Positionnement du produit: SIRIUS Innovation series, Taille S0, 3-contacteur AC pôle. Designed for start/stop control of 3-phase motor and load, with screw terminals and DIN rail mounting.
✅ Model Breakdown
3RT2: New generation SIRIUS contactor series
024: Code de spécification, AC-3 12A / 5.5kW @400V
1: Built-in auxiliary contacts 1NO + 1Caroline du Nord
UN: Bobine CA
P.: 230V CA 50 Hz
00: Bornes à vis, no additional function modules
📋 Core Technical Parameters
| Article | Caractéristiques |
| Contacts principaux | 3P normally open, AC-3 12A; controls 5.5kW motor at 400V |
| Contacts auxiliaires | Integrated 1NO + 1Caroline du Nord |
| Tension de bobine | AC230V 50Hz |
| Taille du cadre | Taille S0; Dimension 45×85×97 mm |
| Câblage | Bornes à vis, Montage sur rail DIN |
| Tension d'isolation nominale | 690V; Rated Impulse Withstand Voltage 6kV |
| Température de fonctionnement | -25℃ ~ +60℃ |
| Endurance mécanique | 10 millions d'opérations |
| Courant de tenue de courte durée | 110A for 10s |
| Classe de protection | IP20 (terminals and front face) |
| Code SH | 85364900 |
🧩 Application Scenarios
Start/stop and reversing control of 3-phase asynchronous motors
Ventilateurs, pompes à eau, belt conveyors and small machine tool loads
HVAC and automation control cabinet power circuits
🔁 Reference Replacement Models
- Upgrade relation: 3RT1024-1AP00 (old, abandonné) → 3RT2024-1AP00 (successor)
- Same rating with different coil voltage:
3RT2024-1AN20: AC220V 50/60Hz wide-range coil
3RT2024-1BB40: Bobine DC24V
- Equivalent national: Siemens 3RT6024-1AP00 (locally manufactured, paramètres électriques identiques)
⚠️ Sélection & Notes d'entretien
- Pour remplacement, verify: AC-3 current rating, tension de bobine, quantity of auxiliary contacts
- Recommended matched thermal overload relay: 3RU2124 series (for 5.5kW motors)
- Accessoires en option: suppresseur de surtension, contacts auxiliaires latéraux, verrouillage mécanique
- Second-hand inspection checklist: coil resistance measurement, main contact erosion check, pull-in & release action test
Siemens 3RT2024-1AP00 Full Technical Data
SIRIUS 3RT2, Cadre S0, 3-contacteur de puissance de pôle, bornes à vis, Montage sur rail DIN
- Contacts principaux (Circuit de puissance)
| Article | Caractéristiques |
| Poteaux | 3P., 3 contacts principaux normalement ouverts |
| Rated operational current Ie (AC-3) | 12Un @400V |
| Puissance nominale du moteur (AC-3) | 5.5kW for 3-phase motor @400V |
| Rated current for resistive load (AC-1) | 20UN |
| Tension assignée d'isolement Ui | 690V |
| Tension assignée de tenue aux chocs Uimp | 6kV |
| AC-4 rated current | 12.5Un @400V |
| Courant de tenue de courte durée | 110UN, 10s |
| Max cross-section of main circuit cable | 10mm簡 |
- Contacts auxiliaires intégrés
Configuration: 1NON + 1Caroline du Nord (intégré, non amovible)
Calibre des contacts auxiliaires: AC-15 3A / DC-13 0.5A
Max voltage for auxiliary contacts: 400V et
III. Paramètres de la bobine (Circuit de contrôle)
| Article | Caractéristiques |
| Rated coil voltage | AC230V, 50Hz |
| Coil operating voltage range | 0.8 ~ 1.1 × Ue (184V ~ 253V) |
| Apparent power during pull-in | 65Virginie |
| Apparent power during holding | 6Virginie |
| Type de bobine | Bobine CA |
- Durée de vie & Fréquence de fonctionnement
Durée de vie mécanique: 10,000,000 opérations
Durée de vie électrique AC-3: environ. 1,000,000 opérations
Max operating frequency under AC-3: 1000 cycles/heure
Max operating frequency under AC-4: 300 cycles/heure
- Environnemental, Dimensionnel & Données mécaniques
Taille du cadre: Taille S0
Dimension hors tout: W45mm × H85mm × D97mm
Poids net: environ. 0.405kilos
Montage: 35mm rail DIN, or plate mounting via screws
Terminaux: Bornes à vis-étrier
Température ambiante de fonctionnement: -25℃ ~ +60℃ (à l'intérieur du meuble)
Température de stockage: -55℃ ~ +80℃
Classe de protection: IP20 (front face and terminals)
- Normes & Certifications
Compliance standard: CEI 60947-4-1 / FR 14048.5
Certifications: CCC, CE, UL
Code SH: 85364900
VII. Définition du modèle
3RT2: New generation SIRIUS contactor series
024: Code de spécification, AC-3 12A, Taille S0
