rotativo, 32A rated motor circuit breaker

  1. Especificações Técnicas Principais
CategoriaEspecificaçõesObservações
General Characteristics
Tipo de produto3-pole thermal-magnetic motor circuit breaker (MPCB)Compatível com IEC 60947-4-1
Faixa de corrente ajustável24-32UM (ajustável)Thermal trip with ambient temperature compensation
Poloneses3P (Trifásico)Designed for three-phase motor protection
Modo de operaçãoRotary knob manual controlWith ON/OFF indicator and lockable function
Parâmetros Elétricos
Tensão operacional nominal230-690V e, 50/60HzSuitable for global industrial power grids
Potência do motor compatível15kW @ 400/415V, 50/60HzMaximum applicable power under standard operating conditions
Magnetic Trip Threshold12×In = 384A (Instant short-circuit protection)Fast disconnection upon short-circuit faults
Capacidade de interrupção de curto-circuito10kA @ 400 V, 50HzMeets industrial standard requirements
Tipo de terminalTerminais de parafusoApplicable copper wire cross-section: 1.5-25mm²
Físico & Parâmetros Ambientais
Grau de ProteçãoIP20Impede o acesso dos dedos às peças energizadas
Tipo de montagemTrilho DIN padrão de 35 mmModular installation, economia de espaço
Dimensões (L×A×P)45×85×95mmCompact design for distribution cabinets
Temperatura operacional-25℃ ~ +60 ℃Ampla faixa de temperatura para ambientes industriais
CertificaçõesCCC, UL, CSA, EAC, Marine Classification (DNV, GL, BV), ATEXMultiple certifications for global application
Informações sobre pedidos
Manufacturer Part No.GV2P32Official Schneider model
Standard Order CodeGV2P32Original imported version
  1. Full GV2P Series Model List
ModeloFaixa de corrente ajustávelPotência do motor compatível (400V)Corrente de Disparo Magnético
GV2P010.16-0.25UM0.06kW3.0UM
GV2P020.25-0.4UM0.12kW4.8UM
GV2P030.4-0.63UM0.25kW7.6UM
GV2P040.63-1UM0.37kW12UM
GV2P051-1.6UM0.75kW19UM
GV2P061.6-2.5UM1.1kW30UM
GV2P072.5-4UM1.5kW48UM
GV2P084-6.3UM3kW76UM
GV2P096.3-10UM4kW120UM
GV2P1010-16UM7.5kW190UM
GV2P1413-18UM11kW216UM
GV2P1616-24UM11kW288UM
GV2P2020-32UM15kW384UM
GV2P3224-32UM15kW384UM
GV2P4032-40UM18.5kW480UM
  1. Modelos de substituição & Comparação de concorrentes

4.1 Internal Schneider Replacements

Modelo originalModelo de substituiçãoDiferençasCenários de aplicação
GV2P32 (Importado)GV2PM32C (Doméstico)Different origin, minor certification differences; profundidade: 91milímetros (GV2P: 95milímetros)Domestic projects, cost-sensitive applications, CCC certification required
GV2P32GV2ME32 (Domestic push-button type)Operação por botão, parâmetros elétricos idênticosApplications requiring push-button control, orçamento limitado
GV2P32GV3P32 (Upgraded series)Higher breaking capacity and enhanced functionsEnvironments with high short-circuit risk, advanced protection required

4.2 Cross-brand Competitor Comparison

MarcaModeloFaixa AtualPolonesesMagnetic Trip RatioPrincipais diferenças
SchneiderGV2P3224-32UM3P12×EmMultiple certifications including marine approval, IP20
ABBMS325-3224-32UM3P12×EmCapacidade de ruptura: 15o, larger dimensions
Siemens3RV2031-4KA1024-32UM3P13×EmOptional electronic trip, preço mais alto
EatonPKZM0-3224-32UM3P12×EmSpring terminals for easy installation
ChintNM1-63S/330025-32UM3P10×EmVantagem de custo, alternativa doméstica
  1. Ambientes de aplicativos & Casos Típicos

5.1 Aplicativos recomendados

Controle de motores industriais: Main circuit protection for three-phase motors such as pumps, fãs, compressors and conveyors

OEM Equipment: Supporting machine tools, máquinas de embalagem, printing machines and textile machinery

Construindo Sistemas Elétricos: Protection for critical motors including air conditioning units, fire water pumps and drainage pumps

Marinho & Engenharia Offshore: Compliant with marine classification standards for ship power systems

