LP1K: TeSys K series, CC coil contactor (LC1K = AC coil version)
09: Rated current 9A under AC-3 duty
01: Intégré auxiliaire contact: 1 Caroline du Nord (Normalement fermé)
BD: Coil voltage DC24V
Terminaux: Bornes à vis-étrier; Montage sur rail DIN; overall width 45 mm
- Principales spécifications électriques
Circuit principal: 3-pôle, 3 AUCUN contact
AC-3 rating @ 440V: 9UN; controls 4kW (380V) moteur; 2.2kW (220V)
AC-1 resistive load rating: 20UN
Tension de fonctionnement maximale: 690V et
Bobine: DC24V, standard DC coil (non-wide voltage)
Contact auxiliaire: Fixed built-in 1 Caroline du Nord
Montage: DIN rail or panel mounting
Front protection degree: IP20
Certifications: CCC, UL, ASC, RoHS, Prime verte
Durée de vie mécanique: 10 millions d'opérations; Durée de vie électrique (AC-3): 1.3 millions d'opérations
Couple de serrage des bornes: 0.8~1.3 N·m
III. Applications typiques
Directly driven by PLC DC transistor outputs; petits ventilateurs, électrovannes, lignes de convoyeurs, Équipement CVC, small power motor start-stop in compact control cabinets.
- Différences de modèles & Options de remplacement
- LP1K0910BD: Same rating, intégré 1 NON (Normalement ouvert) contact auxiliaire (most frequently confused model)
- LP1K0901BD3: Spring-cage terminal variant (different wiring method)
- LC1K0901M7: Même note actuelle, AC220V AC coil version, cannot be directly interchanged
- Alternatives nationales: Chint NC1K, Delixi CJX2K miniature contactors; verify mounting dimensions and auxiliary contact configuration before replacement
- Remarques importantes
Bobine CC; do not connect directly to AC24V supply
DC coils generate back EMF when de-energized. Add a freewheeling diode if driven by PLC transistor outputs to protect the output channel
LA1K auxiliary contact blocks can be snapped on top to expand additional auxiliary contacts
LP1K0901BD (TeSys K, 3Question 9A, DC24V, Built-in 1NC) Cas de candidature
Avantages essentiels: Bobine DC24V, directly driven by PLC transistor outputs; intégré 1 NC contact for interlock and status feedback; seulement 45 mm de large, ideal for dense OEM control cabinets; AC-3 rating for 4kW @ 380V
Cas 1: Small Fan Control for AHU / Fresh Air Handling Units (Building BMS & CVC)
Charger: 380V three-phase centrifugal fans & ventilateurs d'extraction (0.75~4 kW)
Logique de contrôle: DDC/PLC transistor output directly energizes the LP1K0901BD coil; main contacts switch the fan power; the built-in 1 NC contact sends stop feedback to BMS (NC closes when the contactor drops out to report fan shutdown)
Composants correspondants: MCB upstream + LR2K thermal overload relay for motor protection; multiple contactors installed side-by-side on DIN rail to save cabinet space
Avantages: No AC hum from DC coils, suitable for quiet computer room & air-conditioning control cabinets; fully compatible with 24VDC building control buses
Cas 2: Segmented Conveyor Drives for Packaging & 3Automatisation C (Nourriture & Electronic OEM)
Charger: Sectional belt conveyors, small drum motors, alimentateurs de matériaux, moteurs d'agitateurs (≤4kW)
Logique de contrôle: PLC 24VDC outputs control jog or continuous operation; multiple LP1K0901BD units control individual conveyor sections; 1 NC contacts implement section interlock (next section cannot start if the upstream section is still running)
Operating conditions: Frequent cycling (jusqu'à 3,600 opérations/heure). 10 million mechanical cycles fit continuous production lines; IP20 protection meets clean cabinet requirements for food workshops
Rappels: Fit a freewheeling diode across the coil to suppress back EMF and prevent PLC transistor burnout
Cas 3: Small Pump Stations & Circulating Water Systems (Traitement de l'eau & Constant Temperature Tanks)
Charger: 380V circulation pumps, chemical dosing agitators, pompes à eau de refroidissement
Logique de contrôle: [text truncated in original draft]
Full TeSys K Contactor Model List
- Coil Voltage Code for AC Models (LC1K / LC2K)
B7=AC24V、E7=AC48V、F7=AC110V、M7=AC220V、P7=AC230V
- LP1K DC Single Contactor (3P., PLC DC24V Preferred)
6Un cadre (06)
LP1K0610BD (6UN, 1NON, 24VCC)
LP1K0601BD (6UN, 1Caroline du Nord, 24VCC)
LP1K0610BD3 (bornes à ressort + suppression de surtension intégrée)
LP1K0601BD3 (bornes à ressort + suppression de surtension intégrée)
9Un cadre (09, your model series)
LP1K0910BD (9UN, 1NON, 24VCC)
LP1K0901BD (9UN, 1Caroline du Nord, 24VCC, your part number)
LP1K0910BD3 (bornes à ressort + suppression de surtension intégrée)
LP1K0901BD3 (bornes à ressort + suppression de surtension intégrée)
12Un cadre (12)
LP1K1210BD (12UN, 1NON, 24VCC)
LP1K1201BD (12UN, 1Caroline du Nord, 24VCC)
LP1K1210BD3 / LP1K1201BD3
16Un cadre (16)
LP1K1610BD (16UN, 1NON, 24VCC)
LP1K1601BD (16UN, 1Caroline du Nord, 24VCC)
LP1K1610BD3 / LP1K1601BD3
Replace BD with ED=48VDC, FD=110VDC, MD=220VDC for other coil voltages.
- LP2K DC Reversing Contactors (Avant/Arrière, built-in mechanical interlock)
9A popular models
LP2K0910BD (9UN, 1NON, 24VDC reversing contactor)
LP2K0901BD (9UN, 1Caroline du Nord, 24VDC reversing contactor)
LP2K0901BD3 (bornes à ressort + suppression de surtension intégrée)
Other current ratings follow the same rule: LP2K0601BD, LP2K1201BD, etc..
- LC1K / LC2K AC Miniature Contactors (Bobine CA)
LC1K Single AC Contactors (examples)
LC1K0610B7, LC1K0601B7 (AC24V)
LC1K0910M7, LC1K0901M7 (AC220V)
LC2K AC Reversing Contactors
LC2K0901B7, LC2K1201M7
- TeSys K Matching Accessories
- Bloc de contacts auxiliaires: LA1K (1NON+1NC, snap-on top mounting)
- Verrouillage mécanique: LA2K (for DIY forward/reverse with two LP1K units)
- Relais de surcharge thermique (direct snap-on bottom): LR2K03… (0.1~8A range, matches 06/09A contactors)
- Suppression des surtensions: BD3 versions have built-in suppression; standard BD coils require external 1N4007 freewheeling diode
- Guide de sélection rapide
- Need RUN feedback (AUCUN contact) → select 10 (LP1K0910BD)
- Need STOP feedback (Contact NF) → select 01 (LP1K0901BD, votre modèle actuel)
- PLC transistor output: prefer BD3 (suppression de surtension intégrée) to eliminate external diodes
- Vibration-prone conveyor applications: choose spring-cage terminal suffix 3 (BD3)