Siemens 3RT2024-1AP00 Power Contactor - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Siemens 3RT2024-1AP00 Power Contactor - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

contacteur/

Siemens 3RT2024-1AP00 Power Contactor

Positionnement du produit: SIRIUS Innovation series, Taille S0, 3-contacteur AC pôle. Designed for start/stop control of 3-phase motor and load, with screw terminals and DIN rail mounting. ✅ Model Breakdown 3RT2: New generation SIRIUS contactor series 024: Code de spécification, AC-3 12A / 5.5kW @400V 1: Built-in auxiliary contacts 1NO + 1NC A: AC coil P: 230V ...

  • Détails du produit

Positionnement du produit: SIRIUS Innovation series, Taille S0, 3-contacteur AC pôle. Designed for start/stop control of 3-phase motor and load, with screw terminals and DIN rail mounting.

✅ Model Breakdown

3RT2: New generation SIRIUS contactor series

024: Code de spécification, AC-3 12A / 5.5kW @400V

1: Built-in auxiliary contacts 1NO + 1Caroline du Nord

UN: Bobine CA

P.: 230V CA 50 Hz

00: Bornes à vis, no additional function modules

📋 Core Technical Parameters

ArticleCaractéristiques
Contacts principaux3P normally open, AC-3 12A; controls 5.5kW motor at 400V
Contacts auxiliairesIntegrated 1NO + 1Caroline du Nord
Tension de bobineAC230V 50Hz
Taille du cadreTaille S0; Dimension 45×85×97 mm
CâblageBornes à vis, Montage sur rail DIN
Tension d'isolation nominale690V; Rated Impulse Withstand Voltage 6kV
Température de fonctionnement-25℃ ~ +60℃
Endurance mécanique10 millions d'opérations
Courant de tenue de courte durée110A for 10s
Classe de protectionIP20 (terminals and front face)
Code SH85364900

🧩 Application Scenarios

Start/stop and reversing control of 3-phase asynchronous motors

Ventilateurs, pompes à eau, belt conveyors and small machine tool loads

HVAC and automation control cabinet power circuits

🔁 Reference Replacement Models

  1. Upgrade relation: 3RT1024-1AP00 (old, abandonné) → 3RT2024-1AP00 (successor)
  2. Same rating with different coil voltage:

3RT2024-1AN20: AC220V 50/60Hz wide-range coil

3RT2024-1BB40: Bobine DC24V

  1. Equivalent national: Siemens 3RT6024-1AP00 (locally manufactured, paramètres électriques identiques)

⚠️ Sélection & Notes d'entretien

  1. Pour remplacement, verify: AC-3 current rating, tension de bobine, quantity of auxiliary contacts
  2. Recommended matched thermal overload relay: 3RU2124 series (for 5.5kW motors)
  3. Accessoires en option: suppresseur de surtension, contacts auxiliaires latéraux, verrouillage mécanique
  4. Second-hand inspection checklist: coil resistance measurement, main contact erosion check, pull-in & release action test

Siemens 3RT2024-1AP00 Full Technical Data

SIRIUS 3RT2, Cadre S0, 3-contacteur de puissance de pôle, bornes à vis, Montage sur rail DIN

  1. Contacts principaux (Circuit de puissance)
ArticleCaractéristiques
Poteaux3P., 3 contacts principaux normalement ouverts
Rated operational current Ie (AC-3)12Un @400V
Puissance nominale du moteur (AC-3)5.5kW for 3-phase motor @400V
Rated current for resistive load (AC-1)20UN
Tension assignée d'isolement Ui690V
Tension assignée de tenue aux chocs Uimp6kV
AC-4 rated current12.5Un @400V
Courant de tenue de courte durée110UN, 10s
Max cross-section of main circuit cable10mm簡
  1. Contacts auxiliaires intégrés

Configuration: 1NON + 1Caroline du Nord (intégré, non amovible)

Calibre des contacts auxiliaires: AC-15 3A / DC-13 0.5A

Max voltage for auxiliary contacts: 400V et

III. Paramètres de la bobine (Circuit de contrôle)

ArticleCaractéristiques
Rated coil voltageAC230V, 50Hz
Coil operating voltage range0.8 ~ 1.1 × Ue (184V ~ 253V)
Apparent power during pull-in65Virginie
Apparent power during holding6Virginie
Type de bobineBobine CA
  1. Durée de vie & Fréquence de fonctionnement

Durée de vie mécanique: 10,000,000 opérations

Durée de vie électrique AC-3: environ. 1,000,000 opérations

Max operating frequency under AC-3: 1000 cycles/heure

Max operating frequency under AC-4: 300 cycles/heure

  1. Environnemental, Dimensionnel & Données mécaniques

Taille du cadre: Taille S0

Dimension hors tout: W45mm × H85mm × D97mm

Poids net: environ. 0.405kilos

Montage: 35mm rail DIN, or plate mounting via screws

Terminaux: Bornes à vis-étrier

Température ambiante de fonctionnement: -25℃ ~ +60℃ (à l'intérieur du meuble)

Température de stockage: -55℃ ~ +80℃

Classe de protection: IP20 (front face and terminals)

  1. Normes & Certifications

Compliance standard: CEI 60947-4-1 / FR 14048.5

Certifications: CCC, CE, UL

Code SH: 85364900

VII. Définition du modèle

3RT2: New generation SIRIUS contactor series

024: Code de spécification, AC-3 12A, Taille S0

1: Contacts auxiliaires 1NO+1NC intégrés

UN: Bobine CA

P.: AC230V 50Hz

00: Bornes à vis, no built-in surge suppression

VIII. Matching Selection Reference

  1. Relais de surcharge thermique: 3RU2124 (matched for 5.5kW motors)
  2. Accessoires: contacts auxiliaires latéraux, RC surge absorber, mechanical interlock module
  3. Locally manufactured equivalent model: 3RT6024-1AP00, fully identical electrical parameters

Siemens 3RT2024-1AP00|Application Fields & Load Types

Specification baseline: Cadre S0, AC-3 12A / 5.5kW@400V, 3-contacteur AC pôle. Primarily used for direct-on-line (DOL) starting of 3-phase motors; also suitable for AC-1 resistive loads. Integrated 1NO+1NC auxiliary contacts for PLC feedback and interlock circuits.

🏭 1. General Machinery Manufacturing (Le plus courant)

Petites machines-outils: cooling pumps, pompes de lubrification, chip removal motors

Conveying equipment: convoyeurs à bande, lignes à rouleaux, ascenseurs

Pneumatic systems: start/stop for small piston air compressor motors

Équipement d'emballage: stretch wrappers, soudeuses de caisses, small stirring motors

Travail du bois & plastic machinery: shredders, auxiliary extruder motors, les fans

🌬️ 2. CVC & Automatisation des bâtiments

Ventilateurs d'unité de traitement d'air, pompes à eau de refroidissement, condensate pumps for central air conditioning

Petits compresseurs, exhaust fans and fresh air fans of air-cooled / water-cooled units

Building control cabinets, fire smoke exhaust fans (with thermal relay protection)

Charges résistives: electric heating elements, commercial lighting circuits (AC-1, max.20A)

🥤 3. Nourriture, Boisson & Industrie pharmaceutique

Wash pumps, agitator tanks, transfer pumps, small drive motors for filling lines

Fans and pump sets for CIP cleaning systems

Fans and circulating water pumps in cold storage and clean rooms

Avantages: Wide temperature range -25~+60℃, CCC/CE/UL certifications, suitable for clean control cabinets

💧 4. Traitement de l'eau & Water Supply/Drainage

Small sewage pumps, clean water pumps, chemical dosing agitator motors

Rainwater harvesting, greywater systems, filter drive motors

Local pump station control cabinets, PLC remote start-stop + operation feedback (via built-in auxiliary contacts)

🚗 5. Automobile & Component Automation

Montages d'outillage, roller conveyors at workstations, workstation cooling fans

Exhaust fans in spray booths, small hydraulic station motors

Motor start-stop control for test benches

⚙️ 6. Autres applications industrielles

  1. MCC Motor Control Centre: 5.5kW motor circuits in drawer units; forms complete motor protection unit together with circuit breaker and thermal relay
  2. Contournement du VFD: Bypass switching for small variable frequency drives (Note: Frequent switching is not recommended)
  3. Small hydraulic stations: Start-stop control for hydraulic oil pump motors
  4. Solaire / energy storage auxiliary: Cabinet cooling fans and circulating pump control

✅ Applicable Load Types

  1. AC-3: 3-phase asynchronous motor (5.5kW@400V), Direct en ligne (DOL) starting (primary use)
  2. AC-1: Charges résistives, electric heating, incandescent lamp groups, max.20A
  3. AC-4: Motor inching and forward/reverse rotation (Note: limited operating frequency, max.300 cycles/hour)

❌ Non-suitable Scenarios

Motors rated >5.5kW

Heavy frequent inching and heavy shock duty (long-term high frequency under AC-4)

Capacitor reactive power compensation (special 3RT26 capacitor contactor required; this model cannot be substituted)

DC main circuit loads (this is an AC contactor)

💡 Selection Key Points

Built-in 1NO+1NC mirror auxiliary contacts for running feedback, fault interlocking and safety circuits, ideal for PLC automation control

Montage sur rail DIN, compact width (45mm), suitable for dense cabinet layout

Siemens 3RT2024-1AP00|Cross-Brand Equivalent Comparison Table

Baseline specification: 3P., AC-3 12A, 5.5kW@400V, AC230V 50Hz coil, built-in 1NO+1NC auxiliary contacts, bornes à vis, Rail DIN

⚠️ Remarque: Electrically equivalent replacement; dimensions hors tout, cutouts and accessories may not be fully compatible. Verify mounting dimensions and auxiliary contact configuration before cabinet retrofit.

MarqueModèle équivalentRemarques
Siemens (Même marque)3RT6024-1AP00SIRIUS domestique, fully identical parameters, local replacement; obsolete predecessor: 3RT1024-1AP00
Schneider ÉlectriqueLC1D12P7 (TeSys Déca)3P AC-3 12A, Bobine AC230V, built-in 1NO+1NC; same 45mm width, most popular direct replacement
ABBAF12-30-11-13 (Série AF)3P12A, Bobine AC230V, built-in 1NO+1NC; AF wide-voltage coil, grande polyvalence
Rockwell AB100-C12*11, coil code A0 (AC230V)100série C, 3P12A, integrated 1NO+1NC auxiliary contacts
OMRONCJX2-1211 AC230V (Omron contactor)3P12A, 1NON+1NC, bornes à vis
LOVATOBF1211A230BF series, 3P AC-3 12A, AC230V, 1NON+1NC
SoignéNXC-12 11 AC220/230VMainstream domestic model, 3P12A, 1NON+1NC, rentable
DÉLIXICJX2s-1211 AC230VCJX2s series, 12UN, 1NON+1NC

✅ Key Notes for Cross-brand Replacement (Engineering)

  1. Contacts auxiliaires: The reference model has built-in 1NO+1NC. Many economical models only have 1NO (par exemple. LC1N1210), cannot be directly replaced due to missing NC feedback contact. Must select suffix 1211 (1NON+1NC).
  2. Tension de bobine: Baseline AC230V 50Hz. Distinguish:

M7=AC220V 50/60Hz; P7=AC230V 50Hz (fully matches coil of this model)

  1. Dimensions de montage: Siemens S0 frame width 45mm; Schneider LC1D12, ABB AF12 also 45mm width, directly mountable on DIN rail, cutout generally compatible. Depth differs; verify depth if cabinet space is limited.
  2. Matched Thermal Relay: Thermal relay model must be changed when switching brand. Contactors and thermal relays from different brands cannot snap-fit together, separate mounting required.
  3. Verrouillage mécanique & Accessoires: Cross-brand accessories not interchangeable. Reversing interlock modules and side-mounted auxiliary contacts cannot be mixed.

❗ Quick Selection Recommendation

Direct replacement for project, haute compatibilité: Schneider LC1D12P7

Cost reduction with domestic product: CHNT NXC-12 11 AC230V

Overseas project, wide voltage requirement: ABB AF12-30-11-13

Siemens 3RT2024-1AP00 (S0 Frame) Dimensions de montage

Unité: mm

Dimensions hors tout

Largeur W:45

Hauteur H:85

Profondeur D:97 (from DIN rail backplate to front of terminals)

Méthodes de montage

  1. Montage sur rail DIN: Rail DIN standard de 35 mm (VOTRE UN 60715), clip-on installation
  2. Fixation par vis: Can also be plate-mounted directly on backplate (without rail)

Orientation de montage: ±180° rotation on vertical plane; ±22.5° tilt forward/backward allowed

Cabinet Clearance for Heat Dissipation

Installation côte à côte: 0mm jeu (can be mounted tightly together)

Minimum top, bottom and front clearance: 10mm

Clearance to earthed metal parts: ≥6mm laterally, ≥10mm top/bottom/front

⚠️ Dimension change after adding accessories (Important for cabinet cutout design)

  1. Front-mounted auxiliary contact block: Largeur & height unchanged, depth increases by 44mm
  2. Contacts auxiliaires latéraux: Hauteur & profondeur inchangée, width increases

This unit has built-in 1NO+1NC auxiliary contacts; dimension remains 45×85×97 without extra accessories.

Poids

Poids net: 0.405kilos

Référence de remplacement

Schneider LC1D12P7 also has 45mm width, compatible DIN rail position; but depth varies slightly. Double-check depth for cabinet retrofit with limited depth.