Rockwell Automation no longer supplies new units. Items available on the market are second-hand, refurbished or spare stock. It is a classic legacy monochrome HMI of the PanelView Standard 550 série. ✅ Model Breakdown 2711-T5A2L1 2711: PanelView Standard series T: Touchscreen only (no membrane keypad) 5: 5.5-inch display A: Monochrome LCD (noir & blanc) 2: ...

  • Détails du produit

Rockwell Automatisation no longer supplies new units. Items available on the market are second-hand, refurbished or spare stock. It is a classic legacy monochrome IHM of the PanelView Standard 550 série.

✅ Model Breakdown

2711-T5A2L1

2711: PanelView Standard series

T: Touchscreen only (no membrane keypad)

5: 5.5-inch display

UN: Monochrome LCD (noir & blanc)

2: DH-485 communication port, no print port

L1: 24V DC power supply version

📋 Core Technical Specifications

ArticleCaractéristiques
Afficher5.5-inch monochrome LCD, resistive touchscreen
Alimentation18~30 V CC, rated 24VDC; Max 12W, 0.5A@24V
CommunicationDH‑485 (for connection with legacy AB SLC500, MicroLogix PLCs)
MémoireNon-volatile memory 240KB / RAM 170KB
MontagePanel cutout mounting, front panel IP65
Logiciel de programmationPanelBuilder32 (legacy software, 32-bit OS only)
Firmware VersionsCommon A series, micrologiciel 3.30/4.41 etc..
Température de fonctionnement0~55℃
Unavailable PortsNo print port, pas d'Ethernet

📌 Typical Applications

Legacy production line retrofits, machines d'emballage, manutention des matériaux, traitement de l'eau, and older SLC500/MicroLogix projects. DH485 bus only, no EtherNet/IP support.

⚠️ Common Failures & Des pièces de rechange

  1. Backlight degradation: Most typical fault. Spare part 2711-NL1 (CCFL backlight tube; LED backlight modification is also feasible)
  2. Panneau tactile endommagé: PV550 touch membrane can be replaced separately
  3. Perte de programme: On-board coin cell battery preserves screen programs; program loss occurs once battery fails
  4. Échec de communication: DH485 bus termination resistor, wiring polarity, RSLinx driver issues

🔁 Replacement Options for Engineering Retrofit

Original project cannot be migrated directly, screen reconfiguration is mandatory

  1. Preferred direct replacement: 2711R-T4T / 2711R-T7T (Vue du panneau 800). Supports RS485 and connects to legacy PLCs;
  2. Modern alternative: PanelViewPlus 7 / Vue du panneau 5000 series with Ethernet port;
  3. 3rd-party domestic HMI: Weintek / Kunlun MT, connecting legacy AB controllers via DH485/Modbus with lower cost.

📎 Supporting Documentation

Manuel: 2711-UM014 (PanelView Standard Terminal User Manual)

Datasheet: 2711-TD007

Référence du code SH

85287110 (Industrial touchscreen, IHM, applicable for customs declaration)

2711-T5A2L1 (Vue du panneau 550) Old-to-New HMI Program Migration Assessment Checklist

En vigueur: Migration from legacy AB PanelView Standard 550 to PanelView 800 / PanelViewPlus / 3rd-party domestic HMI

Point clé: PanelBuilder32 project cannot be imported into new HMI software; full reconfiguration required. This checklist is used for pre-migration risk assessment and workload estimation.

  1. Matériel & Communication Assessment
Assessment ItemInspection ContentRisk Notes
Original Controller ModelSLC500 / MicroLogix 1000/1100/1200/1500?Legacy PLC only supports DH485; verify whether new HMI has native DH485, otherwise protocol converter required
Protocole de communicationOriginal: DH485New HMI options: DH485 / DF1 / Modbus RTU (PLC side must support)
Address MappingOriginal PV550 tags: N, B, T, C, R., F and other PLC registers⚠️ Register addresses must be checked line by line, do not copy by experience; distinguish bits / mots / floats
Câblage des communicationsExisting DH485 bus, termination resistors, wiring polarityNew HMI communication interface differs, evaluate rewiring and additional converter workload
Alimentation24VCCMost old & new units compatible; verify terminal definition and fuse rating
Panel Cutout Dimension2711-T5A2L1 cutout: 216 × 152mmNew HMI dimension differs; evaluate: remplacement direct / adapter plate / cabinet cutout modification
Environnement d'installationTempérature, poussière, vibrationVerify new HMI environmental rating and IP protection match site conditions
  1. Original HMI Project Inventory (Export from PanelBuilder32)
Assessment ItemInspection ContentRemarques
Total Screen CountMain screen, manual mode, alarme, parameter, trendCount screens to estimate configuration man-hours
Screen Element ListButtons, indicateurs, numeric displays, input boxes, sélecteursDistinguish bit read/write, word read/write, multi-state indicators
Alarm InformationAlarm text, trigger bit, acknowledge bit, alarm log⚠️ PV550 uses simple bit-triggered alarms; new HMI alarm storage capacity varies
Recipe FunctionRecipe used or not?PV550 recipes stored locally in HMI; re-plan recipe storage location (IHM / API) for new HMI
Trend CurvesReal-time / historical trend, sampling cycleLegacy PV550 only supports simple real-time trend without large-capacity history logging; evaluate history storage for new HMI
Security AccessPassword, user level, screen access permissionVieux & new permission models differ; recreate user accounts
Macro / Script LogicPanelBuilder32 built-in macrosHigh risk: Macros cannot be migrated. All logic must be rewritten using new software scripts / fonctions
Screen Switch LogicScreen jump buttons, conditional jumpReplicate conditional jump logic line by line
Print FunctionThis 2711-T5A2L1 model has no print port, skip this itemEvaluate printing if other models in the series are used
Hardcopy / ScreenshotScreen capture function required?Configure on demand for new HMI

III. Tag / Variable Mapping Assessment (Core Workload Item)

  1. Export full variable list of original project (print variable table in PB32)
  2. Classification & statistics:

Boolean (Peu: Courir, Faute, Auto/Manual, Alarms)

Integer (Word: Setpoints, Counters)

Float (Température, Pression)

  1. Verify PLC data file types: N files, B files, T/C preset values, registers
  2. Mark special variables:

Arrays

Indirect addressing (High risk: many new HMIs do not support legacy AB indirect addressing syntax)

Read-only / Read-write attributes

Risk note: DH485 address notation differs between HMI software packages, prone to address offset errors.

  1. Function Equivalence Assessment (Item-by-item comparison, mark missing functions)
Original PV550 FunctionRemarques
Bit buttons, momentané / latching buttonsDistinguish momentary pushbuttons (most common error source)
Multi-state indicators (3-État / multi-state)
Numeric input, limit validationPV550 local limit check; new HMI can validate on HMI side or PLC side
Screen jump, conditional jumpTest conditional jump logic
Alarm trigger, alarm acknowledgeAlarm text encoding (Chinois / Anglais; legacy units mostly English)
Recipe read/writeVerify recipe quantity and data length
Real-time trendCycle d'échantillonnage, channel quantity
User password permissionPassword hierarchy, lock function
Macro logicDecompose macro logic and implement via PLC logic or new HMI scripts
  1. PLC Side Change Assessment

Whether PLC program modification is required to adapt new HMI communication

Whether spare PLC register space is available for new HMI functions (recipes, history logging)

Whether PLC firmware supports new protocols (par exemple. DF1)

Downtime window assessment for PLC program download

  1. Test Plan Assessment
  2. Offline simulation: Simulate screens and variables in HMI software, verify addresses
  3. Bench test: New HMI + identical site PLC bench commissioning (recommended to reduce on-site downtime)
  4. Step-by-step on-site power-up test:

Communication connectivity test

All screen switching

Full button operation & indicator feedback

Parameter write / read verification

Alarm trigger & acknowledge test

Recipe read/write test

  1. Long-term aging test (facultatif)
  2. Rollback plan: Keep old HMI, mark wiring for fast fallback in case of failure

VII. Documentation & Delivery Assessment

Backup of new HMI project source file

Variable cross-reference table (old tags ↔ new HMI variables)

Screen function specification document

Updated wiring diagram (HMI terminals, communication bus)

Updated site operation manual

Spare parts list (new HMI spare parts, module de communication)

VIII. Risk Summary & Man-hour Estimation

Fill directly into assessment form

  1. High-risk items: Macro logic, indirect addressing, address misalignment
  2. Medium-risk items: Alarm logic, recipes, communication parameter mismatch
  3. Low-risk items: Screen layout, static text

Man-hour reference:

10 basic screens without complex macros/recipes: estimated 1~2 working days for configuration + essai; projects with heavy macros, recipes, indirect addressing require double the man-hours.

  1. Downtime Plan Assessment

Planned downtime window duration

Wiring modification time

Commissioning time

Emergency plan & rollback scheme

Rockwell Allen-Bradley PanelView HMI Full Series List

Grouped by generation, marked【Active / Discontinued】, with supporting software and key features. Optimized for your 2711-T5A2L1 legacy screen retrofit selection

Catalog rule: 2711 = legacy classic; 2711R=PanelView800; 2711P=PanelView Plus; 2715=PanelView5000; 2800=OptixPanel

  1. Legacy Classic Series (All discontinued, second-hand/spare market; your 2711-T5A2L1 belongs here)

1.1 PanelView Standard (2711 série, monochrome / early color, PanelBuilder32 software)

Vue du panneau 300: 2711-T3A / 2711-K3A, 3-inch monochrome, DH485

Vue du panneau 550: 2711-T5A2L1 / 2711-K5A2L1, 5.5-inch monochrome (votre modèle)

Vue du panneau 600: 2711-T6C / 2711-K6C, 6-inch color

Vue du panneau 900: 2711-T9C / 2711-K9C, 9-inch color

Vue du panneau 1000: 2711-T10C / 2711-K10C, 10-inch color

Communication: DH485, DF1; Pas d'Ethernet; Logiciel de programmation: PanelBuilder32 (32-bit Windows only)

Typical faults: CCFL backlight aging, on-board coin cell causing program loss

1.2 PanelView Component (2711C, Discontinué)

2711C-C200, miniature modular HMI, paired with Micro800 compact PLC, simple screens

1.3 Early Generation PanelView Plus (First-gen 2711P, Discontinué)

Original PV Plus, Grimacer, FactoryTalk Voir ME, 600/700/1000/1250/1500

  1. Previous Generation: PanelViewPlus 6 (2711P., EOL Discontinued, existing installed base)

Logiciel: FactoryTalk View Machine Edition (FTView ME), WinCE6.0

PV Plus6 400: 2711P-T4C / K4C, 4-pouce

PV Plus6 600: 2711P-T6C / K6C, 6.5-pouce

PV Plus6 700: 2711P-T7C / K7C, 7-pouce

PV Plus6 1000: 2711P-T10C / K10C, 10.4-pouce

PV Plus6 1250: 2711P-T12C / K12C, 12.1-pouce

PV Plus6 1500: 2711P-T15C / K15C, 15-pouce

Suffix explanation: T=Touch; K=Membrane Keypad; C=Color; D=DC power; A=AC power

  1. Active Classic: PanelViewPlus 7 (2711P., Active for Sale), Standard / Performance versions

Logiciel: FactoryTalk Voir ME; Performance version runs Win10 IoT Core, supports video, VNC, DLR ring

Version standard: 4”,7”,10”,12”,15”

Exemples: 2711P-T4W21D8S, 2711P-T7C21D8S, 2711P-T10C21D8S, 2711P-T12W21D8S, 2711P-T15C21D8S

