Schneider LC1E630U7 AC Contactor

The domestic full model designation is commonly LC1E630U7N. Discontinued in April 2021. It is a 3-pole high-power AC contactor. ✅ Model Code Definition LC1E: EasyPact TVS AC contactor series 630: AC-3 rated operational current of 630 A U: Tension de bobine 240 V et 7: 50/60 Hz universal AC coil N: Domestic version with CCC certification ...

  • Détails du produit

The domestic full model designation is commonly LC1E630U7N. Discontinued in April 2021. It is a 3-pole high-power AC contactor.

✅ Model Code Definition

LC1E: EasyPact TVS AC contactor series

630: AC-3 rated operational current of 630 UN

U: Tension de bobine 240 V et

7: 50/60 Hz universal AC coil

N: Domestic version with CCC certification (Overseas model LC1E630U7 does not carry suffix N)

This unit has no built-in auxiliary contacts. Auxiliary contacts require add-on accessories.

📋 Core Electrical Specifications

ArticleParamètre
Nombre de pôles3P., 3AUCUN contact principal
Utilisation categoryAC-3 (charges du moteur), AC-1 (charges résistives)
AC-3 Ie630 UN (@ ≤440 V, 55 °C)
AC-1 Ith1000 UN (@ 40 °C)
Tension assignée d'isolement Ui690 V
Tension assignée de tenue aux chocs Uimp8 kV
Coil rated voltage Uc240 V et, 50/60 Hz
Plage de fonctionnement de la bobineRamasser: 0.85~1.1 × Uc; Abandonner: 0.25~0.5 × Uc
Inrush power consumption1650 Virginie; Hold power consumption: 22 Virginie
Compatible motor power220 V: 185 kW 380/400 V: 335 kW 440 V: 400 kW 690 V: 450 kW
Rated short-time withstand current Icw5050 UN / 10 s
Fabrication / Pouvoir de coupureFabrication: 6300 UN; Rupture: 5040 Et @440V

🛠 Mechanical & Endurance Characteristics

Endurance mécanique: 4 millions de cycles

AC-3 electrical endurance: 600,000 cycles; AC-1: 200,000 cycles

Maximum operating rate: 1200 cycles/heure

Temps de fonctionnement: Closing 40~80 ms; Opening 100~200 ms

Montage: Plate mount (high-current frame does not support standard DIN rail)

Couple de serrage: Circuit principal 58 N·m; Circuit de commande 1.2 N·m

Dimension hors tout: W309 × H304 × D255 mm; Poids net: 18.6 kilos

Classe de protection: IP00

Température ambiante de fonctionnement: -5 ~ +55 °C; No derating up to altitude 3000 m

📌 Typical Applications

High-power fans, pompes à eau, compresseurs d'air, concasseurs, large motor starter cabinets, appareillage basse tension; AC-3 squirrel-cage motor start-stop control, switching of heavy resistive loads.

⚠️ Discontinuation & Options de remplacement

LC1E630U7N discontinued in April 2021, no new original production. Stock / second-hand units available on market.

  1. Schneider OEM replacement: LC1G630KUEC (TeSys Giga series, 630 UN, 240 VAC compatible coil)
  2. Alternative nationale: CJX2-F630, NC2-630, etc.. (Vérifier la tension de la bobine, temperature rise and short-time withstand current)

🧰 Optional Accessories

Bloc de contacts auxiliaires: LA1KN (add-on 1NO+1NC)

Coil surge suppressor, verrouillage mécanique, terminal shroud, relais de surcharge thermique (large frame LRD series)

📎 Inspection Checklist for Second-hand Acceptance

  1. Measure coil resistance and compare with reference value for same model; power on to test pull-in / drop-out, pas de grippage ni de bruit anormal
  2. Inspect main contact surface for ablation or welding; check consistency of contact resistance across three phases
  3. Dielectric strength test: 2.5 kV / 1 min between phases and main circuit to earth
  4. Verify terminal tightening torque; inspect busbar contact surface for oxidation and overheating discoloration
  5. Test operating voltage: Reliable pull-in at 0.85Uc, reliable drop-out below 0.5Uc

LC1G630KUEC VS LC1E630U7 Parameter Comparison Table

LC1E630U7: Téléviseurs EasyPact, abandonné; LC1G630KUEC: TeSys Giga, OEM replacement. KU = 100~250 V AC/DC wide-range coil (compatible with original 240 ACC).

ParamètreLC1E630U7LC1G630KUECRemarques
Série de produitsTéléviseurs EasyPact (Easy TeSys)TeSys GigaSchneider new generation high power contactor
Model definition3P., AC-3 630 UN, bobine 240 V et, 50/60 Hz3P., AC-3 630 UN, 100~250 V AC/DC wide coilGiga AC/DC universal coil, direct replacement for U7 (240ACC) without control circuit modification
Statut du produitDiscontinued Apr 2021, action / second-handEn production, genuine new
Poteaux / Contacts principaux3P., 3NON3P., 3NON
AC-3 rated Ie @≤440V630 UN (55 °C)630 UNIdentical rating for motor loads
AC-1 conventional thermal current Ith @40 °C1000 UN1050 UNGiga higher resistive load capacity
Tension assignée d'isolement Ui690 V1000 VGiga upgraded insulation
Tension assignée de tenue aux chocs Uimp8 kV8 kVIdentique
Rated short-time withstand current Icw5050 UN /10 s5050 UN /10 s; 4400 UN /30 sSame 10s withstand; Giga superior long-duration withstand
Making capacity @440V6300 UN7220 UNGiga higher short-circuit making capability
Breaking capacity @440V5040 UN5550 UN
Contacts auxiliaires intégrésAucun, LA1KN add-on required1NO+1NC built-inNo need to purchase auxiliary contact block for retrofit
Type de bobineAC only, 240 V, 50/60 HzWide-range AC/DC 100~250 VCompatible with AC and DC control supply, better engineering flexibility
Plage de fonctionnement de la bobinePull-in:0.85~1.1Uc Drop-out:0.25~0.5UcPull-in:0.8~1.1Ucmin~Ucmax Drop-out: ≤0.45UcWider voltage tolerance for grid fluctuation
Consommation électrique de la bobineAppel 1650 Virginie; Hold 22 VirginieAppel 800 Virginie; Hold 15 VirginieMuch lower coil power, less cabinet heat
Endurance mécanique4 millions de cycles5 millions de cycles25% amélioration
AC-3 electrical endurance600,000 cycles1 millions de cyclesSignificant improvement under motor duty
Maximum operating rate1200 cycles/heureAC-3: 600 cycles/heureLC1E better for frequent cycling; LC1G sufficient for standard motor applications
Temps de fonctionnementClose 40~80 ms; Open 100~200 msClose 40~70 ms; Open 15~50 msGiga faster opening
Température ambiante-5 ~ +55 °C-25 ~ +60 °CGiga supports low-temperature startup
Classe de protectionIP00IP2X with shroudFinger-safe protection
Dimension(L×H×P)309 × 304 × 255 mm211 × 284 × 266 mm~32% narrower, économise de l'espace dans l'armoire
Poids net18.6 kilos14.2 kilos4.4 kg lighter for easier handling
Main circuit tightening torque58 N·m58 N·mBusbar torque unchanged, busbars can be reused
Control circuit torque1.2 N·mPush-in spring terminalTool-free control circuit connection
MontagePlate mountPlate mountMounting hole pattern incompatible, base plate re-drilling required
Power dissipation per pole (AC-3)48 W26 WLower contact loss, less temperature rise
Motor power AC-3 @400V335 kW335 kWIdentical motor rating
Extra featuresBasic contactorOptional contact wear diagnosis, verrouillage mécanique, retour d'étatPredictive maintenance available for critical loads

✅ Replacement Summary

  1. Main circuit rating fully equivalent: Convient pour 335 kW, 400 V motor. Keep busbar torque at 58 N·m; Mounting hole layout differs, base plate re-drilling required.
  2. Control circuit advantage: LC1G630KUEC wide-range 100~250 V AC/DC coil works directly with original 240 VAC control supply; lower coil power and built-in 1NO+1NC auxiliary contacts, no auxiliary accessory purchase.
  3. Limitation: Max operating rate reduced to 600 cycles/heure. Applications with frequent inching or high cycle count need evaluation.
  4. Temperature rise & fiabilité: Giga higher insulation voltage, lower contact loss and wider ambient temperature range, ideal for critical continuous-duty loads.

⚠️ Engineering Replacement Risk Notes

Original 240 V AC control supply can connect directly to LC1G630KUEC coil.

Do not replace directly for heavy inching / marche arrière fréquente >600 cycles/heure; performance review mandatory.

Much narrower frame width; existing busbars and protective baffles need rework.

LC1G630KUEC (TeSys Giga) Industrie & Load Application Guide

LC1G630KUEC: AC-3 630 UN, rated for 335 kW three-phase squirrel cage motor at 400 V. Built-in contact wear diagnosis, wide-range AC/DC coil and IP2X shroud. Designed for high-power motor start-stop, star-delta starters and heavy resistive load switching. Max operating rate 600 cycles/heure, not recommended for high-frequency inching.

🏭 1. Eau & Eaux usées (Waterworks, Sewage Plants, Pumping Stations)

Typical loads: Large raw water pumps, pompes de relevage des eaux usées, pompes de circulation, sludge pumps, ventilateurs d'aération, main drive motors for scrapers.

Caractéristiques: 24/7 continuous operation requiring high reliability. LC1G supports -25 °C low temperature operation and contact wear diagnosis for predictive maintenance. Widely used in MCC pump cabinets and the most common retrofit candidate replacing LC1E630U7.

🌬️ 2. Grand CVC, Centres de données & Commercial Complexes

Typical loads: Chiller compressors, large cooling tower fans, primary / secondary chilled water pumps, building exhaust fans.

Caractéristiques: Building MCC switchgear, frequent start-stop and elevated cabinet ambient temperature. Giga Ui=1000 V high insulation and low temperature rise; wide coil accommodates building supply voltage fluctuation.

⚙️ 3. Métallurgie, Exploitation minière & Matériaux de construction

Typical loads: Concasseurs, broyeurs à boulets, heavy belt conveyors, kiln blowers, hoist motors (derating required for AC-4 duty).

Caractéristiques: Heavy shock loads and dusty harsh environment; strong short-time withstand and short-circuit capacity. AC-4 hoist duty limited to max 150 cycles/heure, derating mandatory during selection.

🛢️ 4. Pétrochimique & Énergie (Huile & Gas, Solaire, Énergie éolienne)

Typical loads: Process pumps, compresseurs, thermal oil furnace blowers, wind turbine yaw / pitch large motors, high-power resistive load switching for PV systems.

Caractéristiques: Mounted outside explosion-proof enclosures, prone to supply voltage fluctuation. Wide-range 100~250 V AC/DC coil with high control supply compatibility; Marine certification available for auxiliary motor circuits on offshore platforms.

📦 5. Papier, Pulpe, Nourriture & Pharmaceutique

Typical loads: Paper machine main fans, pompes à vide, large agitator motors, drying resistive heating loads (AC-1).

Caractéristiques: Continuous production with zero unscheduled downtime tolerance. Contact wear diagnosis enables advance replacement planning.

🏗️ 6. Infrastructure & Railway Auxiliary Systems

Typical loads: Tunnel exhaust fans, station large water pumps, refroidisseurs, port crane auxiliary drives, terminal conveying equipment.

Caractéristiques: Preferred choice for project-type MCC panel builders; compatible with star-delta starter schemes with LA9G mechanical interlock accessory.

🧱 7. OEM Panel Builders & System Integrators

Panel builders: Low voltage Motor Control Centre (Centre multicompte), large motor starter cabinets, star-delta starter panels, soft starter bypass contactors (Bypass duty breaking capacity assessment required).

✅ Load Category Compatibility Summary

AC-3 (Primary use): Normal start-stop squirrel cage motors (pompes, les fans) ✅ Preferred

AC-1: Chauffage résistif, resistive load switching, Ith=1050 A ✅

AC-4: Motor plugging / freinage en marche arrière, avancer lentement (hoists etc.), derating required and strict operating frequency limits ⚠️

AC-6a: Commutation de banque de condensateurs, capacitor dedicated protection required; direct use not recommended

⚠️ Key Selection Limitations

  1. Max AC-3 operating rate: 600 cycles/heure. Applications with higher frequency (avancer lentement, marche arrière fréquente) are not recommended; LC1E630U7 is preferred.
  2. Operating ambient: -25 °C ~ +60 °C, wider temperature range than legacy LC1E630U7.
  3. Mounting hole pattern incompatible with LC1E; cabinet base plate re-drilling required for retrofit.
  4. Marine type approval available for vessel applications.