1: Contacts auxiliaires 1NO+1NC intégrés
UN: Bobine CA
P.: AC230V 50Hz
00: Bornes à vis, no built-in surge suppression
VIII. Matching Selection Reference
- Relais de surcharge thermique: 3RU2124 (matched for 5.5kW motors)
- Accessoires: contacts auxiliaires latéraux, RC surge absorber, mechanical interlock module
- Locally manufactured equivalent model: 3RT6024-1AP00, fully identical electrical parameters
Siemens 3RT2024-1AP00|Application Fields & Load Types
Specification baseline: Cadre S0, AC-3 12A / 5.5kW@400V, 3-contacteur AC pôle. Primarily used for direct-on-line (DOL) starting of 3-phase motors; also suitable for AC-1 resistive loads. Integrated 1NO+1NC auxiliary contacts for PLC feedback and interlock circuits.
🏭 1. General Machinery Manufacturing (Le plus courant)
Petites machines-outils: cooling pumps, pompes de lubrification, chip removal motors
Conveying equipment: convoyeurs à bande, lignes à rouleaux, ascenseurs
Pneumatic systems: start/stop for small piston air compressor motors
Équipement d'emballage: stretch wrappers, soudeuses de caisses, small stirring motors
Travail du bois & plastic machinery: shredders, auxiliary extruder motors, les fans
🌬️ 2. CVC & Automatisation des bâtiments
Ventilateurs d'unité de traitement d'air, pompes à eau de refroidissement, condensate pumps for central air conditioning
Petits compresseurs, exhaust fans and fresh air fans of air-cooled / water-cooled units
Building control cabinets, fire smoke exhaust fans (with thermal relay protection)
Charges résistives: electric heating elements, commercial lighting circuits (AC-1, max.20A)
🥤 3. Nourriture, Boisson & Industrie pharmaceutique
Wash pumps, agitator tanks, transfer pumps, small drive motors for filling lines
Fans and pump sets for CIP cleaning systems
Fans and circulating water pumps in cold storage and clean rooms
Avantages: Wide temperature range -25~+60℃, CCC/CE/UL certifications, suitable for clean control cabinets
💧 4. Traitement de l'eau & Water Supply/Drainage
Small sewage pumps, clean water pumps, chemical dosing agitator motors
Rainwater harvesting, greywater systems, filter drive motors
Local pump station control cabinets, PLC remote start-stop + operation feedback (via built-in auxiliary contacts)
🚗 5. Automobile & Component Automation
Montages d'outillage, roller conveyors at workstations, workstation cooling fans
Exhaust fans in spray booths, small hydraulic station motors
Motor start-stop control for test benches
⚙️ 6. Autres applications industrielles
- MCC Motor Control Centre: 5.5kW motor circuits in drawer units; forms complete motor protection unit together with circuit breaker and thermal relay
- Contournement du VFD: Bypass switching for small variable frequency drives (Note: Frequent switching is not recommended)
- Small hydraulic stations: Start-stop control for hydraulic oil pump motors
- Solaire / energy storage auxiliary: Cabinet cooling fans and circulating pump control
✅ Applicable Load Types
- AC-3: 3-phase asynchronous motor (5.5kW@400V), Direct en ligne (DOL) starting (primary use)
- AC-1: Charges résistives, electric heating, incandescent lamp groups, max.20A
- AC-4: Motor inching and forward/reverse rotation (Note: limited operating frequency, max.300 cycles/hour)
❌ Non-suitable Scenarios
Motors rated >5.5kW
Heavy frequent inching and heavy shock duty (long-term high frequency under AC-4)
Capacitor reactive power compensation (special 3RT26 capacitor contactor required; this model cannot be substituted)
DC main circuit loads (this is an AC contactor)
💡 Selection Key Points
Built-in 1NO+1NC mirror auxiliary contacts for running feedback, fault interlocking and safety circuits, ideal for PLC automation control
Montage sur rail DIN, compact width (45mm), suitable for dense cabinet layout
Siemens 3RT2024-1AP00|Cross-Brand Equivalent Comparison Table
Baseline specification: 3P., AC-3 12A, 5.5kW@400V, AC230V 50Hz coil, built-in 1NO+1NC auxiliary contacts, bornes à vis, Rail DIN
⚠️ Remarque: Electrically equivalent replacement; dimensions hors tout, cutouts and accessories may not be fully compatible. Verify mounting dimensions and auxiliary contact configuration before cabinet retrofit.