Performance high-performance version: 7~19” wide screen, stainless steel enclosure, conformal coated ArmorView machine-mount type

Exemples: 2711P-T7C22D9P, 2711P-T10W22D9P, 2711P-T15C22D9P, 2711P-T19C22D9P

  1. Economy Small Size: Vue du panneau 800 (2711R., Active for Sale), Preferred replacement for legacy DH485 projects

Logiciel: FactoryTalk View 800 (lightweight standalone software); Ethernet + RS485/DF1 native support, perfect for SLC500/MicroLogix, recommended replacement for your 2711-T5A2L1

2711R-T4T: 4.3-inch touch

2711R-T7T: 7-inch touch

2711R-T10T: 10.4-inch touch

Touch-only models, rentable, popular for legacy line retrofit

  1. New High-End Platform PanelView 5000 (2715 série, Active for Sale), for Logix5000: ControlLogix/CompactLogix

Logiciel: Studio5000 View Designer (integrated into Studio5000, FTView ME incompatible), native EtherNet/IP for large automation projects

  1. Vue du panneau 5310 (2713P., basique): 4”,7”,10”,12”,15”

Exemple: 2713P-T10CD

  1. Vue du panneau 5510 (2715P., haute performance):7/10/12/15/19”, touche / keypad hybrid

Exemple: 2715P-T7CD, 2715P-T10CD, 2715P-T15CD

⚠️Critical reminder: PV5000 project is fully incompatible with PanelView Plus projects, screen migration impossible

  1. Nouvelle génération: OptixPanel (2800 série, Rockwell new HMI, Active for Sale)

Successor to PanelView 800 doubler, Compact and Standard models, FactoryTalk Optix software, native IoT & edge visualization

OptixPanel Compact (2800C): 2800C-070AS-1S (7-pouce)

OptixPanel Standard (2800S):7/10/12/15-pouce

Designed for new projects, weak native DH485 serial support, not recommended for direct replacement of legacy 2711 écrans

  1. Mobile Handheld HMI: MobileView (2711T)

Cabled pendant handheld operator terminal for machine-side operation, 2711T series, partial models available.

  1. Industrial Panel PC (Not pure touchscreen, industrial all-in-one PC, ASEM series)

6300P., 6300M series industrial panel PCs, Système d'exploitation Windows, for local advanced SCADA operation

Series Selection Comparison Table (Quick reference for retrofit projects)

SérieCatalog NumberCycle de vieLogiciel de configurationScénarios d'application
PanelView Standard2711DiscontinuéPanelBuilder32Legacy spare part maintenance (2711-T5A2L1)
PanelView Plus62711P.DiscontinuéFTView MESpare parts for existing installed base
PanelView Plus72711P.ActifFTView MEMoyen & large production lines, compatible with legacy FT projects
Vue du panneau 8002711R.ActifFTView800✅Legacy DH485 line retrofit, replace 2711-T5A2L1
PanelView50002713P/2715PActifStudio5000 View DesignerLarge Logix5000 projects
OptixPanel2800ActifFactoryTalk OptixNouveaux projets, IoT visualization

General Suffix Definition (Rapid model decoding)

T = Touch only; K = Keypad membrane; B = Touch + Keypad combined

C = Color LCD; A=Monochrome

D = 24VDC supply; A=AC100-240V

W = Wide screen; P = Performance high grade

S = Standard grade

Key Project Migration Tips (Continued from your 2711-T5A2L1 migration assessment)

  1. 2711 (PV Standard) → 2711R PanelView800: Recommandé, supports RS485/DF1 for SLC500/MicroLogix, coût modéré; screens must be reconfigured, PB32 project cannot be imported
  2. 2711 → PanelView Plus7: Also feasible, requires DF1 / serial communication module
  3. 2711 → PanelView5000: Not recommended for legacy DH485 retrofit. Software fully different, extra gateway required for serial port, heavy engineering workload

 