Áreas Perigosas: ATEX certified for motor protection in non-explosion-proof zones

5.2 Aplicativos não recomendados

Single-phase Motors: 3-pole design not suitable for single-phase circuit protection

Frequent Start-Stop Operations: Mais do que 10 cycles per hour will shorten service life

High Altitude (>2000eu): Derating required (10% reduction per 1000m rise)

Ambientes de vibração severa: Extra reinforcement needed to avoid false tripping

Ambientes Corrosivos: IP20 protection is insufficient; additional enclosure is required

5.3 Casos de aplicação típicos

Caso 1: Water Treatment Plant Pump Protection

Equipamento: 3 sets of 15kW submersible three-phase pumps (400V)

Configuração: GV2P32 + LC1D32 Contactor + LRD3322 Thermal Overload Relay (redundant protection)

Resultado: Prevented 3 motor overload faults and 1 short-circuit fault, extending equipment service life by 2 anos

Caso 2: Conveyor System in Automobile Manufacturing Plant

Equipamento: 12 conveyor lines each equipped with 15kW motor

Configuração: GV2P32 linked with Schneider PLC

Características: Rotary knob enables quick on-site reset and reduces downtime

  1. Solução de problemas & Maintenance Manual

6.1 Falhas Comuns & Soluções

Fenômeno de falhaPossíveis causasSoluções
Frequent thermal tripping1. Sobrecarga do motor1. Check motor load and eliminate mechanical jamming
2. Improper low current setting2. Set current to 1.1 times motor Full Load Current (FLA)
3. Temperatura ambiente excessivamente alta3. Melhore a ventilação e reduza a temperatura ambiente
4. Loose terminals causing overheating4. Inspect and tighten terminals
Instant magnetic tripping1. Curto-circuito1. Power off and test circuit insulation
2. Damaged motor winding insulation2. Measure winding resistance and replace faulty motor
3. Arc short circuit inside contactor3. Inspect contactor contacts and replace if necessary
Falha ao fechar1. Tripping mechanism not reset1. Turn knob to OFF position then re-close
2. Damaged rotary knob2. Check knob linkage and replace damaged parts
3. Internal mechanical failure3. Arrange professional maintenance or replace the breaker
Nenhuma saída após o fechamento1. Burned internal contacts1. Desligar, inspect main contacts and replace defective unit
2. Fiação incorreta2. Verify wiring to ensure correct three-phase connection
3. Faulty tripping mechanism3. Check tripping mechanism and replace if needed

6.2 Maintenance Procedures

  1. Inspeção Diária (Semanalmente)

Check knob position and status indication

Look for abnormal heat, odor or noise

Confirm all terminals are tightly connected

  1. Manutenção de rotina (Todo 6 Meses)

Power off and remove dust with dry compressed air

Inspect main contacts for burning and oxidation

Test tripping function by simulating overload and short circuit conditions

  1. Annual Maintenance

Check lubrication of internal mechanical components

Verify accuracy of current setting

Retighten all electrical connections

6.3 Quick Diagnosis Tips

Thermal trip? Check load and current setting.

Magnetic trip? Locate short circuit and test insulation.

Fail to close? Reset first; replace for mechanical faults.

No output? Inspect contacts and wiring.

  1. Seleção & Installation Guidelines

7.1 Regras de seleção

Correspondência atual: Motor FLA must fall within 24-32A; recommended setting: FLA × 1.1

Combinação de poder: Standard solution for 15kW @ 400V three-phase motors

Protection Coordination: Use with contactors and fuses to ensure selective protection

Ambient Derating: Desclassificar 1% per ℃ above 40℃

7.2 Notas de instalação

Mounting Direction: Instalação vertical (allowable deviation: ±15°) for normal tripping operation

Liberação: Reserve 10mm space on left & right sides, 20mm on top & bottom for heat dissipation

Padrão de fiação: Copper wire with cross-section 1.5-25mm²; torque de aperto: 6-8Nm

Função de bloqueio: Padlock can be fitted to prevent accidental operation, cumprindo as normas de segurança

  1. Production Status & Soluções de atualização

Current Status of GV2P32: Em produção, no discontinuation plan (as of June 2026)

Atualizar & Opções de substituição:

  1. Atualização Funcional: GV3P32 (higher breaking capacity and extra protection functions)
  2. Alternativa Doméstica: GV2PM32C (lower cost with equivalent performance)
  3. Atualização Inteligente: TeSys T series (with communication for remote monitoring)