| Marque | Modèle équivalent | Remarques |
| Siemens (Même marque) | 3RT6024-1AP00 | SIRIUS domestique, fully identical parameters, local replacement; obsolete predecessor: 3RT1024-1AP00 |
| Schneider Électrique | LC1D12P7 (TeSys Déca) | 3P AC-3 12A, Bobine AC230V, built-in 1NO+1NC; same 45mm width, most popular direct replacement |
| ABB | AF12-30-11-13 (Série AF) | 3P12A, Bobine AC230V, built-in 1NO+1NC; AF wide-voltage coil, grande polyvalence |
| Rockwell AB | 100-C12*11, coil code A0 (AC230V) | 100série C, 3P12A, integrated 1NO+1NC auxiliary contacts |
| OMRON | CJX2-1211 AC230V (Omron contactor) | 3P12A, 1NON+1NC, bornes à vis |
| LOVATO | BF1211A230 | BF series, 3P AC-3 12A, AC230V, 1NON+1NC |
| Soigné | NXC-12 11 AC220/230V | Mainstream domestic model, 3P12A, 1NON+1NC, rentable |
| DÉLIXI | CJX2s-1211 AC230V | CJX2s series, 12UN, 1NON+1NC |
✅ Key Notes for Cross-brand Replacement (Engineering)
- Contacts auxiliaires: The reference model has built-in 1NO+1NC. Many economical models only have 1NO (par exemple. LC1N1210), cannot be directly replaced due to missing NC feedback contact. Must select suffix 1211 (1NON+1NC).
- Tension de bobine: Baseline AC230V 50Hz. Distinguish:
M7=AC220V 50/60Hz; P7=AC230V 50Hz (fully matches coil of this model)
- Dimensions de montage: Siemens S0 frame width 45mm; Schneider LC1D12, ABB AF12 also 45mm width, directly mountable on DIN rail, cutout generally compatible. Depth differs; verify depth if cabinet space is limited.
- Matched Thermal Relay: Thermal relay model must be changed when switching brand. Contactors and thermal relays from different brands cannot snap-fit together, separate mounting required.
- Verrouillage mécanique & Accessoires: Cross-brand accessories not interchangeable. Reversing interlock modules and side-mounted auxiliary contacts cannot be mixed.
❗ Quick Selection Recommendation
Direct replacement for project, haute compatibilité: Schneider LC1D12P7
Cost reduction with domestic product: CHNT NXC-12 11 AC230V
Overseas project, wide voltage requirement: ABB AF12-30-11-13
Siemens 3RT2024-1AP00 (S0 Frame) Dimensions de montage
Unité: mm
Dimensions hors tout
Largeur W:45
Hauteur H:85
Profondeur D:97 (from DIN rail backplate to front of terminals)
Méthodes de montage
- Montage sur rail DIN: Rail DIN standard de 35 mm (VOTRE UN 60715), clip-on installation
- Fixation par vis: Can also be plate-mounted directly on backplate (without rail)
Orientation de montage: ±180° rotation on vertical plane; ±22.5° tilt forward/backward allowed
Cabinet Clearance for Heat Dissipation
Installation côte à côte: 0mm jeu (can be mounted tightly together)
Minimum top, bottom and front clearance: 10mm
Clearance to earthed metal parts: ≥6mm laterally, ≥10mm top/bottom/front
⚠️ Dimension change after adding accessories (Important for cabinet cutout design)
- Front-mounted auxiliary contact block: Largeur & height unchanged, depth increases by 44mm
- Contacts auxiliaires latéraux: Hauteur & profondeur inchangée, width increases
This unit has built-in 1NO+1NC auxiliary contacts; dimension remains 45×85×97 without extra accessories.
Poids
Poids net: 0.405kilos
Référence de remplacement
Schneider LC1D12P7 also has 45mm width, compatible DIN rail position; but depth varies slightly. Double-check depth for cabinet retrofit with limited depth.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur